COMMITMENT & INTEGRITY DRIVE RESULTS Chloramination, The Science Methods of Application & Other Stuff. Ron Hidu, PE...

126 downloads 589 Views 1010KB Size
Chloramination, The Science Methods of Application & Other Stuff Ron Hidu, PE

COMMITMENT & INTEGRITY DRIVE RESULTS

Ammonia Source

▀ ▀ ▀ ▀

Naturally Occurring Anhydrous Ammonia Aqueous Ammonia Ammonium Sulfate

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 2

Aqueous Ammonia – NH4OH • H2O ▀ ▀ ▀ ▀ ▀ ▀ ▀

Ammonium Hydroxide 19, 25, 40 %...typically 19% SG = 0.926 7.8 lbs/gal Boiling point = 86º F Odor threshold = 5 ppm Fed directly 19% concentration provides 15.6% N by wt.

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 3

Ammonium Sulfate - (NH4)2SO4 ▀ ▀ ▀ ▀ ▀ ▀ ▀ ▀

50 lb bags Granular; little issue with dusting Solubility up to about 40% solution @ 77º F Easiest to mix as 12% solution (i.e. 1 lb chemical to 1 gal water) Molecular wt. = 132.14 Ammonium Sulfate is 21% N by wt. Also proprietary products NSF 60

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 4

Cost Comparison ▀

Ammonium Sulfate ▀ ▀ ▀



~ 65¢ / lb (in pallet quantities, 2000 lbs, 40 bags) 21% N by wt. Equates to $3.09 / lb N

19% Aqueous ▀ ▀ ▀ ▀

~ 16¢ / lb (6000 gal delivery; 7300 lbs N) ~ 40¢ / lb (400 gal delivery; 500 lbs N) 15.6% N by wt - 7.8 lbs / gal Equates to $2.56 / lb N (400 gal delivery)

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 5

Cost Example ▀ ▀ ▀ ▀ ▀

1 MGD 1.5 mg/l Cl2 Usage would be 3.0 lbs/day N (see table) Ammonium Sulfate = $9.27 / day Aqueous Ammonia = $7.68 / day

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 6

Plant Flow Rate 700 4.2 50# Bag (99.5%) For 12% Solution For 12% Solution

Ratio 4.2:1 CL2-N 49.75 414.58 49.71

Total Chlorine Residual mg/l as Cl2 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 3 lbs N 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5

lb/hr as N 0.0167 0.0250 0.0334 0.0417 0.0500 0.0584 0.0667 0.0751 0.0834 0.0917 0.1001 0.1084 0.1168 0.1251 0.1334 0.1418 0.1501 0.1585 0.1668 0.1751 0.1835 0.1918 0.2002 0.2085

/day

lbs. lbs. Water gal. Water

GPM

Mix 1 Bag Ammonium Sulfate to 50 gallons of water

lb/hr as (NH4)2 (SO4) 0.0786 0.1180 0.1573 0.1966 0.2359 0.2752 0.3145 0.3539 0.3932 0.4325 0.4718 0.5111 0.5504 0.5898 0.6291 0.6684 0.7077 0.7470 0.7863 0.8257 0.8650 0.9043 0.9436 0.9829

hrs/bag 632.7 421.8 316.3 253.1 210.9 180.8 158.2 140.6 126.5 115.0 105.4 97.3 90.4 84.4 79.1 74.4 70.3 66.6 63.3 60.3 57.5 55.0 52.7 50.6

Feed Rate gal/hr 0.08 0.12 0.16 0.20 0.24 0.28 0.31 0.35 0.39 0.43 0.47 0.51 0.55 0.59 0.63 0.67 0.71 0.75 0.79 0.83 0.86 0.90 0.94 0.98

Feed Rate ml/min 5.0 7.4 9.9 12.4 14.9 17.3 19.8 22.3 24.8 27.3 29.7 32.2 34.7 37.2 39.7 42.1 44.6 47.1 49.6 52.0 54.5 57.0 59.5 62.0

3 ½ days / bag in 50 gal of water COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 7

Materials of Construction ▀ ▀ ▀ ▀ ▀

Poly tanks SCH 80 PVC (not for Anhydrous…SS) PE, PP, PTFE tubing No copper, brass, etc. If using peristaltic pumps with Aqueous, careful with hose (use silicone, Tygon, Bioprene©… not nitrile, rubber)

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 8

Chemical Addition ▀

NH3 then NaOCl NaOCl then NH3



Reaction is rapid



▀ ▀





}

Doesn’t matter…Typically OCl- first since you usually have to meet a CT requirement.

