U-Series
Air Circuit Breaker
LV &
MV Circ uit B reak ers
Leader of Technology Hyundai Heavy Industries' state-of-the-art technologies have created circuit breakers and contactors for electrical systems that are genuine masterpieces.
CONTENTS 04 Features
•
74 Dimensions
11 Structure •
•
13 Ratings
92 Ordering Codes
•
•
14 Protection Trip Relay (OCR) • 30 Accessories • 72 Circuit Diagrams
96 Technical Data
•
105 Operating Conditions
•
106 Ordering Sheet
U-Series Air Circuit Breaker HYUNDAI ACB meets your demands for high breaking capacity, full line-up, and optimized panel size. Various accessories and connection methods realize user-friendly handling.
U-Series
/ Air Circuit Breaker
Features | Full line-up |
460mm
•U-Series ACB maximize your choice and satisfaction with compact size and dual (UAN/UAS) model.
766mm 624mm
8m
36
399mm
m
328mm
B frame [100kA]
A frame [85kA] •630-2,000A(UAN) •630-1,600A(UAS)
C frame [100kA]
D frame1) [150kA] •4,000-6,300A(UAN)
•4,000-5,000A(UAN)
•2,000-4,000A(UAN) •2,000-3,200A(UAS)
※ - Breaking capacity is at AC500V. 1) D frame will be available from October 2013.
| Applications | •U-Series ACB offering high breaking capacity and advanced protection trip relay is suitable to cover various applications including buildings, data centers, industrials and so on. U-Series ACB protects these facilities from harmonic frequency by 100% capacity of N phase.
Buildings
Industrials
Electric power facilities
•Multipurpose buildings
•Broadcasting stations
•Steel/Metal
•Electric power stations
•Hospitals
•IT/Telecommunications
•Gas/Chemical
•Electric power substations
•Pulp/Paper
•Dispersed power generators
•Commercial buildings •Hotels
4
Data centers & Networks
•Renewable energy facilities
ACB
| Compliance with standards | Standard •IEC 60947-1,2
International Electrotechnical Commission
•EN 60947-2
European Standard
•GB
China National Standard (Guojia Biaozhun)
•GOST R 50030.2-99 9
Government Standard of Russia
•GOST R 50030.1-2000
Government Standard of Russia
•KS C 4620
Korean Standards Association
Approval •ISO 18001, 14001, 9001 •KS/KOREA
Korea Quality Certificate Standard Association
•CE
Community European
•GOST-R/RUSSIA
Government Standard of Russia
•CCC/CHINA
China Compulsory Certification
•KR/KOREA
Korean Register of Shipping
•GL/GERMANY
Germanischer Lloyd
•LR/U.K
Lloyd's Register of Shipping
•ABS/U.S.A
American Bureau of Shipping
•BV/FRANCE
Bureau Veritas
•NK/JAPAN
Nippon Kaiji Kyokai
CB type test •DEKRA
Formerly KEMA Quality Registered
•KERI
Korea Electrotechnology Research Institute
U-Series Air Circuit Breaker_ 5
U-Series
/ Air Circuit Breaker
Features | Various accessories |
[ Body side ]
❶
❷
❸
❹
❺
❻
❼
❽
❾
❿
❶ Motor ❷ Closing coil ❸ Trip coil ❹ Double trip coil ❺ Trip supervision coil ❻ Under voltage trip coil
6
❼ Auxiliary switch ❽ Condenser trip device ❾ Lifting lug ❿ Mechanical interlock kit Phase insulation barrier ON/OFF button cover
OCR portable checker Key lock device Wrong insertion preventer Fixing block Counter O CR & Alarm switch reset device
