November 2014 Type Y692 Gas Blanketing Regulator System

Bulletin 4.1:Y692 November 2014 D102032X012 www.fisherregulators.com Type Y692 Gas Blanketing Regulator System W5930-1 Figure 1. Type Y692 Low-Pressur...

1 downloads 366 Views 689KB Size
Bulletin 74.1:Y692 November 2014

Type Y692 Gas Blanketing Regulator System

W5930-1

Figure 1. Type Y692 Low-Pressure Gas Blanketing Regulator

Introduction

Features

An Accu-Pressure™ Gas Blanketing Regulator System reduces a high-pressure gas, such as Nitrogen, to maintain a protective environment above any liquid stored in a tank or vessel when the liquid is being pumped out. Also when the vessel is suddenly cooled, causing vapors inside the vessel to contract, the regulator system replaces the volume of contracting vapors with a volume of blanketing gas to prevent the internal vessel pressure from decreasing. In both cases, a slight positive vessel pressure prevents outside air, moisture and other contaminants from entering the vessel and the possible collapse of the vessel walls.

• Accuracy of Control—Large diaphragm areas provide more precise control even at low-pressure settings and the pitot tube also creates a dynamic boost that helps provide greater capacity. • Speed of Response—The downstream pressure is sensed directly by the diaphragm through the pitot tube providing quick response. • Ease of Installation—The Type Y692 is easy to install in the pipeline because no additional connections are required.

D102032X012

The Type Y692 (Figure 1) is a direct-operated regulator used for accurate pressure control on very low-pressure blanketing systems. Downstream pressure is sensed through a pitot tube installed in the lower casing of the regulator for units with internal pressure registration or through a downstream control line for units with external pressure registration. The Type Y692 is available in NPS 1-1/2 and 2 / DN 40 and 50 body sizes.

• Ease of Inspection and Maintenance—The union nut connection between the body and actuator permits access to the disk and orifice by only removing the diaphragm casing assembly without removing the body from the line.

www.fisherregulators.com

Bulletin 74.1:Y692 Specifications This section lists the specifications of theType Y692 Gas Blanketing Regulator System. Factory specification, such as spring range and orifice size are stamped on the nameplate fastened on the regulator at the factory. Available Configurations Direct-operated pressure reducing regulator with external or internal pressure registration with seven outlet (control) pressure ranges from 1 in. w.c. to 7 psig / 2 mbar to 0.48 bar. Available in NPS 1-1/2 and 2 / DN 40 and 50 body sizes. Body Sizes and End Connection Styles(1) Cast Iron: NPS 1-1/2 / DN 40, NPT, NPS 2 / DN 50, NPT or CL125 FF Steel: NPS 1-1/2 or 2 / DN 40 or 50, NPT, SWE, CL150 RF, CL300 RF or PN 16/25/40  Stainless steel: NPS 1-1/2 or 2 / DN 40 or 50, NPT, CL150 RF, CL300 RF or PN 16/25/40 Maximum Inlet Pressure(2) 150 psig / 10.3 bar Maximum Outlet (Casing) Pressure(2) 15 psig / 1.0 bar Maximum Operating Outlet (Control) Pressure to Avoid Internal Part Damage(2) 3 psig / 0.21 bar above outlet (control) pressure setting Control Pressure Ranges(2) See Table 1 Flow Capacities See Table 5 Relief Sizing Coefficients See Table 6 Orifice Size See Table 6 Pressure Registration Internal (standard) or External Spring Case Connection 1/4 NPT

Temperature Capabilities(2) Nitrile (NBR): -20 to 180°F / -29 to 82°C Fluorocarbon (FKM): 0 to 300°F / -18 to 149°C Perfluoroelastomer (FFKM): -20 to 300°F / -29 to 149°C EthylenePropylene (EPDM): -20 to 275°F / -29 to 135°C IEC Sizing Coefficients XT: 0.775 FD: 0.50 FL: 0.89 Approximate Weights Cast Iron Body: 45 lbs / 20 kg Steel/Stainless steel Body: 57 lbs / 26 kg Canadian Registration Number (CRN) Approved PED (Pressure Equipment Directive) Category The Type Y692 may be used as a safety accessory with pressure equipment in the PED 97/23/EC Category I. Construction Materials Body, Union Nut, Spring Case and Lower Casing Assembly: Cast iron, WCC steel, CF8M Stainless steel  Control Spring, Control Spring Seat, Split Ring and Diaphragm Plate: Plated steel Diaphragm: Nitrile (NBR) (standard), Fluorocarbon (FKM), Ethylenepropylene (EPDM), Silicone (VMQ)  O-rings: Nitrile (NBR), Fluorocarbon (FKM), Perfluoroelastomer (FFKM), Ethylenepropylene (EPDM)  Orifice, Pusher Post, Pusher Post Connector, Lever Assembly, Stem and Pitot Tube: Stainless steel Gasket: Composition Disk Assembly: Nitrile (NBR) and Stainless steel, Fluorocarbon (FKM) and Stainless steel, Polytetrafluoroethylene (PTFE) and Stainless steel or Ethylenepropylene (EPDM) and Stainless steel

1. Fabricated by using slip-on flanges and socket welding nipples into body. 2. The pressure/temperature limits in this Bulletin and any applicable standard limitation should not be exceeded.

