Boiler Feedwater Oxygenated Treatment in Power Plants in China

Boiler Feedwater Oxygenated Treatment in Power Plants in China Zhigang Li, Wanqi Huang, Songyan Cao, and Hongbo Zhang

ABSTRACT This paper presents the development of the oxygenated treatment (OT) technique application in power plants in China. The oxide morphologies of boiler tubes (economizer and water wall) under three different feedwater treatment techniques – all-volatile treatment under reducing conditions (AVT(R)), all-volatile treatment under oxidizing conditions (AVT(O)) and oxygenated treatment (OT) – were analyzed, and it was found that the reddish brown Fe2O3 coating layer formed by oxygen in feedwater only extended as far as the economizer inlet section. This paper also has a detailed discussion about the CrO42– release phenomenon and demonstrates that the CrO42– detected in the steam cycle comes from sampling tubing and apparently does not originate from the boiler tube material.

INTRODUCTION The Status Quo of Oxygenated Treatment in China In the 1980s, the Thermal Power Research Institute (TPRI) realized the value of the oxygenated treatment (OT) technique, which was first proposed and implemented in Germany, and researched the technology both in the laboratory and by field testing. In 1988, TPRI successfully conducted OT field tests for the first time in the Wang Ting power plant subcritical boiler and achieved satisfactory results. Subsequently, the application of OT has become an effective solution to the problem of iron oxide deposition on economizer inlet orifices of 300 MW subcritical units made in China. In the 1990s, as China imported many 300 to 600 MW supercritical units and put them into operation one after another, OT was applied successfully to solve the frequent problems of high boiler heating surface corrosion rates and rapid increases in the boiler pressure differential. In 1995, TPRI first applied the OT technique to the Shanghai Shidongkou Power Plant 2 x 600 MW supercritical boilers, and achieved the desired results [1]. The units have also become the longest OToperating supercritical units in China at present. In 2002, TPRI formulated a "Once-through Boiler Feedwater Oxygenated Treatment Guideline" to regulate the feedwater oxygenated treatment mode of boilers in domestic power plants [2]. In the 21st century, with a large number of domestic 600 MW supercritical units and 1 000 MW ultra-supercritical units having been put into operation in China, high corrosion rates of boiler heating surfaces, deposits on water wall tube orifices and deposits plugging high-pressure (HP) heater drain control valves have become more prominent (Figures 1 to 4). Corrosion and

deposition of downstream equipment caused by flowaccelerated corrosion (FAC) is particularly prominent. These units originally applied the all-volatile treatment under oxidizing conditions (AVT(O)), but to solve the abovementioned problems, OT has been more actively utilized in these supercritical units [3]. At the same time, when the feedwater is in the AVT condition, mixed bed condensate polishing has a heavy operational burden, and many units are forced to operate in ammonium form, which causes severe leakage of chlorine and sodium into the mixed bed effluent. The deposition and corrosion of

Figure 1: Example of an economizer tube with a scaling rate of 260 g · m–2 per year.

© 2014 by Waesseri GmbH. All rights reserved.

294

PowerPlant Chemistry 2014, 16(5)

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

Figure 2:

Figure 3:

Oxide deposition in the last stage of HP heater tube inlets.

Water wall tube orifice deposits.

Figure 5: Deposits on the blade of a HP rotor.

Figure 4: Deposits on a drain control valve.

steam turbine blades is also very common (Figures 5 and 6). The advantages and effects of the OT technique for solving these problems are obvious, and therefore have become the driving force for the development of the technology. As of the end of 2011, there are more than 100 units with OT in China, of which more than 80 % are ultra-supercritical or supercritical units. All the 1 000 MW ultra-supercritical units in operation are using OT for feedwater treatment. Statistics of the units with OT and unit capacity are shown in Figure 7.

