Method Statement Static Pile Load Test - i-astm.com

1 Method Statement FOR Static Pile Load Test (Compression Test,Tension Test and Lateral Test) PREPARED BY...

17 downloads 621 Views 433KB Size
Method Statement FOR

Static Pile Load Test (Compression Test,Tension Test and Lateral Test)

PREPARED BY

1

METHOD STATEMENT FOR COMPRESSION, TENSILE AND LATERAL PILE LOAD TEST

PROJECT INFORMATION Owner

:

……………………………..

Client

:

……………………………..

Main Contractor

:

…………………………….

Contractor

:

…………………………….

Location

:

…………………………….

TEST PILE INFORMATION Pile No. 385

Pile No. 368

Pile No. 416

Pile Type

40 x 40 Driven

40 x 40 Driven

40 x 40 Driven

Pile Tip

4.2 m.

4.2 m.

4.2 m.

Pile Top

0.0 m.

0.0 m.

0.0 m.

Design Load

65 tons

15 tons

7 tons

Maximum Test Load (200 % of design Load)

130 tons

30 tons

14 tons

Test Type

Axial Compression Test

Axial Tension Test

Lateral Test

Anchor Piles

367, 368, 416, 417

367, 369

432, 417, 385

Testing Standard

ASTM D1143-81 ASTM D3689-90 ASTM D3966-90 (Reapproved 1994) (Reapproved 1995) (Reapproved 1995)

2

1.0 TESTING APPARATUS 1.1

Reaction Beam The steel girders will be laid across the test pile with system set up similar to that shown in Appendix A.

1.2

Hydraulic Jacks Axial Compressive Test

:

Axial Tension Test

:

Lateral Test

:

One hydraulic jack (1x400) ton capacity will be provided on top of the pile head as loading apparatus. One hydraulic jack (1x165) ton capacity will be provided on top of the pile head as loading apparatus. One hydraulic jack (1x59) ton capacity will be provided on the side of the pile head as loading apparatus.

1.3

Ball Bearing To provide non-eccentric load to the pile head, a ball bearing shall be inserted in between the reaction beam and the hydraulic jack.

1.4

Dial gauges Four dial gauges (Mitutoyo brand) will be provided to monitor the pile movements by mounting between the pile head and reference beams. The micrometer has a range of 0-50 mm and an accuracy of 0.01 mm.

1.5

Reference Beam Two reference beams (channel 125x65x5 mm) will be cross-connected and laid on support, firmly embedded in ground with one end fixed and the other end freed.

1.6

Leveling instrument Relative movements of the test pile head, reference beam and anchor pile will be checked by a Shokisha precise leveling instrument with an accuracy of 0.01 mm. Readings will be made on ruler scale fixed on the reading points (1 point at pile head, 2 points at reference beams and 1 point at each anchor pile).

2.0 TEST PROCEDURE 2.1

Compression Pile Load Test

The test shall conform to the modified ASTM D 1143-81(Reapproved 1994) item 5.0 “Standard Loading Procedure” with load sequence in percentage of design load. Three cycles of test will be performed. Cycle 1 (maximum to 100% of the design load) A. B.

C. D.

E.

The load will be added gradually by increasing from initial 0 to 25%, 50%, 75%, and 100% of the design load. When each load increment will be achieved, the next load increment will be added only when the settlement rate will be less than 0.25 mm per hour or after 2 hours, whichever shall occur first. At each load increment, load, settlement and time will be recorded at 1, 2, 4, 8, 15, 30, 60, 90, 120, 240 minutes and every 2 hours with an accuracy of at least 0.01 mm. The maximum load will be kept constant for at least 24 hours and then reduced to 75%, 50%, 25% and 0% of the design load, respectively. Each load will be maintained until the rate of settlement would not be greater than 0.25 mm per hour or after two hours, whichever shall occur first. At "0" load, rebound movement will be recorded at 1, 2, 4, 8, 15, 30, 40, 60 minutes and every hour thereafter until a constant settlement will be reached.

Cycle 2 (QUICK TEST, maximum to 200% of the design load) 3

A. B.

The load will be added gradually by increasing from initial 0 to 25%, 50%, 75%, 100%, 125%, 150%, 175% and 200% of the design load. When each load increment will be achieved, the next load increment will be added every after 5 minutes..

