IEC instrument transformers
Type VOG-17 Outdoor voltage transformer
Product features −− 12 and 17.5 kV, outdoor −− 110 kV BIL, 50 and 60 Hertz −− Power frequency withstand voltage: 42 kV −− Primary volts: 11000 - 13800 −− Electrical clearances: Strike: 10.3" (262 mm) Creep: 24.7" (627 mm) −− Approximate weight: 45 lbs (20 kg) Application The VOG-17 outdoor voltage transformer is designed for measuring line-to-ground circuits. The single centered bushing and reduced neutral end insulation permit a significant reduction in size and installation spacing, while maintaining full 110 kV BIL insulation clearances. Construction features The primary and secondary coils are wound using special winding and shielding techniques for improved voltage stress distribution. Each coil is carefully insulated with mylar film to provide a high dielectric medium between layers. The completed winding structure and double-loop cores are assembled to a support frame. For insulation and protection, the assembly is cast in hydrophobic cycloaliphatic epoxy (HCEP) using automatic pressure gelation. The HCEP material offers superior arc track, ozone, and ultravioletresistive properties while maintaining physical strength. The hydrophobic surface properties of HCEP ensure highly reliable performance in wet, humid, or polluted environments. Terminals Electro-tin plated copper primary line terminals accommodate 6 mm2 to 120 mm2 conductors. Clamp-type secondary terminals accommodate 2.5 mm2 through 25 mm2 wire. A ground terminal is also provided for grounding the secondary circuit at the transformer. Junction box The metal junction box has a 1" conduit hub on each end. The box is anchored to the body of the transformer with screws and can be easily detached, simplifying installation and change-out procedures.
Baseplate The base is constructed of corrosion-resistant aluminum and is secured to the encapsulated base support. Mounting The VOG-17 can be mounted in upright, cantilever, or upside-down positions. Stress relief devices should be used to support cable connections. The unit can also be mounted using optional mounting rails. Test reports IEC test reports are stored electronically and can be e-mailed in various formats at the time of shipment. Standards This unit meets all applicable ANSI, CSA, and IEC standards.
Unit dimensions 1" KNOCKOUT BOTTOM OF JUNCTION BOX
10.00 10.87 [254] [276]
13.75 [349]
Ø0.41 [Ø10] TERMINALS FOR #10 TO #250 MCM WIRE
9.37 [238] 0.39 [10]
15.82 [402] 1.31 [33]
RATING DECALS ON BOTH SIDES GROUND LUG WITH Ø0.44[Ø11] HOLE
1" STD. PIPE TAP BOTH SIDES 1.00 [25] 0.19 [5]
Baseplate dimensions
Optional mounting accessories The VOG-17 transformer is designed for mounting on poles or substation structures, with high voltage bushings in either vertical or horizontal positions.
10.75 [273]
0.44 x 1.69 SLOTS 4 TOTAL [11 x 43]
10.00 [254] 10.87 [276]
NAMEPLATE
8.63 [219]
When mounted with high voltage bushings in a horizontal plane, it is recommended that this plane be parallel to the ground and not one bushing above the other. This precaution prevents formation of ice and snow which could cause flashover between bushings. −− Vertical mounting with mounting brackets & back-up plates: Mounting bracket 463C035G02 Back-up plate 28D2876G01 −− Vertical mounting with mounting brackets and hangers: Mounting bracket 463C035G02 Hangers 261A233G01 −− Vertical mounting with channel brackets for tandem mounting of voltage and current transformers: Channel bracket 332B955G02 −− Horizontal mounting with hangers: Hangers 261A233G01 −− IEC mounting rails: 50C5124G01
