FLAME CURRENT MEASUREMENT - honeywell.cz

Application note AN 3. ENAR--9003 0001R0--NE FLAME CURRENT MEASUREMENT Whatis flame current When two electrodes are placed side by side in the flame a...

44 downloads 827 Views 96KB Size
Application note AN 3.

FLAME CURRENT MEASUREMENT What is flame current When two electrodes are placed side by side in the flame and if they are connected to an ac voltage source, an ac current will flow. Conduction in the flame takes place because the flame itself is ionised. The relatively large and heavy positive particles in the flame, called ions, are attracted to the electrode that is negative. The small and ligth negative particles in the flame, called electrons, are attracted by the positive electrode. If both electrodes are equal, current in both halves of the sine is equal (see fig. 1.).

Flame electrode Flame Burner

5 ←A

− 0

+

5 ←A

Fig. 1. Principle of ionisation flame safeguard

This principle can be used for flame sensing, by making the two electrodes unequal. If one electrode is at least 4 times larger than the other, the current in both halves of the sine will not be equal. This is caused by the difference in mobility due to size and weigth of the positive and negative particles. In practice in most cases the main burner is used as the large electrode. If the large electrode is positive, the small electrons are easily attracted by it. On the contrary, the heavy ions do not easily come in contact with the small electrode. This limits the current (see fig. 2.)

The other way around, ions are easily captured by the large electrode and also the electrons by the small electrode, so current is not limited (see fig. 3.)

− Ions

Electrons

+ + 0



1 ←A Fig. 2. Flame signal during negative half--wave

+ Ions

Electrons



5 ←A

+ 0



Fig. 3. Flame signal during positive half--wave

In figure 4. the current signal during one sine wave is shown. Because positive and negative half wave are unequal, a dc current is the result. This is the signal on which flame sensing is based and which can be in the range of 0.5 ←A to several tens of ←A depending on applied voltage, position in the flame and measuring circuit.

5 ←A

1 ←A Fig. 4. Flame signal during full wave

ENAR--9003 0001R0--NE

How can it be measured The flame current can be measured with a common multimeter measuring mV across a 1 Kτ resistor in series with the electrode, giving 1 mV per ←A. (see fig. 5.) 1 Kτ

Electrode cable

Fig. 5.

What protection is needed Ignition controls can be differentiated in dual rod systems and single rod systems. Dual rod systems Dual rods systems have separate electrodes for ignition and flame sensing and a multimeter can be connected to the flame sensing electrode without any problem. Single rod systems Single rod systems use one electrode for ignition and sensing. A multimeter connected to the electrode will get disturbed and it’s very likely that it gets damaged by the high voltage ignition peaks. To avoid this problem, a circuit was designed to be able to measure flame current without risk of damage. (see fig. 6.) Important part of the protection is the so called spark gap A circuit like this, in combination with a battery powered digital panel meter, is in use now for many years in the Application Center of Honeywell Combustion Control Center in Emmen without being damaged in single rod systems. Spark electrode

Spark gap 230V

R1 43K

R2 2k2

R6 464K R5

43K R3

2k2 R4

10k

C1

820n

D1 C2

100V

D3

20n

DVM

100V

464K R7

1 ←A = 10 mV

D2

D4

Igniter Diode D1 t/m D4: type 1N4148 Spark gap: Siemens B1--A230 Fig. 6. For suggestions or comments, please contact the Application Center or send an E--mail to: [email protected]

Combustion Controls Center Europe Honeywell BV Application Center Phileas Foggstraat 7, Emmen P.O. Box 83 7800 AB Emmen NL--The Netherlands Tel: +31 (0)591 6959 11 Fax: +31 (0)591 6952 00

ENAR--9003 0001R0--NE

2