Product Data Sheet Edition 06, 2003 Identification no. GF01 SikaGrout® 215
Sikagrout® 215
Construction
Pumpable Non-Shrink Cementitious Grout Description
Sika Grout 215 if a non-shrink self levelling, cementitious grouting mortar with extended working time to suit local ambient temperature.
Uses
Sika Grout 215 is suitable for repairs to concrete structures and the following grouting works with clearance of 10mm or more: n Machine foundations n Rail beds n Columns in pre-cast construction n Concrete anchors n Bridge bearings n Cavities n Gaps n Recesses
Characteristics / Advantages
n Highly early strength n High ultimate stregth n Extended working time n Dense, non-shrink n Non-toxic, non-corrosive n Chloride and iron free n High final strength
Instruction for Use Surface Preparation
Surface Preparation Concrete surfaces should be clean, sound and free from oil, grease, cement laitance and all loosely adhering particles. Metal surfaces (iron and steel) should be free from scale, rust, oil and grease. Absorbent substrates must be saturated thoroughly, but there should be no standing water. Mixing The pre-mixed powder is added to water to suit the desired consistency. For flowable consistency, approximately 4.2 litres of water per bag is required. Mix mechanically for 2-3 mins with a slow speed drill (max. 500 RPM) until a smooth even consistency is achieved. Application After mixing., allow the mortar to rest for a while, stirring lightly to ensure that air displayed by the grouting is allowed to escape. When carrying out base plate grouting, ensure that sufficient pressure head is maintained to keep mortar flow uninterrupted. Make sure that the necessary formwork is firmly in place and kept water light. Sika Grout 215 may be placed in thickness up to a maximum of 50mm at one pour.Where large areas are to be placed, it is important to maintain a continuous flow throughout. It is necessary to organize the work sequence properly (manpower, materials, etc.) to ensure an uninterrupted flow. In such large areas, Sika Grout 215 may also be pumped. A heavy duty diaphragm pump is recommended for this purpose. Screw feed and piston pumps may also be used. Specific Application Grouting under base plate: Use flowable consistency Grouting Anchor bolts: Use trowellable consistency Grouting large volumes: For sections thicker than 50mm it is necessary to fill the Sika Grout 215 with graded 10mm silt free aggregate to minimize temperature rise. The quantity of aggregate should not exceed 1 part Sika Grout 215 by weight. For such mixes, a conventional concrete mixer and pump may be used. Cleaning Clean all tools and equipment with water immediately after use. Hardened mortar can only be mechanically removed.
1
SikaGrout ® -215 1/2
Construction
Important Recommendations
Use Sika Grout 215 for repairs to concrete structure and grouting only. Minimum Gap: 10mm Maximum Gap: 50mm Minimum Application Temperature: 10 0C At temperature lower than 20 0C setting time and stregnth gain will be slower. Cure exposed mortar surface for at least 3 days with Anitsol E curing compound or use other approved curing methods.
Coverage/Consumption (approx.)
Sika Grout Water (Litre) Volume Mortar
Performance
Flow (British Standard Cone): 280 - 320 mm after 3 minutes 260 - 300 mm after 30 minutes (Keep on stirring slightly) Comprehensive Strength in MPa (N/mm2): (Water content: 4.2 liters/25 kg bag. Testing & storge at 25 0 C under water) 1 day : 38 3 days : 45 7 days : 55 28 days : 70
1.84 kg 0.31 1 lit.
25 kg 4.2 13.6 lit.
74 x 25 kg bag 309 1 m3
Technical Data Form
Powder
Color
Grey
Bulk Density
1.64 kg/l
Wet Density
2.10 - 2.20 kg/l
Storage Condition
Store in a dry place
Shelf Life
15 months when unopened
Legal Notice
The information, and, in particular, the recommendations relating to the application and end-use of Sika products, are given in good faith based on Sika’s current knowledge and experience of the products when properly stored, handled and applied under normal conditions in accordance with Sika’s recommendations. In practice, the differences in materials, substrates and actual site conditions are such that no warranty in respect of merchantability or of fitness for a particular purpose, nor any liability arising out of any legal relationship whatsoever, can be inferred either from this information, or from any written recommendations, or from any other advice offered. The user of the product must test the product’s suitability for the intended application and purpose. Sika reserves the right to change the properties of its products. The proprietary rights of third parties must be observed. All orders are accepted subject to our current terms of sale and delivery. Users must always refer to the most recent issue of the local Product Data Sheet for the product concerned, copies of which will be supplied on request.
Sika Philippines, Inc. Unit A & B 888 Marcos Alvarez, Ave. Talon, Las Piñas City 1747 Philippines
2