0.44 [11] 0.44 [11]
Optional mounting rail dimensions 1.18 [30]
6.97 [177]
4.00 [102]
Note: Metric dimensions are displayed in [mm]. 2 Type VOG-17 voltage transformer | ABB product bulletin
5.97 [152]
Selection guide Style number
Primary voltage
Secondary voltage
Winding ratio
Measuring accuracy
Rated voltage factor
Thermal rating @ 30°C
50 Hz
60 Hz
11000/√3
100
63.5:1
0.2, 50 VA
1.2
500
E-923A472G01
E-923A479G01
11400/√3
100
65.8:1
0.2, 50 VA
1.2
500
E-923A472G02
E-923A479G02
12470/√3
100
72:1
0.2, 50 VA
1.2
500
E-923A472G03
E-923A479G03
13200/√3
100
76.2:1
0.2, 50 VA
1.2
500
E-923A472G04
E-923A479G04
13800/√3
100
69.7:1
0.2, 50 VA
1.2
500
E-923A472G05
E-923A479G05
11000/√3
100/√3
110:1
0.2, 50 VA
1.2
500
E-923A472G06
E-923A479G06
11400/√3
100/√3
114:1
0.2, 50 VA
1.2
500
E-923A472G07
E-923A479G07
12470/√3
100/√3
124.7:1
0.2, 50 VA
1.2
500
E-923A472G08
E-923A479G08
13200/√3
100/√3
132:1
0.2, 50 VA
1.2
500
E-923A472G09
E-923A479G09
13800/√3
100/√3
138:1
0.2, 50 VA
1.2
500
E-923A472G10
E-923A479G10
11000/√3
110
57.74:1
0.2, 50 VA
1.2
500
E-923A472G11
E-923A479G11
11400/√3
110
59.83:1
0.2, 50 VA
1.2
500
E-923A472G12
E-923A479G12
12470/√3
110
65.45:1
0.2, 50 VA
1.2
500
E-923A472G13
E-923A479G13
13200/√3
110
69.3:1
0.2, 50 VA
1.2
500
E-923A472G14
E-923A479G14
13800/√3
110
72.4:1
0.2, 50 VA
1.2
500
E-923A472G15
E-923A479G15
11000/√3
110/√3
100:1
0.2, 50 VA
1.2
500
E-923A472G16
E-923A479G16
11400/√3
110/√3
103.64:1
0.2, 50 VA
1.2
500
E-923A472G17
E-923A479G17
12470/√3
110/√3
113.36:1
0.2, 50 VA
1.2
500
E-923A472G18
E-923A479G18
13200/√3
110/√3
120:1
0.2, 50 VA
1.2
500
E-923A472G19
E-923A479G19
13800/√3
110/√3
125.45:1
0.2, 50 VA
1.2
500
E-923A472G20
E-923A479G20
11000/√3
115
55.2:1
0.2, 50 VA
1.2
500
E-923A472G21
E-923A479G21
11400/√3
115
57.2:1
0.2, 50 VA
1.2
500
E-923A472G22
E-923A479G22
12470/√3
115
62.6:1
0.2, 50 VA
1.2
500
E-923A472G23
E-923A479G23
13200/√3
115
66.3:1
0.2, 50 VA
1.2
500
E-923A472G24
E-923A479G24
13800/√3
115
69.3:1
0.2, 50 VA
1.2
500
E-923A472G25
E-923A479G25
11000/√3
115/√3
95.65:1
0.2, 50 VA
1.2
500
E-923A472G26
E-923A479G26
11400/√3
115/√3
99.1:1
0.2, 50 VA
1.2
500
E-923A472G27
E-923A479G27
12470/√3
115/√3
108.4:1
0.2, 50 VA
1.2
500
E-923A472G28
E-923A479G28
13200/√3
115/√3
114.8:1
0.2, 50 VA
1.2
500
E-923A472G29
E-923A479G29
13800/√3
115/√3
120:1
0.2, 50 VA
1.2
500
E-923A472G30
E-923A479G30
11000/√3
120
52.9:1
0.2, 50 VA
1.2
500
E-923A472G31
E-923A479G31
11400/√3
120
54.8:1
0.2, 50 VA
1.2
500
E-923A472G32
E-923A479G32
12470/√3
120
60:1
0.2, 50 VA
1.2
500
E-923A472G33
E-923A479G33
13200/√3
120
63.5:1
0.2, 50 VA
1.2
500
E-923A472G34
E-923A479G34
13800/√3
120
66.4:1
0.2, 50 VA
1.2
500
E-923A472G35
E-923A479G35
11000/√3
120/√3
91.7:1
0.2, 50 VA
1.2
500
E-923A472G36
E-923A479G36
11400/√3
120/√3
95:1
0.2, 50 VA
1.2
500
E-923A472G37
E-923A479G37
12470/√3
120/√3
103.9:1
0.2, 50 VA
1.2
500
E-923A472G38
E-923A479G38
13200/√3
120/√3
110:1
0.2, 50 VA
1.2
500
E-923A472G39
E-923A479G39
13800/√3
120/√3
115:1
0.2, 50 VA
1.2
500
E-923A472G40
E-923A479G40
Additional styles available upon request. Contact your ABB sales representative or call +1-252-827-3212 for more information.
ABB product bulletin | Type VOG-17 voltage transformer 3
ABB Inc. Medium Voltage Distribution Components 3022 NC 43 North Pinetops, NC 27864 USA Phone: +1 252 827 3212 Fax: +1 252 827 4286 www.abb.com/mediumvoltage
Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction–in whole or in parts–is forbidden without ABB’s prior written consent. Copyright 2010 ABB. All rights reserved.
1VAP429802-DB August 2012 Rev. C
For more information please contact: