1 1 Refrigerants and their Application Presented by Thomas E. Watson, P.E. Fellow ASHRAE McQuay International Staunton, Virginia USA 1 What is a Refri...

13 downloads 799 Views 3MB Size
Refrigerants and their Application Presented by

Thomas E. Watson, P.E. Fellow ASHRAE McQuay International Staunton, Virginia USA 1

What is a Refrigerant? • In a refrigerating system, the medium of heat transfer which picks up heat by evaporating at a low temperature and pressure, and gives up heat on condensing at a higher temperature & pressure. • (Refrigerating fluid) fluid used for heat transfer in a refrigerating system which absorbs heat at a low temperature and low pressure of the fluid and transfers heat at a higher temperature and higher pressure of the fluid, usually involving changes of state of the fluid. Ref: ASHRAE Terminology of Heating, Ventilation, Air Conditioning, & Refrigeration

2

1 1

Agenda / Topics • Introduction • History of Refrigerants • Basic Refrigerant Chemistry • Refrigerant Properties • Refrigerant Applications

• Refrigerants In The Future? • Alternative Refrigerants • Ozone Depletion & Montreal Protocol • Global Warming • Summary

3

History of Refrigerants • • • • • • • • •

1830s - Jacob Perkins - Vapor Compression (ether) 1851 - John Gorrie - Patent for Air Cycle 1859 - R-717 / R-718 (Ammonia / Water) 1866 - CO2 - Marine Applications 1873 - R-717 (Ammonia) Commercial Refrigeration Carl Linde 1875 - R-764 (Sulfur dioxide) 1920s -R-600a (Isobutane) & R-290 (Propane) 1922 - Willis Carrier - R-1130 (Dielene) 1926 - R-30 (Methylene Chloride)

4

2 2

Toxicity - Best Minds Tried to Solve Solving Problem of Toxicity was a Large Problem to Development of Refrigeration

1927 Leo Szilard & Albert Einstein Improved on von Platen / Munters Absorption Design Electromagnetic Pumping Patent

5

Challenged to Find Refrigerant: • Non-flammable • Good Stability • Low Toxicity • Atmospheric Boiling Point between -40oC & 0oC

6

3 3

Common Refrigerants in 1920s Ammonia (R-717)

NH3

Carbon Dioxide

CO2

Sulfur Dioxide

SO2

Hydrocarbons

CnHm

Methyl Choride

CH3Cl

Water

H2O

7

History of Refrigerants

8

4 4

History of Refrigerants Midgley Selections

C

N

O S

H F Cl Br

9

Refrigerant Chemistry Hydrocarbon

Formula NBP

Methane

CH4

-260 F -162 ̊C

Ethane

C2H6

-127 F -88 ̊C

Propane

C3H8

-44 F

-42 C ̊

10

5 5

Refrigerant Chemistry

11

Refrigerant Chemistry

12

6 6

Refrigerant Chemistry

13

Refrigerant Chemistry

14

7 7

Refrigerant Chemistry Fluorocarbons •

CFCs, HCFCs, HFCs & HFOs



Limited Combinations

HYDROGEN Flammable

– Adding Chlorine Or Bromine Increases ODP – Adding Fluorine Increases

Toxic

GWP – Adding Hydrogen Increases Flammability And Lowers Atmospheric Lifetime

CHLORINE

FLUORINE Long Atmospheric Lifetime (fully halogenated)

15

Refrigerant Chemistry

16

8 8

Refrigerant Chemistry

17

Refrigerant Chemistry

18

9 9

Refrigerant Chemistry • Refrigerant Blends – Two or More Refrigerants to Achieve Required Properties • • • •

Flammability Volumetric Capacity Limit Discharge Superheating for Lower Disch Temp etc

• Two Basic Types – Zeotropes – Azeotropes

19

Refrigerant Chemistry Zeotropes ZEOTROPIC BEHAVIOR (32/134a) 55 T vap T liq

Temperature, °F

45 35

P= 64 PSIA 25 15 5 -5 0

20

40

60

80

100

% R-32

20

10 10

Refrigerant Chemistry Zeotropic Behavior • •

Fractionalization - Can be Separated by Distillation Service Procedures

21

Refrigerant Chemistry Azeotropes AZEOTROPIC BEHAVIOR (R-125/R-143a) 39 T vap

Temperature, °F

38

T liq

37 P=100 PSIA 36

35 R-507 = AZEOTROPIC MIXTURE R-125/R-143a (50/50) 34

33 0

10

20

30

40

50

60

70

80

90

100

% R-125

22

11 11

ASHRAE Standard 34

23

ASHRAE Standard 34

• Nomenclature • Toxicity Classification • Flammability Classification

24

12 12

ASHRAE Standard 34 Nomenclature 000 Series 100 Series 200 Series 300 Series 400 Series 500 Series 600 Series 700 Series 1000 Series