2

Bulletin 74.1:Y692 Table 1. Control Pressure Ranges CONTROL PRESSURE RANGE WITH CASE BARREL POINTED DOWN

Light Spring Assembly Heavy spring Assembly

1 to 3 in. w.c. / 2 to 7 mbar(2)(3) 3 to 11 in. w.c. / 7 to 27 mbar(2)(4) 6.5 in. w.c. to 1.2 psig / 16 mbar to 83 mbar(5) 0.7 to 2 psig / 48 mbar to 0.14 bar 1 to 3.2 psig / 69 mbar to 0.22 bar 2 to 5.5 psig / 0.14 to 0.38 bar 4 to 10 psig / 0.28 to 0.69 bar

CONTROL SPRING COLOR CODE

CONTROL SPRING PART NUMBER

Brown Iridite Green Blue Orange Silver with green stripe Silver

1D892527022 0B019727052 0B019427052 0B019627032 0A081127202 0Y066427022 1H802427032

SPRING WIRE DIAMETER In. mm 0.109 2.77 0.148 3.76 0.187 4.75 0.225 5.71 0.250 6.35 0.363 9.22 0.406 10.3

SPRING FREE LENGTH In. mm 6.12 155 6.00 152 6.00 152 6.00 152 6.00 152 6.00 152 6.00 152

1. Install with spring case pointing down to achieve low setpoints in these spring ranges. 2. Do not use Fluorocarbon (FKM) diaphragm with these springs at diaphragm temperature lower than 60°F / 16°C. 3. Installation with spring case pointing up will change outlet (control) pressure range to 3 to 5 in. w.c. / 7 to 12 mbar. 4. Installation with spring case pointing up will change outlet (control) pressure range to 5.75 to 14 in. w.c. / 14 to 35 mbar. 5. Installation with spring case pointing up will change outlet (control) pressure range to 7.5 in. w.c. to 1.3 psig / 19 to 90 mbar.

Table 2. Flow Rate Conversion(1) MULTIPLY MAXIMUM PUMP RATE OUT

BY

TO OBTAIN

U.S. GPM U.S. GPH m3/hr Barrels/hr Barrels/day

8.021 0.1337 1.01 5.615 0.2340

SCFH SCFH Nm3/H SCFH SCFH

1. Gas flow of blanketing gas to replace liquid pumped out.

Table 3. Conversion Factors (for converting Nitrogen flow rates to other gas flow rates) BLANKET GAS

SPECIFIC GRAVITY

CORRECTION FACTOR

Natural Gas

0.60

1.270

Air

1.00

0.985

Dry CO2

1.52

0.797

Correction Factor =

0.985 SG

Table 4. Gas Flow Required for Thermal Heating (Outbreathing) or Cooling (Inbreathing) per API 2000 (Interpolate for Intermediate size) VESSEL CAPACITY

AIR FLOW RATE REQUIRED

Barrel

Gallon

Liter

SCFH

Nm3/h

60 100 500 1000 2000

2500 4200 21,000 42,000 84,000

9500 16,000 79,500 159,000 318,000

60 100 500 1000 2000

1.6 2.7 1.3 26.8 53.6

3000 4000 5000 10,000 15,000

126,000 168,000 210,000 420,000 630,000

477,000 636,000 795,000 1,590,000 2,385,000

3000 4000 5000 10,000 15,000

80.4 107 134 268 402

20,000 25,000 30,000 35,000 40,000

840,000 1,050,000 1,260,000 1,470,000 1,680,000

3,180,000 3,975,000 4,769,000 5,564,000 6,359,000

20,000 24,000 28,000 31,000 34,000

536 643 750 831 911

45,000 50,000 60,000 70,000 80,000

1,890,000 2,100,000 2,520,000 2,940,000 3,360,000

7,154,000 7,949,000 9,539,000 11,129,000 12,718,000

37,000 40,000 44,000 48,000 52,000

992 1072 1179 1286 1394

90,000 100,000 120,000 140,000 160,000

3,780,000 4,200,000 5,040,000 5,880,000 6,720,000

14,308,000 15,898,000 19,078,000 22,437,000 25,437,000

56,000 60,000 68,000 75,000 82,000

1501 1608 1822 2010 2198

180,000

7,560,000

28,616,000

90,000

2412

3

Bulletin 74.1:Y692

Type Y692

Type Y692

VENT VALVE

BLOCK VALVE

SUPPLY PRESSURE

VENT VALVE

VENT POINTED DOWNWARD

BLOCK VALVE

T

GAS BLANKETING PRESSURE

July 2007

Type Y692

INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE

LIQUID

TYPE Y692 WITH INTERNAL REGISTRATION

Type Y692

VENT VALVE

BLOCK VALVE INLET PRESSURE

CONTROL PRESSURE SUPPLY (OUTLET PRESSURE)