Test jumper Draw-in/out handle Draw-in/out and
position lock device Door flange Dust cover
ACB
[ Cradle side ]
❶
❷
❸
❹
❺
❻
❼
❽
❾
❿
❶ UVT time delay controller ❷ Remote operation module ❸ Temperature detection module ❹ Short “b”contact ❺ Position switch
❻ Mechanical interlock kit ❼ Phase insulation barrier ❽ Mechanical operated cell (MOC) switch ❾ Dummy ACB ❿ Wrong insertion preventer
Safety shutter Arc shield Control terminal protection cover
U-Series Air Circuit Breaker_ 7
U-Series
/ Air Circuit Breaker
Features | High performance protection trip relay (OCR) | •The protection trip relay (OCR) of U-Series ACB supports stable power supply with temperature alarm, fault recording, and others in addition to main protection functions. Type
UPR-1L-GL
UPR-2L-GS
UPR-1D-GT
UPR-2L-GM
Ordering 50Hz code 60Hz
33
35
36
37
43
45
46
47
•L/S/I/G •Self-power •Failsafe •Pre-trip alarm •Integrated instantaneous output contact
•L/S/I/G •Self-power •AC, DC100-250V •Failsafe •Pre-trip alarm •Individual continuous output contact •Fault event •Temperature alarm
Externals
Main function
8
•L/S/I/G •Self-power •AC, DC100-250V •Failsafe •Pre-trip alarm •Individual output contact •Fault event •Temperature alarm •Earth leakage trip •Communication (Modbus)
•L/S/I/G •Self-power •AC, DC100-250V •Failsafe •Pre-trip alarm •Individual output contact •Fault event •Temperature alarm
ACB
| Multiple terminal busbar connections | •Increases the user's convenience by diversified terminal connection methods according to busbar's type. •Simply turn a horizontal connector 90˚ to make it a vertical connector (The opposite case is same). Standard connection
Vertical
Horizontal
Front
Vertical/Horizontal
Horizontal/Vertical
Vertical/Front
Horizontal/Front
Front/Vertical
Front/Horizontal
Mixed connection (Top/Bottom)
※ - Changing connector is available only for UAN/UAS A frame 630-1,600A, UAN/UAS B frame 2,000-3,200A. - Front connection type is suitable the panel requirement for limited installation space. - Changing connection above 4,000A needs additional component, please contact us. U-Series Air Circuit Breaker_ 9
U-Series
/ Air Circuit Breaker
Features | Easy-to-install | Fixed type •Installed in a switchboard directly. Draw-out type •Consists of ACB and cradle. •Cradle is fixed to a switchboard. •ACB may be in the position of CONNECTED, TEST, ISOLATED, and REMOVED. •Switchboard door may be closed in ISOLATED position.
[ Draw-in/out guide rail ]
접속위치(Connected Position) Connected position
- Main and control circuit are all connected. - Normal condition of use
Isolated position
- Main and control circuit are all isolated. - Switchboard door may be closed in isolated position.
10
Test position
- Main circuit is isolated, control circuit is connected. - Control test is possible when switchboard’s door is closed.
Removed position
- ACB is totally drawn out from the cradle.
ACB
Structure | Externals | [ Front ] ❶
❶
❷
❸
❹ ❺
❻
❷ ❸
❹ ❺
❻ ❼ ❽ ❾ ❿
[ Fixed type ]
[ Draw-out type ]
[ Cradle ]
[ Inside ]
❶ Control terminal ❷ Front cover ❸ Close/Open indicator ❹ Close button ❺ Protection trip relay (OCR) ❻ Open button