Methane Based Ethane Based Propane Based Cyclic Organic Compounds Zeotropes Azeotropes Organic Compounds Inorganic Compounds Unsaturated Organic Compounds

Code Key Rule of 90 - Example R-12

R-

1

2

+

9

0

C

H

F

1

0

2

=

13 13

ASHRAE Standard 34

27

HFO--1234ye Stereoisomers HFO

Entgegen

Zusammen

28

14 14

ASHRAE Standard 34 • Toxicity Classification based on Chronic (long term) Measure - Class A has PEL > 400 PPM - Class B has PEL < 400 PPM PEL = Permissible Exposure Limit

29

ASHRAE Standard 34 • Flammability Classification based on:

ASTM E 681 with an Electrically Activated match

30

15 15

ASHRAE Standard 34 Flammability Classification • Class 1 - No Flame Propagation • Class 2 - LFL > 0.10 kg/m^3 and hc < 19 MJ/kg • Class 2L – Cl 2 w/ flame speed < 10 cm / sec • Class 3 - LFL < 0.10 kg/m^3 or hc > 19 MJ/kg

31

ASHRAE Standard 34

32

16 16

A2L Refrigerants

33

ASHRAE Standard 15

34

17 17

ASHRAE Standard 15 What is ASHRAE 15?

• An industry standard that specifies safe design, construction, installation, and operation of refrigerating systems • Establishes safeguards for life, limb, health, and property, and prescribes safety standards

35

ASHRAE Standard 15

Scope • Design, Construction, Installation, Operation & Inspection of Mechanical and Absorption Machines • Modifications if not Identical in Function and Capacity • Refrigerant Substitutions with Different Designation

36

18 18

ASHRAE Standard 15 Requirements Based on 3 Classifications • Occupancy • Refrigerating System • Refrigerant

37

ASHRAE Standard 15 Occupancy Classifications - Ability to Respond to Exposure •

Institutional - Assistance Required



Public Assembly - Large Numbers



Residential - Sleeping



Commercial - Business Transactions



Large Mercantile - 100 Persons or More



Industrial & Refrigerated Rooms - Access Controlled



Mixed - Two or More in Same Building

38

19 19

ASHRAE Standard 15 Refrigerating System Classification

• High Probability - Leak Can Enter Occupied Space • Low Probability - Leak Cannot Enter Occupied Space

39

ASHRAE Standard 15 Restrictions on Refrigerant Use - Section 7 •

Standard 15 Gives Rules based on Occupancy, System, & Refrigerant Classification



3 kg or Less of Flammable Refrigerants may be used in Listed Equipment



A2L Refrigerant Application Requirements NOT Included – Presently Under Consideration

40

20 20

ASHRAE Standard 15 Refrigerant Qty/vol Limits - See Std 34 • Acute Exposure / Ability to Escape • Direct Systems • Volume - Space to which Refrigerant Disperses in Event of Leak

41

ASHRAE 15 Users Manual

42

21 21

Mechanical Room Safety Check Location of inlet vents in relation to exhaust outlets ?

Location of roof drains ?

Rupture disc outlet locations ?

Purge vents to outside ?

Is there a tight seal on doors ? Are safety rupture lines the right size ? Is access to mechanical room restricted ?

Are drain valves connected to evacuation devices ?

Are there any pit areas in the room ?

Where do the floor drains empty ?

43

Mechanical Room Safety Check Relief discharge shall be located not less than 20 ft (6 m) from ventilation opening and not less than 15 ft (4.5 m) above ground level (9.7.8)

Purge systems and relief devices must be vented to outside (8.16)

All indoor machinery rooms must be vented to the outdoors utilizing mechanical ventilation 98.13.3 & 4 Access to mechanical room shall be restricted. Tight fitting doors opening outward (self closing if the open into the building) adequate in number to ensure freedom of escape. No other openings that would permit passage of escaping refrigerant (8.13)

Refrigerant sensors are located in areas where refrigerant vapor from a leak will be concentrated so as to provide warning at concentration not exceeding the refrigerant PEL

The total amount of refrigerant stored in a machinery room in all containers not provided with relief valves & piped in accordance with standard shall not exceed 330 lb (150 kg). (11.5)

44

22 22

Sample Sensor Locations*

Entrance / Exits Refrigerant Storage Just Above floor Next to Chillers

Drains

Pits

*Examples not part of standard 45

Mechanical Room per ASHRAE 15 Periodic tests of detectors, alarms & ventilation must be performed in accordance with manufacturers recommendations and/or local jurisdiction. (11.7.3)