PRESSURE ATMOSPHERIC PRESSURE

VENT VALVE

VENT POINTED DOWNWARD

BLOCK VALVE

GAS BLANKETING PRESSURE

LIQUID

TYPE Y692 WITH EXTERNAL REGISTRATION A6340

INLET PRESSURE CONTROL PRESSURE (OUTLET PRESSURE) ATMOSPHERIC PRESSURE

INLET PRESSURE PRESSURE Figure OUTLET 2. Type Y692 Operational Schematics ATMOSPHERIC PRESSURE ONTROL PRESSURE (OUTLET PRESSURE)

LET PRESSURE

TMOSPHERIC PRESSURE

4

Bulletin 74.1:Y692 Principle of Operation

Installation

The Type Y692 Gas Blanketing Regulator reduces a high-pressure gas to maintain a positive low-pressure of blanket gas over a stored liquid when the liquid is being pumped out of the vessel (see Figure 2). Also when the vessel (or tank) is suddenly cooled, causing vapors to contract, the regulator replaces the volume of contracting vapors with a volume of blanketing gas to prevent the internal vessel pressure from decreasing. In both cases, a positive vessel pressure prevents outside air from entering the vessel and reduces the possibility of atmospheric pressure collapsing the vessel.

Install the Type Y692 regulator with the spring case barrel pointed down. This will assure that the lowest set pressure shown in Table 1 is achieved. Flow through the regulator body is indicated by the flow arrow cast on the body. If a block valve is required, install a full flow valve between the regulator and the blanketed vessel.

Gas blanketing regulators respond to a slight decrease in internal vessel pressure by throttling open to increase the flow rate of gas into the vessel. When the vessel’s liquid level has been lowered to the desired point and the vapor pressure re-established, the regulator throttles closed. When the liquid level drops and vessel pressure decreases below the setting of the control spring, the spring force on the diaphragm opens the disk assembly to supply the required flow of gas to the vessel. When vessel pressure has been satisfied, control pressure tends to increase slightly, acting on the diaphragm. When the control (vessel) pressure exceeds the control spring setting, the diaphragm moves to close the disk assembly. The Type Y692 Gas Blanketing Regulator provides a constant set pressure for accurate gas blanketing. When vessel pressure decreases below the control spring setpoint, the force of the spring moves the disk away from the orifice allowing gas to flow into the vessel. As the vessel pressure increases, the increase is sensed by the diaphragm through the pitot tube or control line. This movement of the diaphragm causes the disk to move toward the orifice, decreasing the flow of blanketing gas. When the vessel pressure reaches the system setpoint, the disk will seat against the orifice shutting off the flow of gas.

Sizing Tank Blanketing Systems When sizing a gas blanketing regulator system for a low pressure blanketing application, you must consider the replacement of blanketing gas required for the liquid loss during pump out of the vessel and also the condensation/contraction of vessel vapors during atmospheric thermal cooling.

Direct Displacement The direct displacement method should be used with extreme caution. The direct displacement method determines the amount of blanketing gas required to replace liquid pumped out of the tank. Direct displacement does not allow for fluctuating temperature or other factors that may affect pressure in the vapor space. This method is typically applied to tanks operating at constant temperature and containing non-flammable, non-volatile products.          Qtotal = Qpump where, Qtotal = Required Flow Rate Qpump = Required Flow Rate to replace pumped out     liquid from Table 1

5

Bulletin 74.1:Y692 API 2000 The American Petroleum Institute Standard 2000 (API 2000) sizing method accounts for liquid pump-out as well as contraction of tank vapors due to cooling. When using API methods:

Qtotal = Qpump + Qthermal

where,

tank, product and personnel in cases of equipment failure, fire exposure or other conditions that could cause the tank pressure or vacuum to exceed operating limits. Sizing can be done by following these steps:   1. D  etermine the gas flow rate required to replace the liquid being pumped out (see Table 2).

Qpump = R  equired Flow Rate to replace pumped out liquid from Table 1

  2. U  sing the established procedures from the American Petroleum Institute Standard 2000 (API 2000), determine the gas flow rate due to “inbreathing” caused by atmospheric thermal cooling (see Table 4).

Qthermal = Required Flow Rate due to thermal cooling. See Thermal Equations 1 to 4 below or Table 2.