[ Rear ]
❼ Position lock device ❽ Position lock release button ❾ Draw-in/out handle insertion hole ❿ Position indicator Counter Charged/Discharged indicator
Manual charging handle Name plate Arc shield Terminal busbar OCR & Alarm switch reset button Draw-in/out guide rail
U-Series Air Circuit Breaker_ 11
U-Series
/ Air Circuit Breaker
Structure | Internals |
❶ ❷ ❸ ❹ ❺
❻ ❼ ❽ ❾
❿
❶
❻
❹
❽
❾
❿
❶ Arc chamber ❷ Frame ❸ Counter ❹ Auxiliary switch ❺ Motor ❻ Closing/Trip/UVT coil
12
❼ MHT device ❽ Protection trip telay (OCR) ❾ Mechanism ❿ Draw-in/out device Front cover Control terminal protection cover
Control terminal Manual charging handle Closing spring Moving contact Fixed contact T erminal busbar
Current transformer Terminal clip Cradle
ACB
Ratings Frame
A frame
B frame
06 : 630 08 : 800 10 : 1,000 12 : 1,250 16 : 1,600 20 : 2,000
06 : 630 08 : 800 10 : 1,000 12 : 1,250 16 : 1,600 20 : 2,000 25 : 2,500 32 : 3,200 40 : 4,000
Model
Rated operating voltage (Ue) (V) Rated insulation voltage (Ui) (V) Frequency (Hz) Number of poles Current setting range (….. x In max) Rated current of neutral pole (…..% x In)
UAS 20 : 2,000 25 : 2,500 32 : 3,200
20,000
10,000
20,000
15,000
2,000
2,000
30,000
20,000
Without maintenance
5,000
06-20 : 10,000 25-40 : 5,000
2,000
5,000
5,000
With maintenance
10,000
06-20 : 15,000 25-40 : 10,000
5,000
10,000
10,000
65 85 85 143 187 187 65 60 50
Electrical
AC 690 AC 1,000 50/60 3, 4 0.4-1.0 100% 85 100 100
55 65 65
187 220 220 85 75 65
121 143 143 55 45 36
70 85 85 100% 154 187 187 70 65 55 12 40 10 40
Draw-out type
63
06-32 : 87 40 : 107
145
63
87
Fixed type
34
06-32 : 44 40 : 61
76
34
44
Draw-out type
280
06-32 : 130 40 : 61
173
74
103
Fixed type
44
06-32 : 55 40 : 81
81
44
55 399 x 460 x 368
3 pole Weight (kg) 4 pole
4 pole
06 : 630 08 : 800 10 : 1,000 12 : 1,250 16 : 1,600
30,000
IEC 60947-2 AC 690/600/550V category “B” AC 500/480/460V KS C 4620 AC 415/380/230/220V Rated service breaking capacity (…..% x Icu) Rated making capacity IEC 60947-2 AC 690/600/550V (Icm) category “B” AC 500/480/460V (kA peak) KS C 4620 AC 415/380/230/220V 1 sec Rated short-time capacity (Icw) 2 sec (kA, without Inst.) 3 sec Rated impulse withstand voltage (Uimp) (kV) Maximum total breaking time (ms) Motor charging time (sec) max. Closing operating time Closing time (ms) max. Without maintenance Mechanical With maintenance
3 pole
32 : 3,200 40 : 4,000 50 : 5,000
B frame
AC 690 AC 1,000 50/60 3, 4 0.4-1.0 100% 85 100 100 100% 187 220 220 85 75 65 12 40 10 40 15,000
Rated breaking capacity (Icu) (kA sym)
External dimension (mm) (WxHxD, except busbar)
A frame
UAN
Recognition order code: Rated current (In max at 40˚C) (A)
Life cycle (times)
C frame
Draw-out type Fixed type Draw-out type Fixed type
399 x 460 x 368
624 x 460 x 368
328 x 460 x 368
337 x 404 x 296
408 x 404 x 296
633 x 404 x 296
337 x 404 x 296
408 x 404 x 296
413 x 460 x 368
514 x 460 x 368
794 x 460 x 368
413 x 460 x 368
514 x 460 x 368
422 x 404 x 296
523 x 404 x 296
803 x 404 x 296