C. At each load increment, load, settlement and time will be recorded at 1 and 5 minutes with an accuracy of at least 0.01 mm. D. The load will then be reduced to 175%, 150%, 125%, 100%, 75%, 50%, 25% and 0% of the design load, respectively E. At "0" load, rebound movement will be recorded at 1, 2, 4, 8, 15, 30, 40, 60 minutes and every hour thereafter until a no further settlement will be experienced. F. The test pile will be considered failure when a rapid progressive movement of the pile in the direction of loading under a constant load or physical failure of the test pile is observed or a settlement of more than 15% of the diagonal dimension of the pile, which is equivalent to 90 mm. 2.2

Tension Pile Load Test

The test shall conform to the ASTM D 3689-90 (Reapproved 1995) “Standard Test Method for Individual Piles Under Static Axial Tensile Load.” with load sequence as explain below. The test will be conducted until the pile exhibit signs of failure. Cycle 1 (maximum to 100% of the design load) A. B.

C. D.

E.

The load will be added gradually by increasing from initial 0 to 25%, 50%, 75%, and 100% of the design load. When each load increment will be achieved, the next load increment will be added only when the settlement rate will be less than 0.25 mm per hour or after 2 hours, whichever shall occur first. At each load increment, load, settlement and time will be recorded at 1, 2, 4, 8, 15, 30, 60, 90, 120, 240 minutes and every 2 hours with an accuracy of at least 0.01 mm. The maximum load will be kept constant for at least 24 hours and then reduced to 75%, 50%, 25% and 0% of the design load, respectively. Each load will be maintained until the rate of settlement would not be greater than 0.25 mm per hour or after two hours, whichever shall occur first. At "0" load, rebound movement will be recorded at 1, 2, 4, 8, 15, 30, 40, 60 minutes and every hour thereafter until a constant settlement will be reached.

Cycle 2 (QUICK TEST, maximum to 200% of the design load) A. B.

The load will be added gradually by increasing from initial 0 to 25%, 50%, 75%, 100%, 125%, 150%, 175% and 200% of the design load. When each load increment will be achieved, the next load increment will be added every after 5 minutes..

G. At each load increment, load, settlement and time will be recorded at 1 and 5 minutes with an accuracy of at least 0.01 mm. H. The load will then be reduced to 175%, 150%, 125%, 100%, 75%, 50%, 25% and 0% of the design load, respectively I.At "0" load, rebound movement will be recorded at 1, 2, 4, 8, 15, 30, 40, 60 minutes and every hour thereafter until a no further settlement will be experienced. J. The test pile will be considered failure when a rapid progressive movement of the pile in the direction of loading under a constant load or physical failure of the test pile is observed or a settlement of more than 4

15% of the diagonal dimension of the pile, which is equivalent to 90 mm. 2.3

Lateral Pile Load Test

The test shall conform to the ASTM D 3966-90 “Standard Test Method for Individual Piles Under Lateral Load.” with load sequence as explain below. The test will be conducted until the pile exhibit signs of failure. A. The load will be added gradually by increasing from initial 0 to 25%, 50%, 75%, 100%, 125%, 150%, 170%, 180%, 190% and 200% of the design load. B. When each load increment will be achieved, the next load increment will be added after each load duration shown in Table 3. C. At each load increment, load and time will be recorded at 1, 5, 10 minutes with an accuracy of at least 0.01 mm. D. The test pile will be considered failure when a rapid progressive movement of the pile in the direction of loading under a constant load or physical failure of the test pile is observed. During the load test, records including plots of load vs. time and load vs. settlement will be maintained progressively.

3.0 RESULTS OF TEST The test results will then be reported in the form of: x x x x x

Time, load, pile head movements, settlements and reference beam movements. Load-settlement curve. Time-settlement curve. Time-load curve. Report and recommendations on the ultimate pile capacity.

5

Fc'= 400 ksc. Pile Dia.= 0.46 m. Q= 270 Tons L= 12.8 m. A= 0.16 sq.m. Ec= 29,427 Mpa Ec= 3.00E+06 Tons/sq.m. Settle-1= 7.02 mm. Settle-1= 2.81 inch Settle-2= 0.50 inch Settle-2= 1.27 mm. Settle-3= 0.14 inch Settle-3= 0.35 mm. Total Settle= 3.44 inch Davidson Offset Line Limit= 3.44 inch Davidson Offset Line Limit= 8.75 mm.

ESTIMATION OF ULTIMATE LOAD FROM PILE LOAD TEST BY DAVISSON METHOD

APPENDIX A TABLES, FIGURES & DESIGN CALCULATIONS

Table 1 Schedule of Loading

K a e n g K h o i 2 P o w e r P la n t (C o m p r e s s i o n T e s t i n g ) P il e N o . 385 Design Load = 65 Tons

FS = 2

Test Load = 130 Tons

Hydraulic Jack No./s 905 CYCLE 1: Date 3-Jul

4-Jul

CYCLE 2: Date 4-Jul

Maximum to 100% of the design load. Start Time 09:00 10:00 11:00 12:00 13:00 13:00 14:00 15:00