  3. A  dd the requirements of 1 and 2 and select the regulator size, based on total capacity required from Table 6.

Qtotal

= Required Flow Rate

Thermal Equations For tanks up to 840,000 gallons / 3179 m3 capacity, use one of the following equations: Equation 1: Qthermal [SCFH Air] = Vtank x 0.0238 Equation 2: Qthermal [SCFH Nitrogen] = Vtank x 0.0238 x 1.015 Equation 3: Qthermal [Nm /h Air] = Vtank x 0.169 3

Equation 1: Qthermal [Nm3/h Nitrogen] = Vtank x 0.169 x 1.015 where,   For Equations 1 and 2: Vtank = tank volume, gallons   For Equations 3 and 4: Vtank = tank volume, m3 For tanks greater than 840,000 gallons / 3179 m3 capacity: See Table 2. Depending on the method, there can be a significant difference in the calculated required capacity. No matter which method is used, the tank must be equipped with supplemental venting to protect the

6

Sample sizing problem for blanketing applications: Service Conditions: Vessel Capacity . . . . . . . . . 42,000 gallons / 159,000 L Pump In/Out Capacity . . 150 gallons/minute / 570 L/m Inlet Pressure Source . . . . . 20 psig / 1.4 bar Nitrogen Desired Blanket Setpoint . . . . . . . . 1 in. w.c. / 2 mbar Sizing and Selection Methodology:   1. From Table 2 the desired air flow rate due to pump out equals 150 GPM x 8.021 = 1203 SCFH / 32.2 Nm3/h air.   2. From Table 4, the required air flow due to thermal cooling = 1000 SCFH / 26.8 Nm3/h air.   3. Total flow required for pump out and thermal cooling is 1203 + 1000 = 2203 SCFH / 59.0 Nm3/h air.   4. Convert to nitrogen by dividing the total air flow by the square root of the specific gravity of nitrogen: 2203 ÷ 0.97 = 2248 SCFH / 60.2 Nm3/h nitrogen (See Table 3 for the conversion).   5. From Table 5, a Type Y692 in either an NPS 1-1/2 and 2 / DN 40 and 50 body sizes and a 3/8 in. / 9.5 mm orifice will flow 3620 SCFH / 97.0 Nm3/h nitrogen at 20 psig / 1.4 bar inlet pressure. This satisfies the required flow of 2248 SCFH / 60.2 Nm3/h nitrogen.

Bulletin 74.1:Y692 Capacity Information

Ordering Information

Table 5 gives the typical regulating capacities at selected inlet pressures and outlet (control) pressure settings. Flows are in SCFH (60°F and 14.7 psia) of 0.97 specific gravity nitrogen. For gases of other specific gravities, multiply the given capacity of nitrogen by 0.985 and divide the given capacity by the square root of the appropriate specific gravity of the gas required. Then, if capacity is desired in normal cubic meters per hour at 0°C and 1.01325 bar, multiply SCFH by 0.0268.

When ordering, specify:

To determine wide-open flow capacities for relief sizing, use the following formula:

  1. Type of gas being controlled (nitrogen fuel gas, etc.); list any factors such as impurities in the gas that may affect compatibility of the gas with the regulator trim parts.   2. Specific gravity of the gas   3. Temperature of the gas   4. Range of flowing inlet pressures to regulator   5. Flow rates      a) Minimum controlled flow      b) Normal flow

Q  =

520   CgP1SIN GT

3417 C1

P P1

DEG

where,   Cg = gas sizing coefficient from Table 6   C1 = Cg /Cv  or 35 from Table 6    G = gas specific gravity (air = 1.0)   P1abs = inlet pressure, psia (add 14.7 psi to gauge inlet         pressure to obtain absolute inlet pressure)    Q = flow rate, SCFH    T = absolute temperature in °Rankine of gas at inlet

     c) Maximum flow   6. Line size and end connection size of adjacent piping. Adjacent downstream piping must be the same size as the regulator body or longer.   7. Vessel size

7

Bulletin 74.1:Y692 Table 5. Blanketing Regulating Capacities in SCFH / Nm3/h of 0.97 Specific Gravity Nitrogen BODY SIZE

OUTLET PRESSURE RANGE(1), ACCURACY AND SPRING COLOR

OUTLET PRESSURE SETTING

1 in. w.c. / 2 mbar 1 to 3 in. w.c. / 2 to 7 mbar -1 to 2 in. w.c. / -2 to 5 mbar Brown 3 in. w.c. / 7 mbar

3 to 11 in. w.c. / 7 to 27 mbar -1 to 2 in. w.c. / -2 to 5 mbar

7 in. w.c. / 17 mbar

Iridite 6.5 in. w.c to 1.2 psig / 16 to 83 mbar, Green or 0.7 to 2 psig / 48 mbar to 0.14 bar, Blue NPS 1-1/2 / DN 40