PowerPlant Chemistry 2014, 16(5)

According to the "Once-through Boiler Feedwater Oxygenated Treatment Guideline," which was mainly prepared by TPRI , the dissolved oxygen in feedwater is limited within the range of 30 to 150 µg · L–1 for units on OT. In practice, the oxygen content in the feedwater of operating units with OT is in the range of 30 to 80 µg · L–1. The merit of OT is fully reflected in these units, as demonstrated by data showing that the iron content in the economizer inlet and HP heater drain is less than 1.0 µg · L–1 (Figure 8), and the average deposit rate in the tubing of the economizer and water wall after running for six years in this mode is less than 30 g · cm–2 per year. In addition, the

295

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

300 MW subcritical once-through units 8%

300 MW–600 MW subcritical drum units 10 %

1 000 MW ultrasubcritical units 24 % 600 MW subcritical units 58 %

Figure 6:

Figure 7:

Corrosion on the blades of a low-pressure rotor.

Statistics on unit capacity of thermal power plants using OT in China.

Iron Concentration [µg · kg –1]

10.0

8.0

AVT(O) pH: 9.2~9.6

CPD MS DI EI HPD

OT pH: 8.8~9.0

Condensate pump discharge Main steam Deaerator inlet Economizer inlet High-pressure heater drains

6.0

4.0

2.0

0 CPD

MS

DI

EI

HPD

Figure 8: Iron concentration of AVT(O) vs. OT in a 1 000 MW unit. CPD MS DI EI HPD

condensate pump discharge main steam deaerator inlet economizer inlet high-pressure heater drains

regeneration cycle for the condensate polishing system has been extended 4 to 5 times compared with AVT operation, and the rate of boiler differential pressure increase is significantly reduced (Figure 9). At the same time, the deposits on the water wall orifice and oxide blockage in the HP heater drain regulating valve have been significantly mitigated. However, the use of OT is still limited in many generating units in China due to the concern about high-temperature steam oxidation. To reduce the possible risk of introducing increased oxygen concentration into the steam system, hypoxia (low-oxygen) treatment in feedwater, also called weak oxygenated treatment (WOT), has been adopted in

296

some units, and the dissolved oxygen content in the economizer inlet is generally controlled at 5 to 20 µg · L–1. It is evident that hypoxia treatment cannot protect the HP heater drain system. High iron content in the drains caused by two-phase flow-accelerated corrosion (FAC) and drain valve blockage still cannot be avoided with lowoxygen treatment. In addition, the frequent regeneration of the condensate polishing mixed beds is a difficult problem for power plant chemistry workers. Oxygen injection to feedwater systems often uses the auto-adjustment mode. An automatic oxygen feed device developed by TPRI for units with OT is popular in China. Normally, the dissolved oxygen content in the feedwater

PowerPlant Chemistry 2014, 16(5)

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

3.5 O2 + NH3 conditioning

Pressure drop of Unit No. 1

Pressure Drop [MPa]

3.2

Pressure drop of Unit No. 2

2.9

2.6

2.3 O2 + NH3 conditioning 2.0 3

3

4

5

9

10

15

18

20

23

27

27

28

29

29

30

30

Month

Figure 9: Pressure drop from the feed pump to the steam-water separator section in a 1 000 MW unit.

2 000

400

Oxygen flow

Feedwater Flow [t · h–1]

300 1 200 200 800

100 400

Dissolved Oxygen Content [µg · L–1]

Feedwater flow 1 600

DO in feedwater Set value

0

0 0

3

6

9

12

15

18

21

24

27

30

Time [h]

Figure 10: The control effect of the automatic oxygen feed device in running a unit on OT. DO

dissolved oxygen

can be controlled within the setting range ± 20 µg · L–1 even in the case of unit load fluctuations, because this unique oxygen feed device is equipped with a trace gas regulatory agent and a differential pressure stabilization adjusting device, as shown in Figure 10.