Interval (hours) 1 1 1 1 24 1 1 2

Load (Tons) 16.3 32.5 48.8 65.0 48.8 32.5 16.3 0.0

Pressure (Bars) 18.0 34.0 50.1 66.1 56.0 39.9 23.8 0.0

Remarks (%) 25% 50% 75% 100% 75% 50% 25% 0%

QUICK TEST; Maximum to 200% of the design load. Start Time 17:00 17:05 17:10 17:15 17:20 17:25 17:30 17:35 17:40 17:45 17:50 17:55 18:00 18:05 18:10 18:15

Interval (min) 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 120

Load (Tons) 16.3 32.5 48.8 65.0 81.3 97.5 113.8 130.0 113.8 97.5 81.3 65.0 48.8 32.5 16.3 0.0

Pressure (Bars) 18.0 34.0 50.1 66.1 82.1 98.1 114.1 130.2 120.4 104.3 88.2 72.1 56.0 39.9 23.8 0.0

Remarks (%) 25% 50% 75% 100% 125% 150% 175% 200% 175% 150% 125% 100% 75% 50% 25% 0%

Table 2 Schedule of Loading

K a e n g K h o i 2 P o w e r P l a n t (T e n s io n T e s t in g ) P il e N o . 368 Design Load = 15 Tons

FS = 2

Test Load = 30 Tons

Hydraulic Jack No./s 912 CYCLE 1: Date 6-Jul

7-Jul

CYCLE 2: Date 7-Jul

Maximum to 100% of the design load. Start Time 09:00 10:00 11:00 12:00 12:00 12:00 13:00 13:00

Interval (hours) 1 1 1 24 1 1 1 2

Load (Tons) 3.8 7.5 11.3 15.0 11.3 7.5 3.8 0.0

Pressure (Bars) 18.3 31.8 45.3 58.8 71.9 58.3 44.7 0.0

Remarks (%) 25% 50% 75% 100% 75% 50% 25% 0%

QUICK TEST; Maximum to 200% of the design load. Start Time 15:00 15:05 15:10 15:15 15:20 15:25 15:30 15:35 15:40 15:45 15:50 15:55 16:00 16:05 16:10 16:15

Interval (min) 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 120

Load (Tons) 3.8 7.5 11.3 15.0 18.8 22.5 26.3 30.0 26.3 22.5 18.8 15.0 11.3 7.5 3.8 0.0

Pressure (Bars) 18.3 31.8 45.3 58.8 72.3 85.9 99.4 112.9 126.4 112.8 99.2 85.6 71.9 58.3 44.7 0.0

Remarks (%) 25% 50% 75% 100% 125% 150% 175% 200% 175% 150% 125% 100% 75% 50% 25% 0%

Table 3 Schedule of Loading

K a e n g K h o i 2 P o w e r P l a n t (L a t e r a l T e s t i n g ) P il e N o . 416 Design Load = 7 Tons

FS = 2

Test Load = 14 Tons

Hydraulic Jack No./s 8 CYCLE 1: Date 10-Jul

Maximum to 100% of the design load. Start Time 09:00 09:10 09:20 09:35 09:55 10:15 10:35 10:55 11:15 11:35 12:35 12:45 12:55 13:05

Interval min 10 10 15 20 20 20 20 20 20 60 10 10 10

Load (Tons) 1.8 3.5 5.3 7.0 8.8 10.5 11.9 12.6 13.3 14.0 10.5 7.0 3.5 0.0

Pressure (Bars) 36.2 51.9 67.6 83.2 98.9 114.5 127.1 133.3 139.6 145.8 118.0 86.0 54.1 0.0

Remarks (%) 25% 50% 75% 100% 125% 150% 170% 180% 190% 200% 150% 100% 50% 0%

150.5

199.5

250.0

302.0

352.0

403.5

456.5

485.0

150

200

250

300

350

400

450

480

0.98578527

LOADING (Y) = 0.9858 * X + 2.0076

X Coefficient(s)

8

Degrees of Freedom

0.99994275

R Squared 10

1.18920934

Std Err of Y Est

No. of Observations

2.00762866

0.0

485.0

456.5

403.5

352.0

302.0

250.0

199.5

150.5

100.5

49.5

TOTAL (X)

Constant

Regression Output :

49.5

100.5

50

0

905

0

LOADING (Tons)

LOADING

450

400

350

300

250

200

150

448.0

395.5

345.5

295.0

244.0

193.5

143.5

93.5

43.5

0

0.99023655

7

9

0.99997388

0.74816827

7.72212362

0.0

448.0

395.5

345.5

295.0

244.0

193.5

143.5

93.5

43.5

TOTAL (X)

UNLOADING (Y) = 0.9902 * X + 7.7221

X Coefficient(s)

905

UNLOADING (Tons)

UNLOADING

Regression Output :

Degrees of Freedom

No. of Observations

R Squared

Std Err of Y Est

Constant

50

0 100

in bars (Y)

Gage Rdg.