0.2 psig / 14 mbar 1 to 3.2 psig / 69 mbar to 0.22 bar 0.6 psig / 41 mbar

1.5 psig / 0.10 bar

3 psig / 0.21 bar

Orange 2 to 5.5 psig / 0.14 to 0.38 bar 0.5 psig / 34 mbar

5 psig / 0.34 bar

Silver with green stripe 2 to 5.5 psig / 0.14 to 0.38 bar 1 psig / 69 mbar

5 psig / 0.34 bar

Silver with green stripe 4 to 10 psig / 0.28 to 0.69 bar 1 psig / 69 mbar

10 psig / 0.69 bar

Silver 4 to 10 psig / 0.28 to 0.69 bar 2 psig / 0.14 bar Silver

10 psig / 0.69 bar

INLET PRESSURE

ORIFICE SIZE, IN. / mm 1/4 / 6.4

3/8 / 9.5

3/4 / 19

1 / 25

1-3/16 / 30

bar

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

2 5 10 20 40 60 80 100 125 150 2 5 10 20 40 60 80 100 125 150 0.5 1 2 5 13 25 50 100 150 2 6 14 30 50 150 3 7 14 30 50 150 10 15 20 35 60 75 100 10 15 20 35 60 75 100 15 20 25 40 60 75 100 15 20 25 40 60 75 100

0.14 0.34 0.69 1.4 2.8 4.1 5.5 6.9 8.6 10.3 0.14 0.34 0.69 1.4 2.8 4.1 5.5 6.9 8.6 10.3 0.03 0.07 0.14 0.34 0.9 1.7 3.4 6.9 10.3 0.14 0.41 0.97 2.1 3.4 10.3 0.21 0.48 0.97 2.1 3.4 10.3 0.69 1.0 1.4 2.4 4.1 5.2 6.9 0.69 1.0 1.4 2.4 4.1 5.2 6.9 1.0 1.4 1.7 2.8 4.1 5.2 6.9 1.0 1.4 1.7 2.8 4.1 5.2 6.9

360 680 1030 1580 2500 3410 4320 4510 4510 4510 360 680 1030 1580 2500 3410 4320 4510 4510 4510

9.7 18.2 27.6 42.3 67.0 91.4 116 121 121 121 9.7 18.2 27.6 42.3 67.0 91.4 116 121 121 121

970 1560 2350 3620 3620 3620

26.0 41.8 63.0 97.0 97.0 97.0

1750 2800 4210 4900 4900

46.9 75.0 113 131 131

3280 3880 3880 3700

87.9 104 104 99.2

4750 3650 3650

127 97.8 97.8

3650 2840

97.8 76.1

970 1560 2350 3620 3620 3620

26.0 41.8 63.0 97.0 97.0 97.0

1750 2800 4210 4900 4900

46.9 75.0 113 131 131

3280 3880 3880 3700

87.9 104 104 99.2

4750 3650 3650

127 97.8 97.8

3650 2840

97.8 76.1

330 470 770 1270 1850 3040 5370 6100

8.8 12.6 20.6 34.0 49.6 81.5 144 163

630 950 1580 2590 4100 6100 6100

16.9 25.5 42.3 69.4 110 163 163

870 1300 2520 4900 6100 6100

23.3 34.8 67.5 131 163 163

950 1340 2260 6070 6100 6100

25.5 35.9 60.6 163 163 163

1180 1810 3160 6100 6100

31.6 48.5 84.7 163 163

1330 2290 4730 6100

35.6 61.4 127 163

789 1740 3156 4890 7120 18,030

21.1 46.6 84.6 131 191 483

1260 2760 5050 8050 11,990

33.8 74.0 121 216 321

2050 4730 9470 13,360

54.9 127 254 358

2660 9790 12,500

71.3 182 335

3220 7530

86.3 202

1550 2370 4500 7020 17,250 950 1030 1380 1970 2920 3470 5130 1500 1890 2200 3310 5290 6390 8680 1023 1377 1652 2203 3148 3541 5193 1731 2125 2675 3934 5351 6531 8656

41.5 63.5 121 188 462 25.5 27.6 97.0 52.8 78.3 93.0 137 40.2 50.7 59.0 88.7 142 171 233 27.4 36.9 44.3 59.0 84.4 94.9 139 46.4 57.0 71.7 105 143 175 232

2370 3700 7380 10,750

63.5 99.2 198 288

3950 7020 11,680

106 188 313

2450 5130 7470

64.7 137 200

2840 6312

76.1 169

1180 1580 2200 2920 4730 5680

31.6 42.3 59.0 78.3 127 152

1810 2370 2920 4020

48.5 63.5 78.3 108

2200 2840 3310

59.0 76.1 88.7

2370 3310

63.5 88.7

2050 2760 3790 5130 7890 10,260

54.9 74.0 102 137 211 275

3230 4100 5130 7730

86.6 110 137 207

4100 5520 6310

110 148 169

4580 6310

123 169

1338 1967 2203 2912 4643 5666

35.9 52.7 59.0 78.0 124 152

1810 2597 3148 4720

48.5 69.9 84.4 127

2518 3148 4013

67.5 84.4 108

2990 4564

80.1 122

2518 3384 3777 5272 8656 10,230

67.5 90.7 101 141 232 274

3620 5115 6453 8656

97.0 137 173 232

4721 6295 7082

127 169 190

6295 7869

169 211

590 789 950 1420 2210 2760 3550 950 1180 1380 1970 3160 4100 5130 708 944 1102 1810 2361 2754 3541 1023 1259 1574 2282 2990 4013 5115