Monochloramine kinetics optimized at pH 8.5 and takes < 1 min. Drive pH higher due to Pb solubility (9.8)

Often difficult to find a chem feed pump that will operate well at the low dosages used (Prominent Mikro line??) Like to have a static mixer or orifice plate COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 9

Monitoring ▀

Ahead of dosing point: ▀ ▀



At entrance to system: ▀ ▀



Free Chlorine pH Total chlorine pH

Within system: ▀ ▀ ▀

Total chlorine pH (keep high, no Di, no need to monitor for Mono using APA6000) Trace free chlorine but no free NH3

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 10

Chloramine Species Species

Formula

Odor Threshold (mg/l)

Taste Threshold (mg/l)

Monochloramine

NH2Cl

0.48

0.65

Dichloramine

NHCl2

0.13

0.15

Trichloramine

NCl3

0.02

0.02

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 11

Chemistry Cl2 + H20 NaOCl + H20

HOCl + HCl HOCl + NaOH

(hydrolysis)

Free chlorine species

hypochlorous acid

Unbuffered water… Cl2 reduces pH; NaOCl raises pH

HOCl

H+ + OCl- (dissociation)

Equilibrium based on pH & temp

hypochlorite ion

Then add N either naturally or by NH3 source:

HOCl + NH3 HOCl + NH2Cl HOCl + NHCl2

NH2Cl + H2O NHCl2 + H20 NCl3 + H20

Too much chlorine (too high Cl2:N ratio) drives toward Tri., too little leaves excess free nitrogen…range 3:1 to 5:1 (4.2 stoichiometric), but differs for individual water chemistry COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 12

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 13

40

9.8 pH

5

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 16

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 17

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 18

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 19

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 20

Case Studies ▀

Bath – 2003 ▀ ▀

▀ ▀ ▀ ▀



~3 MGD, Microfloc Plant upgrade included setup to go to chloramines using Aqueous ammonia 2) 750 gal bulk tanks PVC & CPVC piping Deliveries twice/yr Considered Ammonium sulfate (4 ½ bags / week), but plant had no provisions for dry chemical delivery and handling. Staff used to handling bulk hypochlorite and chlorine dioxide

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 21

Case Studies (continued) ▀

Bangor – 2003 – Mutual Aid Study ▀ ▀ ▀ ▀



Bangor, Brewer, Hampden, Orono-Veazie, Old Town Blending chloraminated and non-chloraminated waters pH variations Segregating waters

Bangor – 2007 – Anhydrous to Aqueous Conversion ▀ ▀

Reuse of equipment Cl2 to NaOCl conversion

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 22

Case Studies (continued) ▀

Millinocket – 2001 ▀

▀ ▀



0.5 MGD IDI Advent, prechlorinate for filter runs, high organics, high DBPs 600 gpm Ammonium sulfate

Bar Harbor – 2009 ▀ ▀ ▀

3 MGD unfiltered, gravity flow Chlorine gas Ammonium sulfate at remote location (transmission line contactor) COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 23

Case Studies (continued) ▀

Vinalhaven I – 2005 ▀ ▀ ▀ ▀



60,000 gpd, unfiltered (100 gpm) Ammonium sulfate Remote addition point, long transmission line contactor In-system mixing

Vinalhaven II– 2010 ▀ 60,000 gpd, bags, UV, OCl- (60 gpm) ▀ Ammonium sulfate ▀ Short CT contact time ▀ NH3 addition in proximity to pump station. COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 24

Case Studies (continued) ▀

Great Salt Bay – 2009 ▀ ▀ ▀ ▀



160,000 gpd, unfiltered (300 gpm) UV, OCL-,Chloramine Ammonium sulfate NH3 addition in separate building after short transmission line contact for CT pH adjustment to 9.8 using soda ash

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 25

Case Studies (continued) ▀

Hampden – 2001 & 2010 ▀ ▀



340,000 – 440,000 gpd, consecutive system Rechlorination, pH adjustment

LDA – 2010 ▀ ▀ ▀ ▀

120,000 to 2 MGD, conventional filtration (Leopold) UV, OCL-, chloramines Long transmission line Ammonium sulfate

COMMITMENT & INTEGRITY DRIVE RESULTS

000000.00 26