Mechanical room should be dimensioned for easy access to all parts and adequate space for service, maintenance, and operation. Clear head room of not less than 7.25 ft (2.2 m) below equipment situated over passageways. (8.12.1 &2,8.13.1)

No open flames that use combustion air from the machinery room (boilers) can be located within the mechanical as long as the combustion air is ducted from the outside to the boiler or shut down sensors are installed (8.13.6)

A change in the type of refrigerant in a system shall not be made without the notification of the authority having jurisdiction, the user and due observance of safety requirements. The refrigerant being considered shall be evaluated for suitability (5.3)

46

23 23

IIAR 2

47

Back to the Future

24 24

Refrigerants in the Future? Low Direct Global Warming Potential • CO2 •

Ammonia

• Hydrocarbons • HFOs

49

Natural Refrigerants •

Ammonia (NH3) R-717 – Efficient – B2L Classification – Industrial Applications



Water R-718 – Absorption Chillers – Centrifugal Compressors – Axial Flow Compressors



Carbon Dioxide (CO2) R-744 – Low Critical Point

50

25 25

What about other stuff -HFOs?

Refrigerant Applications



pV = (m x Ru x T ) / MM

52

26 26

Refrigerant Applications • What is Pressure? • Pressure = Average Impact of Molecules on a given area. • Pressure is dependent on the Kinetic Energy of the molecules.

53

Volumetric Capacity 180.0 R-114 160.0 R-123 140.0

Molecular Mass

R-245fa R-12 R-1234ze

120.0 R-1234yf 100.0

R-134a

R-500 R-22

80.0

R-407C

R-410A 60.0 R-32 R-744

40.0 20.0

R-11

R-152a

R-40 R-290

R-718

R-717

0.0 0.1

1.0

10.0

100.0

1000.0

CFM/ton 54

27 27

Compressor Types

Compressor Types

Positive Displacement

Reciprocating

Rotary

Singe Shaft

Twin Shaft

Orbiting

Three Shaft

Twin Screw

Single Screw

Dynamic

Centrifugal

Scroll

Tri-Screw

Axial

Trochoidal

Moving Vane

Fixed Vane (Rolling Piston)

Compressor Volumetric Capacities

Axial Centrifugal Screw Rotary Scroll Recip 0

1 NOTE: Log Scale

10

100

1,000

10,000

100,000

1,000,000

CFM

28 28

Refrigerant Flow Requirements 1000 R-718

100

CFM/ton

R-123 R-11 R-245fa R-114

10

R-1234ze R-1234yf R-134a R-40 R-12 R-407C R-500R-22 R-290 R-717 R-410A R-32

1

R-744

0.1 0.1

1.0

10.0 Suction Pressure, PSIA

100.0

1000.0

57

Basic Considerations •



Compressors –

Vapor Pressure



Temperature Lift



Tons

Evaporators –



Glide

Condensers –

Glide



Critical Temperature

58

29 29

R-11 Alternatives Refrigerant

Molecular Mass

CFC-11

137.4

HCFC-123

153.0

HFC-245fa

134.0

59

R-12 Alternatives Refrigerant

Molecular Mass

CFC-12

120.9

CFC-500

99.3

HFC-134a

102.0

HFO-1234yf

114.0

60

30 30

R-22 Alternative Refrigerant

Molecular Mass

HCFC-22

86.5

HFC-407C

86.2

61

Global Warming TEWI - Total Environmental Warming Impact Consists of •

Direct GWP, from refrigerant discharge +



Indirect, power plant CO2 discharge dominates - Over 95% for Well Maintained Equipment - CO2 from Power Generation depends on IPLV

62

31 31

Global Warming

GWP Power Generation

63

Summary - Refrigerant Choice  Ozone saving  Global warming issue - Total Environmental Warming Impact (TEWI)  Safety  Field availability  Application  Cost  Compressor type

64

32 32

Questions?

65

Information Sources  www.ahri.org  www.ashrae.org  www.epa.gov/docs/ozone/index.html  ASHRAE Handbook – Fundamentals - Refrigerants  ASHRAE Standards 15 & 34  IIR-2 Equipment, Design and Installation of Ammonia Mechanical Refrigerating Systems  Fluorocarbon Refrigerants Handbook - Ralph C. Downing, Prentice-Hall  Trade-Offs in Refrigerant Selections: Past, Present, and Future - James M. Calm and David A. Didion - Proceedings of ASHRAE/NIST Refrigerants Conference Oct 1997  HFOS – New Low Global Warming Potential Refrigerants – S. F. Brown, ASHRAE Journal August 2009

66