THE INVESTIGATIONS Change in the Metal Oxide Film in the Low-Temperature Zone of the Boiler Heating Surface At the water temperature of the condensate low-pressure heaters and the first high-pressure heater, the magnetite

PowerPlant Chemistry 2014, 16(5)

film has higher solubility and it is in an active state. Magnetite solubility reaches the highest point at about 150 °C. When the local flow conditions deteriorate, dissolution of the oxide film can cause FAC at local metal surfaces in the feedwater system under reducing conditions, and that is why the iron content is higher (average 8 to 10 µg · L–1) in the feedwater systems of boilers treated with AVT(R) (all-volatile treatment, reducing conditions). When the feedwater treatment was changed from AVT(R) to AVT(O) (all-volatile treatment, oxidizing conditions), the FAC was only partly mitigated, and the iron content of the feedwater was only lowered to an average of 4 to 6 µg · L–1 due to less dissolved oxygen in the feedwater. The corrosion products deposit at various locations in the system,

297

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

as previously mentioned, and this deposition is a widespread problem in supercritical boilers in China. Metal Oxide Film Forming Mechanism According to the oxide film formation mechanism, the metal oxide film in pure water without oxygen below 300 °C consists of a compact Fe3O4 topotactic layer and a porous Fe3O4 epitactic layer due to the insufficient oxidizing effect of water. Oxide film forming reactions can be divided into the following steps [4]: carbon steel is dissolved to form ferrous hydroxide and the magnetite and hydrogen is released. The third step is the slowest. Fe + 2H2O = Fe2+ + 2OH– + H2앖

(1)

Fe2+ + 2OH– = Fe(OH)2앗

(2)

3Fe(OH)2 = Fe3O4 + 2H2O + H2앖

(3)

As the water temperature increases above 200 °C, the third step of the Fe3O4 oxide film formation mechanism is accelerated, but the presence of ferrous hydroxide is still an intermediate link in the corrosion cell reaction. As Fe(OH)2 has high solubility, suppression of Fe2+ will occur if the pH of the water is elevated. When oxygen is added to the water, the oxygen molecules accept electrons to form OH– in the corrosion cell cathode. While water as an oxidizer has insufficient oxidizing strength to transform Fe2+ to Fe3+, oxygen molecules support the reduction reaction at the cathode and provide the required energy for Fe2+ to convert to Fe3+. This increases the phase interface reaction speed, and eventually accelerates the conversion of ferrous hydroxide to ferric oxide. 2Fe(OH)2 + ½O2 = Fe2O3 + 2 H2O

a

(4)

Because oxygen is continuously added to the feedwater, the Fe2+ diffused through the Fe3O4 topotactic layer is oxidized to form FeOOH or Fe2O3, as shown in Eq. (4), which then is deposited in holes and surface pores in the Fe3O4 epitactic layer. The Fe2O3 seals the porous Fe3O4 film, resulting in a dense and stable "double layer protective film" formed on the steel surface [5], as shown in Figure 11a. The iron content in the feedwater is then decreased to less than 1 µg · L–1. The Surface Difference on the Inlet Tube and Outlet Tube of the Economizer The status of the metal oxide films on the surfaces of the feedwater system cannot be directly analyzed and compared. This is because the sampling is difficult, and it can only be judged by means of the analysis of economizer tubes. Before 2008 in China, all feedwater oxygenated treatment was directly converted from AVT(O) while operating the boilers without first carrying out chemical cleaning. After the boiler treatment had been converted to OT (the oxygen concentration in the feedwater was about 50 to 70 µg · L–1) for a period of time, tubes were sampled and metal surfaces were observed. It was found that the surface color of all tubes from the economizer to the water wall appeared brown-red due to heavy powdery iron oxides, which resulted from performing the conversion to OT without a prior chemical clean. This observed phenomenon led to some confusion regarding the theoretical effective oxygen range for OT. After 2008, power plants in China began to focus more on saving energy and reducing the cost of running the unit. In order to completely clear out the iron oxide deposits in the feedwater system and boiler, chemical cleaning was carried out prior to OT conversions. Some tubes from

b

c

Figure 11: Surface appearance of boiler economizer tubes. a) Brown-red color on economizer inlet zone tube surface of a 600 MW boiler operating under OT b) Economizer outlet zone tube surface without brown-red color of a 600 MW boiler operating under OT c) Economizer inlet zone tube surface of a 660 MW boiler operating under AVT(O)

298

PowerPlant Chemistry 2014, 16(5)

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

economizers of 600 MW supercritical boilers which were treated with the abovementioned method were analyzed and studied. It was discovered that with this approach, when economizer and water wall tubes were sampled from 600 MW boilers which were treated with OT, their oxide film color and appearance characteristics were obviously different – the inner surface of the economizer inlet section tube sample had a reddish brown layer, and that of the economizer outlet section tube had a steel-grey colored layer with very weak brown, as shown in Figure 11b. The water wall tube also had a light steel-grey colored layer on the surface. The color of the economizer inlet zone tube surface in a boiler operating under AVT(O) is dark steel-grey (Figure 11c). The product on the metal surface has been analyzed by X-ray diffraction (XRD), showing that the oxidation film formed in hot water with O2 is different from that formed in hot air. The product on the economizer inlet and outlet zone tube surfaces in a boiler operating under AVT(O) is a pure Fe3O4. The product on the economizer inlet zone tube surface in a boiler operating under OT is ␣-Fe2O3 and some Fe2O3 with cubic crystals as well as a small amount of Fe3O4. The product on the tube surface of the economizer outlet zone in a boiler operating under OT is Fe3O4 and a small amount of ␣-Fe2O3. These tube sample surface appearances were magnified 500 times by scanning electron microscopy (SEM) and the images are shown in Figure 12. The reddish brown layer on the surface of the inlet section tube is a dense covering layer. This may suggest that a certain amount of ferrous hydroxide still exists in the film, which is the driving force for the oxygen reduction at the cathode. Due to the increased oxygen concentration in the water, Fe2+ from the metal matrix was oxidized to Fe3+ by oxygen and sub-

a

sequently a Fe2O3 oxide coating in the oxide layer was formed under the conditions of the water temperature at the inlet section of the economizer, which is very important for inhibiting FAC at the economizer tube entrance. This kind of Fe2O3 film is different from the ␣-Fe2O3 formed at high temperatures and is unstable at the temperature of feedwater [6] and the high flow rate of feedwater; it requires continuous oxygen feed (above 30 µg · L–1) to maintain its stability. The oxide film color and appearance characteristics of the economizer outlet tube samples are close to those of water wall tube samples, showing a "clean" surface compared with that of the inlet section tube although there is a very weak brown color on the tube surface. This phenomenon may also suggest that the effect of oxygen promoting the formation of a double protective layer on the metal surface by means of cathodic reduction in a corrosion cell has visibly begun to weaken. Thus, the Fe2O3 oxide coating layer formed by oxygen feed only extends as far as the economizer inlet section where the water temperature is still about 300 °C (water temperatures of the economizer inlet and outlet are 290 °C and 320 °C, respectively). However, the oxidation-reduction potential (ORP) of the water here has been kept at a positive value in the boiler water solution due to oxygen feeding, until oxygen in the water enters into the steam in the water wall evaporating section of the boiler. When the water temperature of the economizer outlet exceeds 300 °C, redox reactions occurring on the metal surface may directly oxidize ferrous ions to ferric ions instantly, as illustrated in the chemical reaction Eq. (5), which also suggests that bivalent iron ion migrating outward from the metal matrix may be converted to ferric ions

b

c

Figure 12: SEM surface appearance (magnified 500 times) of 600 MW unit boiler tubes under OT. a) Economizer inlet tube surface with a dense covering layer b) Economizer outlet tube surface c) Water wall tube surface

PowerPlant Chemistry 2014, 16(5)

299

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

in an instant. The formation of dense magnetite oxide films has no ferrous hydroxide as a transitional product here (Eq. (5)): 3Fe + 4H2O = Fe3O4 + 4H2앖

face can be spontaneously oxidized to form a fine and dense film by water and steam with sufficient oxidizing strength. However, there are different surface appearances due to iron corrosion products depositing on tube surfaces when boiler feedwater treatments are different; Figure 13 illustrates boiler water wall tube surfaces with feedwater treatments of AVT(R), AVT(O) and OT, respectively. The outside layer of the oxide film on a water wall tube treated with AVT(R) (Figure 13a) has an oxide that has a coarse granular particle size, since the iron oxide particle comes from the upstream thermal system by corrosion product transport. The outside layer of the oxide film on a water wall tube treated with OT (Figure 13c) has a fine granular particle size since the oxide film was formed in situ and few iron oxide particles originate from the upstream thermal system water. The outer layer of the oxide film on the water wall tube treated with AVT(O) (Figure 13b) has iron oxide particles of a size between the above two scenarios; nevertheless, the oxide layer still has obvious rippled characteristics.

(5)

As long as the ferric iron concentration is above a very low threshold, it precipitates and becomes a stable solid phase, because the solubility of magnetite is much lower than that of ferrous hydroxide. In this process, Eq. (5) is in balance with no excess bivalent ferrous ions or electrons, so the oxygen molecule here has no way to participate in the formation process of the oxide film reaction. In other words, the metal oxide film is in a passive state due to the temperature (above 300 °C) and ORP (above 100 mV of the water, and an excess of oxygen in the water and elevation of water pH are not important in this pure water system. The scaling rate on the tube surface here also indicates that the oxidation film is very thin in the economizer outlet in Table 1. Among 4 boilers, the scaling rate of the economizer of the boiler operating under OT is the lowest.

The products on the metal surfaces have been tested by XRD. The product on the water wall tube surface in a boiler with AVT(O) is a Fe3O4. The product on the water wall tube surface, including the economizer outlet section, in a boiler with OT is Fe3O4 and a small amount of ␣-Fe2O3, because hot water is strongly oxidizing under conditions of higher temperature and positive ORP; corrosive product migration and deposition can also impact the products on the water wall tube surfaces.

This phenomenon indicates that in metal oxidation there is a competitive relationship between hot water and a small amount of oxygen at the temperatures in the thermal system. In the lower temperature zone, oxygen in the water can promote the formation of a double protective coating layer on the metal surface. In the middle temperature zone, the oxidizing strength of the water is enhanced due to higher temperature and positive ORP of the water; water and oxygen may contribute jointly to metal oxidation. In the steam zone, the contribution of water steam and oxygen to metal high-temperature oxidation mainly depends on the gas partial pressure.

Change in the Metal Oxide Film in the High-Temperature Zone of the Boiler Heating Surface It has been a concern to chemistry personnel whether feedwater oxygenated treatment (OT) affects the oxidation behavior of the internal surfaces of superheater and reheater tubes. All collected data from field samples show that OT did not increase the oxide growth rate of superheater and reheater tube interiors. There is almost no controversy regarding this result. With regard to the oxide layer peeling off, it has been confirmed that oxide layer exfoliation of low-chromium alloy steel (T23), martensitic steel

Deposition on the Water Wall Tube Surface The temperature of water or steam in supercritical boiler water wall tubes is high (above 350 °C), so the metal sur-

Unit Treatment

#1

#2

#3

#4

AVT(O) 1 year WOT 0.4 years

AVT(O) 0.83 years

AVT(O) 1 year

OT 1.17 years

Measuring point

EIS

EOS

EIS

EOS

EIS

EOS

EIS

EOS

Scaling rate (g · m–2 per year)

60.6

46.9

42.9

33.5

79.5

51.3

35.3

29.2

Table 1: Scaling rate (g · m–2 per year) at the tube surface of the economizers in one power plant. WOT EIS EOS

300

weak OT economizer inlet section economizer outlet section

PowerPlant Chemistry 2014, 16(5)

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

a

b

c

Figure 13: Surface appearance (magnified 2 000 times) of 600 MW boiler tubes with different feedwater treatments. a) AVT(R), operation for 4.5 years b) AVT(O), operation for 1 year c) OT, operation for 1 year

(T91) and high-chromium alloy steel (HR3C) has not been affected by oxygen concentrations in steam. The focus of the argument is whether oxygen in the steam promotes the spallation of the metal oxide layer of 18 Cr series austenitic stainless steel in high-temperature zones [7,8]. It was found from the investigations and surveys in China that the issue of oxide removal from 18 Cr series austenitic stainless steel is more prominent in boilers treated with OT. The extent of serious oxide layer exfoliation is quite different when the design of the unit includes the same pipe material in boilers with or without OT. In some units, exfoliation took place in the superheater, while in other units exfoliation took place in the reheater, and in some units, the exfoliation occurred in both the superheater and the reheater, or in neither. After careful research and comparison, it was shown that temperature is the key factor in addition to the specific metal alloy. The influential factors for boiler tube temperature are the boiler model, type of coal, combustion mode, heating surface design, arrangement of superheater and reheater, etc. Chromium Acid Ion (CrO42–) Release during OT Conversion An increase in cation conductivity in water and steam is a common phenomenon during OT conversion. This is because some anionic impurities are released from the oxide film as phase transition occurs. These anionic impurities commonly include Cl–, F–, SO42–, formic acid and acetate ions as well as carbonate ions. As the concentration is low and release time is short, they do not jeopardize the water and steam quality. TPRI has found another anionic impurity, the chromium acid ion (CrO42–) [9] released in later phases of OT conversion, as shown in

PowerPlant Chemistry 2014, 16(5)

Table 2, which has a higher concentration than common anionic impurities, and also contributes to the cation conductivity increase. The source of chromium acid ion is a special concern because boiler section materials contain the element Cr. According to the data compiled after converting to OT in dozens of units, TPRI has developed a summary of the characteristic release of chromium acid ion as follows: 1. Chromium acid ion mainly appears in economizer inlet and superheated steam samples (see Table 3 below). It is usually accompanied by an oxygen content increase in the feedwater and superheated steam samples after oxygen is added to the feedwater, and the CrO42– content peaks in a short time. The higher the dissolved oxygen (DO) content, the larger the peak value is. This level gradually decreases, but this rate of decrease is not related to DO. In fact, CrO42– release does not appear in all units during the OT conversion process, which may be associated with the sample tubing material. 2. There is no evidence of chromate ions in the water/ steam cycle. CrO42– is never detected in the condensate, low-pressure feedwater, boiler water, and highpressure drains, or reheat steam in either the OT conversion process or under normal operating conditions of a unit. Chromium content is also not detected in deposits in steam systems and turbines. When running on normal OT, DO is 30 to 80 µg · L–1, and CrO42– is not detected in any sampling points of the water/steam cycle. If the DO concentration is increased intentionally for testing, CrO42– will clearly increase in the economizer inlet sample. This reveals that the DO concentration plays an important role in CrO42– release.

301

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

3. In superheated steam sample tubing, CrO42– release is only found when dry steam in the end part of the pipe segment is gradually converted to wet steam or even water. There is only a trace of CrO42– in superheated steam sampling of some supercritical units. For one unit, it has been confirmed that the sample tubing insu-

Unit

lation is good [10]. However, CrO42– has not been found in low-pressure and low-temperature feedwater samples, even though the low-pressure heater tubing is made of stainless steel. This also confirms that temperature plays an important role in CrO42– release.

Economizer Inlet (µg · L–1)

Unit Capacity

Steam (µg · L–1)

DO

CrO42–

DO

CrO42–

A

600 MW supercritical once-through boiler

150–200

< 0.3

< 10

< 0.3

B

500 MW subcritical once-through boiler

200–300

< 0.3

50–100

5.1

C

300 MW subcritical drum boiler

300–350

4.6

150–250

0.5

D

600 MW supercritical once-through boiler

150–200

18.4

70–60

< 0.3

E

600 MW supercritical once-through boiler

150–200

211

~ 100

1.4

F

300 MW subcritical once-through boiler

200–300

17

50–100

26

G

600 MW supercritical once-through boiler

100–200

7

50–150

< 0.3

H

1 000 MW ultra-supercritical once-through boiler

100–150

23

30–40

1.2

Table 2: Dissolved oxygen (DO) and chromium acid ion content at some sample points during OT conversion.