422 x 404 x 296
523 x 404 x 296
Draw-out type
H
H
Fixed type
328 x 460 x 368
W
D
W
D
U-Series Air Circuit Breaker_ 13
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR) | Overview |
❶ LCD display window ❷ Fault indication LED
❷ PTA: Pre-trip alarm LTD: Long time delay
❶
❺
❸
STD/INST: Short time or instantaneous tripping GFT/ELT: Ground fault trip or earth-leakage trip TAL: Temperature alarm
❸ Overload indication LED ❹ Function key
❹
❽ ❻
❼ ❾
❿
14
Reset: Fault reset Hi/Low: Field test function (Hi: STD/INST, Low: LTD) Move List: Secondary menu Enter: Setting input
❺ Phase indication Iine ❻ Ir: Long time current setting knob
Tr: Long time tripping delay setting knob ❼ Isd: Short time current setting knob Tsd: Short time tripping delay setting knob ❽ Ii: Instantaneous current setting knob ❾ GFT/STD, MCR setting knob ❿ Ip: Pre-trip alarm current setting knob Tp: Pre-trip alarm delay setting knob Ig: Ground fault current setting knob Tg: Ground fault tripping delay setting knob Rated current setting knob Test jack Earth leakage pick-up and tripping delay setting knob
ACB
General feeder
Application
Generator
UPR-1L-GL
UPR-2L-GS
UPR-1D-GT
UPR-2L-GM
UPR-1S-AL
UPR-2S-AS
Control power Self power Long time delay (LTD) Short time delay (STD) Instantaneous trip (INST) Pre trip alarm Ground fault trip Field test Failsafe True RMS detection Fault indication LED Overload indication LED Display window
-
-
Integrated instantaneous contact (1a)
-
-
PTA: 1a L/S/I/G: 2a
-
Individual continuous contact (4a)
-
PTA: 1a L/S/I/G: 2a
-
MCR Temperature detection Event/Fault recording Earth leakage trip (ELT) Communication
-
-
-
-
Externals
Power supply
Protection
Indication
Output contact
Optional function ※ : Standard
LTD: 1a S/I: 1a PTA:1a -
: Option
O rdering codes Model UPR-1L-GL UPR-2L-GS UPR-1D-GT UPR-2L-GM UPR-1S-AL UPR-2S-AS UPR-1L-GL UPR-2L-GS UPR-1D-GT UPR-2L-GM UPR-1S-AL UPR-2S-AS
Ordering codes Frequency Complete parts Spare part of ACB/Cradle
50Hz
60Hz
33 35 36 37 38 39 43 45 46 47 48 49
UANS OCR33A/33J UANS OCR35A/35J UANS OCR36A/36J UANS OCR37A/37J UANS OCR38A/38J UANS OCR39A/39J UANS OCR43A/43J UANS OCR45A/45J UANS OCR46A/46J UANS OCR47A/47J UANS OCR48A/48J UANS OCR49A/49J
Application Specifications for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type for auto connection/manual connection type
UAN UAS
Mounting position
Inside of ACB body
U-Series Air Circuit Breaker_ 15
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR) | UPR-1L-GL | •Overload protection - Long time delay
•Short circuit protection - Short time delay, instantaneous trip - I2t on/off optional (for STD)
•Ground fault protection - I2t on/off optional
•Self power •1a DO (Digital output)
Characteristic Ir: Long time current setting tr: Long time tripping delay setting
Ir
Isd: Short time current setting
tr
tsd: Short time tripping delay setting Ii: Instantaneous current setting
Isd
Ig I2t on tg
Ig: Ground fault current setting
tsd Ii
I2t off
I2t off
tg: Ground fault tripping delay setting
I2t on
Protection Current setting (Ir) Long time