15.8 21.1 25.5 38.1 59.2 74.0 95.1 25.5 31.6 37.0 52.8 84.7 110 137 19.0 25.3 29.5 48.5 63.3 73.8 94.9 27.4 33.7 42.2 61.2 80.1 108 137

1. Spring ranges based on regulator installation with the spring case pointed down. - Light shaded areas show where indicated droop would be exceeded regardless of capacity. - Dark shaded areas show where maximum operating inlet pressure for a given orifice size is exceeded.

- continued -

8

1/2 / 13

psig

Bulletin 74.1:Y692 Table 5. Blanketing Regulating Capacities in SCFH / Nm3/h of 0.97 Specific Gravity Nitrogen (continued) BODY SIZE

OUTLET PRESSURE RANGE(1), ACCURACY AND SPRING COLOR

OUTLET PRESSURE SETTING

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

SCFH

Nm3/h

0.14 0.34 0.69 1.4 2.8 4.1 5.5 6.9 8.6 10.3

320 680 1030 1580 2500 3410 3650 3650 3650 3650

8.6 18.2 27.6 42.3 67.0 91.4 97.8 97.8 97.8 97.8

930 1560 2350 3620 4420 4420

24.9 41.8 63.0 97.0 118 118

1750 2800 4210 3450 3450

46.9 75.0 113 92.5 92.5

4000 6050 3650 3650

107 162 97.8 97.8

5010 4630 4060

134 124 109

5930 4260

159 114

1 in. w.c. / 2 mbar

2 5 10 20 40 60 80 100 125 150

0.14 0.34 0.69 1.4 2.8 4.1 5.5 6.9 8.6 10.3

320 680 1030 1580 2500 3410 3650 3650 3650 3650

8.6 18.2 27.6 42.3 67.0 91.4 97.8 97.8 97.8 97.8

930 1560 2350 3620 4420 4420

24.9 41.8 63.0 97.0 118 118

1750 2800 4210 3450 3450

46.9 75.0 113 92.5 92.5

4000 6050 3650 3650

107 162 97.8 97.8

5010 4630 4060

134 124 109

5930 4260

159 114

3 in. w.c. / 7 mbar

2 5 10 20 40 60 80 100 125 150

7 in. w.c. / 17 mbar

0.5 1 2 5 13 25 50 100 150

0.03 0.07 0.14 0.34 0.90 1.7 3.4 6.9 10.3

330 470 770 1270 1850 3040 5370 7890

8.8 12.6 20.6 34.0 49.6 81.5 144 211

630 950 1580 2590 4100 6700 7890

16.9 25.5 42.3 69.4 110 180 211

870 1300 2520 4900 7180 7890

23.3 34.8 67.5 131 192 211

950 1340 2260 6080 7890 7890

25.5 35.9 60.6 163 211 211

1180 1810 3160 7890 7890

31.6 48.5 84.7 211 211

1330 2290 4730 7890

36.5 61.4 127 211

1 psig / 69 mbar

2 6 14 30 50 150

0.14 0.41 0.97 2.1 3.4 10.3

1030 1970 3390 5130 7120

27.6 52.8 90.9 137 191

1340 2840 5130 8130 11,990

35.9 76.1 137 218 321

2450 5680 10,650 16,730

65.7 152 285 448

3230 7730 13,490

86.6 207 362

3390 8760

90.9 235

3 psig / 0.21 bar

3 7 14 30 50 150

0.21 0.48 0.97 2.1 3.4 10.3

1740 3310 5130 7500 19,820

46.6 88.7 137 201 531

2600 4180 7930 11,400

69.7 112 213 306

4730 770 14,480

127 206 388

2550 5880 10,450

68.3 158 280

3050 7140

81.7 191

0.69 1.0 1.4 2.4 4.1 5.2 6.9

590 789 950 1420 2210 2760 3550

15.8 21.1 25.5 38.1 59.2 74.0 95.1

950 1030 1380 1970 2920 3470 5130

25.5 27.6 37.0 52.8 78.3 93.0 137

1180 1580 2200 2920 4730 5680

31.6 42.3 59.0 78.3 127 152

1810 2370 2920 4020

48.5 63.5 78.3 108

2200 2840 2920

59.0 76.1 78.3

2370 3310

63.5 88.7

5 psig / 0.34 bar

10 15 20 35 60 75 100

0.69 1.0 1.4 2.4 4.1 5.2 6.9

950 1180 1380 1970 3160 4100 5130

25.5 31.6 37.0 52.8 84.7 110 137