Data

Deaerator Inlet (µg · L–1)

Economizer Inlet (µg · L–1)

Steam (µg · kg–1)

HP Heater (µg · L–1)

Reheater (µg · kg–1)

Condensate (µg · kg–1)

6-27

< 0.3

< 0.2

< 0.3

< 0.3

< 0.3

< 0.3

6-28

< 0.3

< 0.2

< 0.3

< 0.3

< 0.3

< 0.3

6-30

< 0.3

< 0.2

< 0.3

< 0.3

< 0.3

< 0.3

7-1

< 0.3

< 0.2

< 0.3

< 0.3

< 0.3

< 0.3

7-3

< 0.3

< 0.2

< 0.3

< 0.3

< 0.3

< 0.3

7-5

< 0.3

2.82

< 0.3

< 0.3

< 0.3

< 0.3

7-8

< 0.3

90.8

< 0.3

< 0.3

< 0.3

< 0.3

7-17

< 0.3

148.5

1.4

< 0.3

< 0.3

< 0.3

7-18

< 0.3

211.0

< 0.3

< 0.3

< 0.3

< 0.3

7-20

< 0.3

171.1

< 0.3

< 0.3

< 0.3

< 0.3

7-23

< 0.3

54.5

< 0.3

< 0.3

< 0.3

< 0.3

Mode

AVT(O)

OT convertion

Table 3: CrO42– content at cycle sampling point in Unit E during OT conversion. Note: < 0.3 indicates that the CrO42– content is less than the detection limit (0.3 µg · L–1) for the chromatograph.

302

PowerPlant Chemistry 2014, 16(5)

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

The analysis above reveals that CrO42– only comes from the sample tubing surface film. One possible mechanism is as follows:

REFERENCES [1]

Li, Z., Shen, B., Thermal Power Generation 1998, 27(6), 42 [in Chinese].

In the stainless steel sample tubing of the economizer inlet, the water temperature is at 270 °C to 290 °C; there are Cr2O3, Crx FeyO3, Cr(OH)2 and Cr(OH)3 present, from the inside to outside of the metal oxide film under AVT conditions. The higher the temperature, the higher the ratio of chromium oxide in the oxide film, due to the accelerating diffusion of chromium ions in the material. During the unit conversion to OT, as oxygen passes through the sampling tubes, the redox potential rises, and the water changes to a more oxidizing state. The metal oxide film on the surface of the sampling tube changes accordingly. Low-valence oxides in the oxide film are oxidized to highvalence oxides, such as Fe2+, Cr2+ and Cr3+ being converted to Fe3+ and Cr6+. Part of the high-valence chromium compounds dissolve and combine with water to form CrO42–. Under a certain water temperature and fluid flow velocity, if the oxygen concentration is beyond a certain range, the higher the oxygen concentration, the faster the chromium ion release from the metal [11]. Therefore, for feedwater sample tubing made of stainless steel material, specific high temperatures, water flow rate and DO concentration prove to be three key conditions for chromium acid ion release; without any of these three conditions, chromium acid ion release will not happen.

[2]

Guideline for Cycle Chemistry in Fossil Power Plant: Part One, Oxygenated Treatment of Once-Through Boiler, 2002. Thermal Power Research Institute, Xi'an, P. R. China, DL-T 850.1 [in Chinese].

[3]

Li, Z., Chen, R., China Electric Power 2004, 37(11), 47 [in Chinese].

[4]

VGB Guidelines for Boiler Feed Water, Boiler Water, and Steam of Steam Generators with a Permissible Operating Pressure >68 bar, 1988. VGB Kraftwerkstechnik GmbH, Essen, Germany, VGB-R 450 Le.

[5]

Li, Z., Thermal Power Generation 2002, 31(6), 26 [in Chinese].

[6]

Evans, U. R., Corrosion and Oxidation on Metal, 1976. China Mechanical Industry Press [in Chinese].

[7]

Jia, J., Li, Z., China Electric Power 2008, 41(5), 37 [in Chinese].

[8]

Dooley, R. B., Bursik, A., PowerPlant Chemistry 2011, 13(4), 236.

[9]

Li, Z., Shen, B., Huang, W., Thermal Power Generation 2012, 41(2), 47 [in Chinese].

[10] Shanghai Shidongkou Power Plant Report, 2004. Thermal Power Research Institute, Xi'an, P. R. China [in Chinese].