Time delay (tr) Accuracy: ±15% or below 100ms Current setting (Isd)
Short time
Instantaneous
Time delay (tsd) at 10×Ir Accuracy: ±20% Current setting (Ii) Trip time
In = Ict×…
(A)
0.5
0.63
0.7
0.8
0.9
1
Ir = In×…
(A)
0.8
0.83
0.85
0.88
0.9
0.93
0.95
0.98
1
Non
(sec) 10.4 (sec) 0.5 (sec) 0.35
26.1
41.7
52
104
208
312
417
521
626
1.25 0.86
2 1.38
2.5 1.73
5 3.45
10 6.9
15 10.4
20 13.8
25 17.3
30 20.7
1.5 0.1
2 0.2
2.5 0.3
3 0.4
4 0.5
6
8
10
Non
tr at (1.5×Ir) tr at (6.0×Ir) tr at (7.2×Ir) Isd = In×… tsd
I2t off I2t on
Min. trip time (msec) (I2t off) Max. trip time (msec) Ii = In×… (A)
16
Time delay (tg) at 1×In Accuracy: ±20%
0.1
0.2
0.3
0.4
0.5
20 80
80 140
160 240
260 340
360 440
460 540
2
3
4
6
8
10
12
15
Non
0.7
0.8
1
below 50ms
Pick-up (Ig) Accuracy: ±15% (Ig>0.4In) Ig = Ict×… ±20% (Ig≤0.4In) Ground fault
1 (A) (sec) 0.05 (sec) 0.05
tg (I2t off)
I2t off I2t on
0.1
0.2
0.3
0.4
0.5
0.6
(sec) 0.05 (sec) 0.05
0.1
0.2
0.3
0.4
0.5
0.1
0.2
0.3
0.4
0.5
(A)
Min. trip time (msec)
20
80
160
260
360
460
Max. trip time (msec)
80
140
240
340
440
540
Non
ACB
| UPR-2L-GS, UPR-2L-GM | •Overload protection
•Event recording
- Long time delay
- Short time delay, instantaneous trip - I2t on/off optional (for STD)
•Short circuit protection - Short time delay, instantaneous trip - I2t on/off optional (for STD)
•Pre-trip alarm - Prevent unnecessary over load trip according to rated current (In)
•Ground fault protection
•Field test
- I2t on/off optional
•Realization of protective coordination by ZSI (Zone selective interlocking)
- Simulation of long time, short time, instantaneous delay
•4a(3a) DO (Digital output) - 4a (UPR-2L-GS) - 3a (UPR-2L-GM)
•Fault recording - Records max. up to 10 fault information about fault type, fault phase, fault valve, occurrence time of fault
Characteristic Ir: Long time current setting tr: Long time tripping delay setting
Ir IP
Isd: Short time current setting
tr
tsd: Short time tripping delay setting Ii: Instantaneous current setting
Tp
I2t off
tg: Ground fault tripping delay setting
I2t on
Isd
Ig I2t on tg
Ig: Ground fault current setting
tsd
tp: Pre-trip alarm delay setting
Ii
I2t off
Ip: Pre-trip alarm current setting
Protection Current setting (Ir) Long time
Time delay (tr) Accuracy: ±15% or below 100ms Current setting (Isd)
Short time
Instantaneous
Time delay (tsd) at 10×Ir Accuracy: ±15% Current setting (Ii) Trip time Pick-up (Ig)
Ground fault
Time delay (tg) at 1×In Accuracy: ±15% (Ig>0.4In) ±20% (Ig≤0.4In)
Current setting (Ip) Pre trip alarm Accuracy: ±15% Time delay (tp)
In = Ict×…
(A)
0.5
0.63
0.7
0.8
0.9
1
Ir = In×…
(A)
0.8
0.83
0.85
0.88
0.9
0.93
0.95
0.98
1
Non
(sec) 10.4 (sec) 0.5 (sec) 0.35
26.1
41.7
52
104
208
312
417
521
626
1.25 0.86
2 1.38
2.5 1.73
5 3.45
10 6.9
15 10.4
20 13.8
25 17.3
30 20.7
1.5 0.1
2 0.2
2.5 0.3
3 0.4
4 0.5
6
8
10
Non
tr at (1.5×Ir) tr at (6.0×Ir) tr at (7.2×Ir) Isd = In×… tsd
I2t off I2t on
1 (A) (sec) 0.05 (sec) 0.05
Min. trip time (msec) (I2t off) Max. trip time (msec) (A) Ii = In×…
0.1
0.2
0.3
0.4
0.5
20 80
80 140
160 240
260 340