Kaeng Khoi 2 Power Plant (Compression Testing)

100

in bars (Y)

Gage Rdg.

Calibrated

ASTM Testing Co., Ltd. 1032/217 Phaholyothin 18/1 Road, Bangkok 10900 : (662)+ 272-2474!5 : (662)+ 272-2475

CALIBRATION OF ONE HYDRAULIC JACK FOR STATIC PILE LOAD TESTING

ASTM

165.0

600

3.60596349

LOADING (Y) = 3.6060 * X + 4.7290

X Coefficient(s)

4

Degrees of Freedom

0.99988216

R Squared 6

2.27054121

Std Err of Y Est

No. of Observations

4.72899540

Regression Output :

138.0

500

0.0

165.0

138.0

109.0

82.0

53.5

27.0

TOTAL (X)

Constant

Calibrated

82.0

109.0

53.5

200

400

27.0

100

300

0

912

500

400

300

200

130.0

101.0

73.0

46.0

20.0

0

3.63468147

3

5

0.99953740

3.92681306

31.03357124

0.0

130.0

101.0

73.0

46.0

20.0

TOTAL (X)

UNLOADING (Y) = 3.6347 * X + 31.0336

X Coefficient(s)

912

UNLOADING (Tons)

UNLOADING

Regression Output :

Degrees of Freedom

No. of Observations

R Squared

Std Err of Y Est

Constant

0 100

in bars (Y)

Gage Rdg.

Kaeng Khoi 2 Power Plant(Tension Testing)

LOADING (Tons)

LOADING

0

in bars (Y)

Gage Rdg.

ASTM Testing Co., Ltd. 437-441 Kampangpeth III Road, behind Jatujak Park, Bangkok 10900 THAILAND : (662)+ 272-5966~7, 272-4565, 272-5973, 272-4582 : (662)+ 272-4583

CALIBRATION OF ONE HYDRAULIC JACK FOR STATIC PILE LOAD TESTING

ASTM

20.0

25.5

31.0

37.0

42.0

48.0

54.0

59.0

200

250

300

350

400

450

500

550

8.94812089

LOADING (Y) = 8.9481 * X + 20.5746

X Coefficient(s)

9

Degrees of Freedom

0.99974914

R Squared 11

2.76858801

Std Err of Y Est

No. of Observations

20.57458863

Regression Output :

15.0

150

9.0

3.0

0.0

59.0

54.0

48.0

42.0

37.0

31.0

25.5

20.0

15.0

TOTAL (X)

Constant

Calibrated

3.0

9.0

50

0

8

0

500

450

400

350

300

250

200

150

53.0

47.0

41.0

35.5

30.0

25.0

19.0

14.5

9.0

3.0

0

9.13006552

8

10

0.99932717

4.16489690

22.09718515

9.0

3.0

0.0

53.0

47.0

41.0

35.5

30.0

25.0

19.0

14.5

TOTAL (X)

UNLOADING (Y) = 9.1301 * X + 22.0972

X Coefficient(s)

8

UNLOADING (Tons)

UNLOADING

Regression Output :

Degrees of Freedom

No. of Observations

R Squared

Std Err of Y Est

Constant

50

0 100

in bars (Y)

Gage Rdg.

Kaeng Khoi 2 Power Plant(Lateral Testing)

LOADING (Tons)

LOADING

100

in bars (Y)

Gage Rdg.

ASTM Testing Co., Ltd. 437-441 Kampangpeth III Road, behind Jatujak Park, Bangkok 10900 THAILAND : (662)+ 272-5966~7, 272-4565, 272-5973, 272-4582 : (662)+ 272-4583

CALIBRATION OF ONE HYDRAULIC JACK FOR STATIC PILE LOAD TESTING

ASTM

367

368

Main Beam 385

416

417

Main Beam

Hydraulic Jack

Figure 1 Compression Test

KHAENG KHOI 2 Power Plant Project

ASTM TESTING CO., LTD.

Hydraulic Jack

Reaction Beam 367

368

369

Hydraulic Jack

367

368

369

Figure 2 Tension Test

KHAENG KHOI 2 Power Plant Project

ASTM TESTING CO., LTD.

385

416

417

432

Hydraulic Jack

1.0 m. 416

417

Figure 3 Lateral Test

KHAENG KHOI 2 Power Plant Project

ASTM TESTING CO., LTD.

APPENDIX B SAMPLE PRESENTATION OF RESULTS

Infratech ASTM CO., LTD.

APPENDIX C EQUIPMENT DETAILS

1

Infratech ASTM CO., LTD.

APPENDIX D COMPANY REFERENCE PROJECTS

2