1500 1890 2200 2050 5290 6390 8680

40.2 50.7 59.0 54.9 142 171 233

2050 2760 3790 5130 7890 10,260

54.9 74.0 102 137 207 275

4100 5520 6310

110 148 169

4100 5520 6310

110 148 169

4580 6310

123 169

5 psig / 0.34 bar

10 15 20 35 60 75 100

1.0 1.4 1.7 2.8 4.1 5.2 6.9

708 944 1102 1810 2361 2754 3541

19.0 25.3 29.5 48.5 63.3 73.8 94.9

1023 1377 1652 2203 3148 3541 5193

27.4 36.9 44.3 59.0 84.4 94.9 139

1338 1967 2203 2912 4643 5666

35.9 52.7 59.0 78.0 124 152

2518 3148 4013

67.5 84.4 108

2518 3148 4013

67.5 84.4 108

2990 4564

80.1 122

10 psig / 0.69 bar

15 20 25 40 60 75 100

1.0 1.4 1.7 2.8 4.1 5.2 6.9

1023 1259 1574 2282 2990 4013 5115

27.4 33.7 42.2 61.2 80.1 108 137

1731 2125 2675 3934 5351 6531 8656

46.4 57.0 71.7 105 143 175 232

2518 3384 3777 5272 8656 10,230

67.5 90.7 101 141 232 274

4721 6295 7082

127 169 190

4721 6295 7082

127 169 190

6295 7869

169 211

10 psig / 0.69 bar

15 20 25 40 60 75 100

1 to 3.2 psig / 69 mbar to 0.22 bar

Orange 2 to 5.5 psig / 0.14 to 0.38 bar

Silver with green stripe 2 to 5.5 psig / 0.14 to 0.38 bar

Silver with green stripe 4 to 10 psig / 0.28 to 0.69 bar 1 psig / 69 mbar Silver 4 to 10 psig / 0.28 to 0.69 bar 2 psig / 0.14 bar Silver

1-3/16 / 30

Nm3/h

0.2 psig / 14 mbar

1 psig / 69 mbar

1 / 25

SCFH

Iridite

0.5 psig / 34 mbar

3/4 / 19

Nm3/h

3 to 11 in. w.c. / 7 to 27 mbar

0.6 psig / 41 mbar

1/2 / 13

SCFH

Brown

NPS 2 / DN 50

3/8 / 9.5

bar

-1 to 2 in. w.c. / -2 to 5 mbar

6.5 in. w.c to 1.2 psig / 16 to 83 mbar, Green or 0.7 to 2 psig / 48 mbar to 0.14 bar, Blue

ORIFICE SIZE, IN. / mm 1/4 / 6.4

psig

1 to 3 in. w.c. / 2 to 7 mbar

-1 to 2 in. w.c. / -2 to 5 mbar

INLET PRESSURE

1. Spring ranges based on regulator installation with the spring case pointed down. - Light shaded areas show where indicated droop would be exceeded regardless of capacity. - Dark shaded areas show where maximum operating inlet pressure for a given orifice size is exceeded.

9

Bulletin 74.1:Y692

8.94 / 227

5.88 / 149 2.94 / 75 1/4 NPT DOWNSTREAM CONTROL LINE CONNECTION

10.38 / 264

17.44 / 443

NPT DIMENSIONS

8.94 / 227

A

10.38 / 264 IN. / mm

17.44 / 443

A - CAST IRON FLANGES ARE 10 IN. / 254 mm FACE-TO-FACE; STEEL, STAINLESS STEEL AND HASTELLOY® C FLANGES ARE 14 IN. / 356 mm FACE-TO-FACE.

FLANGED DIMENSIONS

Figure 3. Dimensions Table 6. Orifice Sizes and Coefficients for Relief Valve Sizing BODY SIZE NPS

1-1/2 and 2

ORIFICE SIZE DN

In.

mm

40 and 50

1/4 3/8 1/2 3/4 1 1-3/16

6.4 9.5 13 19 25 30

Hastelloy® C is a mark owned by Haynes International, Inc.

10

WIDE-OPEN Cv

WIDE-OPEN Cg

C1

1.51 3.14 5.43 11.9 20 26

53.0 111 190 415 700 910

35

Bulletin 74.1:Y692 Ordering Information Carefully review the Specifications section, then specify the desired selection on the Ordering Guide. If a pilot

setpoint is not requested, the regulator will be factory set at the approximate midrange.