360 440
460 540
2
3
4
6
8
10
12
15
Non
0.3 0.2
0.4 0.3
0.5 0.4
0.6 0.5
0.7
0.8
1
Non
Non
below 50ms In = Ict×… I2t off tg I2t on
0.1 (sec) 0.05 (sec) 0.05
0.2 0.1 0.1
0.2
0.3
0.4
0.5
Min. trip time (msec) (I2t off) Max. trip time (msec)
20 80
80 140
160 240
260 340
360 440
460 540
Ip = In×…
0.6
0.65
0.7
0.75
0.8
0.85
0.9
0.95
1
5
10
15
20
40
60
80
120
160
tp
(A) (sec)
U-Series Air Circuit Breaker_ 17
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR) | UPR-1D-GT | •Overload protection
•Event recording
- Long time delay
- Records events of device related to setting change, operation and state change (Max. up to 10)
•Short circuit protection - Short time delay, instantaneous trip - I2t on/off optional (for STD)
•Pre trip alarm - Prevent unnecessary over load trip according to rated current (In)
•Ground fault protection - I t on/off optional 2
•Realization of protective coordination by ZSI (Zone selective interlocking)
•Field test
•Fault recording
•4a DO (Digital output)
-R ecords max. up to 10 fault information about fault type, fault phase, fault valve, occurrence time of fault
- Simulation of long time, short time, instantaneous delay
•Communication: Modbus-RTU/RS-485 •Earth leakage trip (Optional)
Characteristic Ir: Long time current setting
Ir IP
tr: Long time tripping delay setting Isd: Short time current setting
tr
tsd: Short time tripping delay setting
Tp
Ii: Instantaneous current setting
Isd
Ig I2t on tg I2t off
I2t on tsd
tp: Pre-trip alarm delay setting
Ii
I2t off
tg: Ground fault tripping delay setting Ig: Ground fault current setting Ip: Pre-trip alarm current setting
Protection Current setting (Ir) Long time
Time delay (tr) Accuracy: ±15% or below 100ms Current setting (Isd)
Short time
Instantaneous
Ground fault
Time delay (tsd) at 10×Ir Accuracy: ±15% Current setting (Ii) Trip time Pick-up (Ig) Time delay (tg) at 1×In Accuracy: ±15%(Ig>0.4In) ±20%(Ig≤0.4In)
Current setting (Ip) Pre trip alarm Time delay (Tp) Accuracy: ±15% Current setting (IΔn) Earth leakage Time delay (Δt) (optional) Accuracy: ±15% or below 40ms
18
In = Ict×… Ir = In×… tr at (1.5×Ir) tr at (6.0×Ir) tr at (7.2×Ir) Isd = In×…
(A) (A) (sec) (sec) (sec) (A) (sec) I2t off tsd (sec) I2t on Min. trip time (msec) 2 (I t off) Max. trip time (msec) Ii = In×… (A) Ig = Ict×… I2t off (sec) tg (sec) I2t on Min. trip time (msec) 2 (I t off) Max. trip time (msec) Ip = In×… (A) tp
(sec)
IΔn Δt
Alarm time Trip time
(A) (msec) (msec)
0.5 0.63 0.8 0.83 10.4 26.1 0.5 1.25 0.35 0.86 1 1.5 0.05 0.1 0.05 0.1 20 80 80 140 2 3 below 50ms 0.1 0.2 0.05 0.1 0.05 0.1 20 80 80 140 0.6 0.65
0.7 0.85 41.7 2 1.38 2 0.2 0.2 160 240 4
0.8 0.88 52 2.5 1.73 2.5 0.3 0.3 260 340 6
0.9 0.9 104 5 3.45 3 0.4 0.4 360 440 8
1 0.93 208 10 6.9 4 0.5 0.5 460 540 10
0.3 0.2 0.2 160 240 0.7
0.4 0.3 0.3 260 340 0.75
0.5 0.4 0.4 360 440 0.8
0.95 312 15 10.4 6
0.98 417 20 13.8 8
1 521 25 17.3 10
12
15
Non
0.6 0.5 0.5 460 540 0.85
0.7
0.8
1
Non
0.9
0.95
1
Non
5
10
15
20
40
60
80
120
160
0.5 140 60
1 230 140
2 350 230
3 800 350
5 950 800
10 80
20 120
30 160
Non