CONCLUSION The application of feedwater oxygenated treatment technology in China is successful and has achieved technical and economic benefits. Feedwater oxygenated treatment for the pre-boiler system can significantly reduce the iron content in the feedwater system and then reduce the boiler differential pressure drop and deposit rate on boiler tubing, which eventually results in the improvement of boiler efficiency and energy savings. Feeding oxygen to the water makes the metal surface form a reddish brown Fe2O3 coating layer. This layer requires continuous oxygen feed to maintain its stability. Research has confirmed that oxygen promotes the formation of a double protective film on the metal surface through the cathodic reduction effect in the corrosion cell. This mechanism is closely related to water temperature, and its effective temperature range is from room temperature to about 300 °C. The CrO42– detected at some water sampling points during OT conversion and/or normal operation with OT does not come from the thermal equipment material but most likely is released from stainless steel sample line tubing.

PowerPlant Chemistry 2014, 16(5)

[11] Effertz, P.-H., Die kombinierte Ammoniak-, Sauerstoffkonditionierung von Wasser-, Dampfkreisläufen in Kraftwerken: Tagungsbericht d. Allianz-Workshops im Allianz-Zentrum für Technik Ismaning bei München, 8./9. November 1982 (Editor P.-H. Effertz). Allianz-Berichte fur Betriebstechnik und Schadenverhütung, 1985, 23. Allianz-Versicherungs-AG, München, Germany.

ACKNOWLEDGMENTS We acknowledge Mr. Andrew Howell from Xcel Energy and Mr. Peigang Cao from Ontario Power Generation for reviewing and revising this paper.

THE AUTHORS Zhigang Li (B.S., Metal Corrosion Protection, Dalian University, China) is a senior committee member of the Chinese Society of Electrical Engineering and has been responsible for research and development of power plant

303

PPChem

Boiler Feedwater Oxygenated Treatment in Power Plants in China

chemistry for fossil plants in China since 1980 as a engineer of the Thermal Power Research Institute, China. He has been a director engineer of the Chemical Engineering Research Department of Xi'an Thermal Power Research Institute since 2011. He was a researcher and deputy director of the Chemical Engineering Research Department of Xi'an Thermal Power Research Institute, P. R. China, from 1999 to 2010. Wanqi Huang (B.S., Power Plant Chemistry, Wuhan University of Hydraulic and Electrical Engineering, China) is a senior engineer and has been working at the Thermal Power Research Institute (TPRI) Co. LTD. since 1999. He is a director of a department of TPRI which is responsible for the technology of metal corrosion and protection of thermal equipment and water treatment for power plants. Songyan Cao (M.S., Applied Chemistry, University of Northeast China Institute of Electric Power, M.E., Thermal Power Engineering, Xi'an Thermal Power Research Institute) started her career in 2004 in a power plant in Jiangsu province in China. Since 2006, she has been

working at TPRI Co., LTD. with emphases on water chemistry treatment, corrosion and protection of thermal equipment. In 2011 she obtained a Master's degree from TPRI. Hongbo Zhang (M.S., Environmental Engineering, M.E., Chemical Engineering, University of Northeast China Institute of Electric Power) has been working at TPRI Co., LTD. in China with emphases on water chemistry treatment, corrosion and protection of thermal equipment since 2011.

CONTACT Zhigang Li Thermal Power Research Institute 32, Xiying Road Xi'an, Shaanxi Province P. R. China, 710043 E-mail: [email protected]

Chemists and engineers from fossil and nuclear power plants and from industrial power generation, vendors, OEMs, consultants, E&As, and others in more than 60 countries on all continents read PowerPlant Chemistry®.

You can reach them by advertising in our journal. PowerPlant Chemistry® is shipped worldwide. Some examples: • Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • • China • Colombia • Croatia • Cyprus • Czech Republic • Denmark • Egypt • Finland • • France • Germany • Great Britain • Greece • Hong Kong • Hungary • India • Indonesia • • Ireland • Israel • Italy • Jamaica • Japan • Korea • Kuwait • Malaysia • Malta • Mexico • • Montenegro • Morocco • New Zealand • Norway • Pakistan • Philippines • Poland • • Portugal • Romania • Russia • Saudi Arabia • Serbia • Slovakia • Slovenia • South Africa • • Spain • Sweden • Switzerland • Taiwan • Thailand • The Netherlands • Turkey • • Ukraine • United Arab Emirates • United States •