Ordering Guide Body Size (Select One)     NPS 1-1/2 / DN 40     NPS 2 / DN 50 Body Material and End Connection Style (Select One) Cast Iron     NPT***     CL125 FF (NPS 2 / DN 50 body only)* WCC Steel CF8M Stainless Steel   NPT***         NPT***     SWE**          CL150 RF**     CL150 RF**      CL300 RF**     CL300 RF**      PN 16/25/40 RF*     PN 16/25/40* Spring Case Material (Select One)     Cast iron***     WCC steel***     CF8M Stainless steel** Diaphragm Case Material (Select One)     Cast iron***     WCC steel***   CF8M Stainless steel** Trim Material (Select One)     304 Stainless steel***       316 Stainless steel** Diaphragm Material (Select One)     Nitrile (NBR) (standard)***     Fluorocarbon (FKM)***     Ethylenepropylene (EPDM)***     Silicone (VMQ)***

Orifice Size (Select One)     1/4 in. / 6.4 mm***   3/4 in. / 19 mm***     3/8 in. / 9.5 mm***   1 in. / 25 mm***     1/2 in. / 13 mm***   1-3/16 in. / 30 mm*** Outlet Pressure Range (Select One)     1 to 3 in. w.c. / 2 to 7 mbar, Brown***     3 to 11 in. w.c. / 7 to 27 mbar, Iridite***    6.5 in. w.c. to 1.2 psig / 16 to 83 mbar, Green***     0.7 to 2 psig / 48 mbar to 0.14 bar, Blue***     1 to 3.2 psig / 69 mbar to 0.22 bar, Orange***    2 to 5.5 psig / 0.14 to 0.38 bar, Silver with Green stripe***     4 to 10 psig / 0.28 to 0.69 bar, Silver*** Pressure Registration (Select One)     Internal***  External** PTFE Diaphragm Protector (Optional)    Yes CRN (Canadian Registration Number) Required (Optional)    Yes PED (Pressure Equipment Directive) Conformity (Optional)    Yes Replacement Parts Kit (Optional)    Yes, send one replacement parts kit to match this order.

Disk Material (Select One)     Nitrile (NBR) (standard)***     Fluorocarbon (FKM)***   Polytetrafluoroethylene (PTFE)***   Ethylenepropylene (EPDM)***

11

Bulletin 74:1:Y692 Ordering Guide (continued)

Tank Blanketing Specification Worksheet

Regulators Quick Order Guide *** ** *

Readily Available for Shipment Allow Additional Time for Shipment Special Order, Constructed from Non-Stocked Parts. Consult your local Sales Office for Availability.

Availability of the product being ordered is determined by the component with the longest shipping time for the requested construction.

Application Specifications: Tank Size________________________________________________ Pump In Rate____________________________________________ Pump Out Rate__________________________________________ Blanketing Gas (Type and Specific Gravity)________________ Pressure Requirements: Maximum Inlet Pressure (P1max)___________________________ Minimum Inlet Pressure (P1min)____________________________ Control Pressure Setting (P2)______________________________ Maximum Flow (Qmax)_____________________________________ Accuracy Requirements:     0.25 in. w.c. / 0.6 mbar   0.5 in. w.c. / 1 mbar     1 in. w.c. / 2 mbar   2 in. w.c. / 5 mbar     Other Other Specifications: Is a vapor recovery regulator required?     Yes     No Special Material Requirements:   Ductile Iron   Steel   Stainless steel   Other ____________________________ Other Requirements:______________________________________ _________________________________________________________

Industrial Regulators

Natural Gas Technologies

TESCOM

Emerson Process Management Regulator Technologies, Inc.

Emerson Process Management Regulator Technologies, Inc.

Emerson Process Management Tescom Corporation

USA - Headquarters McKinney, Texas 75070 USA Tel: +1 800 558 5853 Outside U.S. +1 972 548 3574

USA - Headquarters McKinney, Texas 75070 USA Tel: +1 800 558 5853 Outside U.S. +1 972 548 3574

USA - Headquarters Elk River, Minnesota 55330-2445, USA Tels: +1 763 241 3238     +1 800 447 1250

Asia-Pacific Shanghai 201206, China Tel: +86 21 2892 9000

Asia-Pacific Singapore 128461, Singapore Tel: +65 6770 8337

Europe Selmsdorf 23923, Germany Tel: +49 38823 31 287

Europe Bologna 40013, Italy Tel: +39 051 419 0611

Europe Bologna 40013, Italy Tel: +39 051 419 0611 Chartres 28008, France Tel: +33 2 37 33 47 00

Asia-Pacific Shanghai 201206, China Tel: +86 21 2892 9499

Middle East and Africa Dubai, United Arab Emirates Tel: +971 4811 8100

Middle East and Africa Dubai, United Arab Emirates Tel: +971 4811 8100

For further information visit www.fisherregulators.com The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC, a business of Emerson Process Management. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.

©Emerson Process Management Regulator Technologies, Inc., 1994, 2014; All Rights Reserved