Non 626 30 20.7 Non
ACB
| UPR-1S-AL | •Overload protection - Long time delay
•Short circuit protection - Short time delay, instantaneous trip - I2t on/off optional (for STD)
•Ground fault protection - I2t on/off optional (for STD)
•Self power •1a DO (Digital output)
Characteristic Ir: Long time current setting tr: Long time tripping delay setting
Ir
Isd: Short time current setting
tr
tsd: Short time tripping delay setting Ii: Instantaneous current setting
I2t on
Isd
tsd Ii
I2t off
Protection Current setting (Ir) Long time
Time delay (tr) Accuracy: ±15% or below 100ms Current setting (Isd)
Short time
Instantaneous
Time delay (tsd) at 10×Ir Accuracy: ±15% Current setting (Ii) Trip time
In = Ict×… Ir = In×…
(A)
1.1
1.15
1.2
1.25
50
60
70
80
100
120
(sec) 10 (sec) 0.99
15 1.49
20 1.99
25 2.48
30 2.98
35 3.48
40 3.97
50 4.97
60 5.96
1 (A) (sec) 0.05 (sec) 0.05
1.5 0.1
2 0.2
2.5 0.3
3 0.4
3.5 0.5
4
4.5
5
12
15
Non
(sec)
tr at (1.2×Ir) tr at (3×Ir) Isd = In×… tsd
I2t on
20
40
tr at (1.05×Ir)
I2t off
(0.5-1.0) x1% unit, or 1A unit 0.7 0.8 0.9 1 1.05 30
(A)
Min. trip time (msec) (I2t off) Max. trip time (msec) Ii = In×… (A)
0.1
0.2
0.3
0.4
0.5
20 80
80 140
160 240
260 340
360 440
460 540
2
3
4
6
8
10
Non
Non
below 50ms
U-Series Air Circuit Breaker_ 19
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR) | UPR-2S-AS | •Overload protection
•Event recording
- Long time delay
- Records events of device related to setting change, operation and state change (Max. up to 10)
•Short circuit protection - Short time delay, instantaneous trip - I2t on/off optional (for STD)
•Realization of protective coordination by ZSI (Zone selective interlocking)
•Pre trip alarm - Prevent unnecessary over load trip according to rated current (In)
•Field test - Simulation of long time, short time, instantaneous delay
•Fault recording -R ecords max. up to 10 fault information about fault type, fault phase, fault valve, occurrence time of fault
•3a DO (Digital output)
Characteristic Ir: Long time current setting tr: Long time tripping delay setting
Ir IP
Isd: Short time current setting
tr
tsd: Short time tripping delay setting Ii: Instantaneous current setting
Tp Isd
tp: Pre-trip alarm delay setting
I2t on
Ip: Pre-trip alarm current setting
tsd Ii
I2t off
Protection Current setting (Ir) Long time
Time delay (tr) Accuracy: ±15% or below 100ms Current setting (Isd)
Short time
Instantaneous
Ground fault
20
Time delay (tsd) at 10×Ir Accuracy: ±20% Current setting (Ii) Trip time
In = Ict×… Ir = In×…
(A)
1.1
1.15
1.2
1.25
50
60
70
80
100
120
(sec) 10 (sec) 0.99
15 1.49
20 1.99
25 2.48
30 2.98
35 3.48
40 3.97
50 4.97
60 5.96
1 (A) (sec) 0.05 (sec) 0.05
1.5 0.1
2 0.2
2.5 0.3
3 0.4
3.5 0.5
4
4.5
5
(sec)
tr at (1.2×Ir) tr at (3×Ir) Isd = In×… tsd
I2t on
20
40
tr at (1.05×Ir)
I2t off
(0.5-1.0) x1% unit, or 1A unit 0.7 0.8 0.9 1 1.05 30
(A)
Min. trip time (msec) (I2t off) Max. trip time (msec) Ii = In×… (A)
0.1
0.2
0.3
0.4
0.5
20 80
80 140
160 240
260 340
360 440
460 540
2
3
4
6
8
10
12
15
Non
Non
Non
below 50ms
Current setting (Ip)
Ip = In×…
Time delay (Tp) Accuracy: ±15%
tp
(A) (sec)
0.7
0.75
0.8
0.85
0.9
0.95
1
1.05
1.1
1
5
10
15
20
25
30
35
40
Non
ACB
| Operation characteristics |
Long time delay (LTD)
t Ir tr
t Ir
I
tr
t t Ig
Ir
Short time delay (STD) tr
I I2t on I2t off
Isd Tsd
I I I2t on t t
Time delay setting
Ig2t on •L type - Standard operating time (sec) is based the time of 600%×[Ir] with inverse time operation. Ig2on t off - Setting range: 0.5, 1.25,Ig2, 2.5, 5, 10, 15, 20, 25, 30sec (10 modes) - The breaker is tripped t at ±15% of setting time. Tg •S type I - Standard operating time (sec) is based on the time of 120%×[Ir] with inverse time operation. - Setting range: 10, 15, 20, 25, 30, 35, 40, 50, 60sec (9 modes) - The breaker is tripped at ±15% of setting Ig2t ontime.
t t
t
Standard current setting
•L type - The scale is marked as magnification of [In]. - Setting range: (Non, 0.8, 0.83, 0.85, 0.88, 0.9, 0.93, 0.95, 0.98, 1.0)×In (10 modes) - No protection in case of non setting of [Ir]. - The breaker is not tripped below 105% of [Ir], and tripped at 120%. •S type t - Setting range: (Non, 0.7, 0.8, 0.9, 1.0, 1.05, 1.1, 1.15, 1.2, 1.25 )×In (8 modes) - The breaker is tripped above 100% of [Ir].
Isd Tsd
I2t off
I I2t on Isd Tsd
Ig2t off
Standard current setting
•L type Tg - The scale is marked as magnification of [In]. I Ig2t on - Setting range: (Non, 1, 1.5, 2, 2.5, 3, 4, 6, 8, 10)×In (10 modes) •S type Ig2t off I∆ n Ig - The scale is marked as magnification of [In]. - Setting range: (Non, t 1, 1.5,T2,g 2.5, 3, 3.5, 4, 4.5, 5)×In (10 modes) ∆T I I Time delay setting •L type - Standard operating time (msec) is based on the time of 120%×[Isd] with definite time operation. - Setting range: 50, 100, 200, 300, 400, 500msec (6 modes) t curveI∆applied - 1000% of inverse time in case of inverse time (I2t on) setting. n •S type t - Standard operating time (msec) is based on the time of 120%×[Isd] with definite time operation. ∆T - The range of set time is 50, 100, 200, 300, 400, 500msec (6 step). I - 500% of inverse time curve applied in case of inverse time (I2t on) setting.
I2t off
I∆ n
Instantaneous trip (INST) t
Ii I
Tp(S type)
Ip
Standard current setting ∆T
t as magnification of [In]. I - The scale is marked Tp - Setting range: (Non, 2, 3, 4, 6, 8, 10, 12, 15)×In (9I modes) - No protection in case of non setting of [Ii].
I
Time delay setting Tp(S type) - Total breaking time is below 50ms. t Ip
t Ii
Tp I
I Tp(S type) Ip
Ii
Tp I
I
U-Series Air Circuit Breaker_ 21
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR) | Operation characteristics |
Ground fault trip (GFT)
Time delay setting
•L type - Standard operating time (msec) is based on the time of 120%×[Ig] with definite time operation. - Setting range: 50, 100, 200, 300, 400, 500msec (6 modes) - Inverse time operated with 100% of [Ict] standard in case of [I2t on] setting. - The breaker is tripped at ±15% of setting time.
t
Ig2t on Ig2t off
Ig t
Standard current setting
•L type - The scale is marked as magnification of OCR rated primary current [ICT]. - Setting range: (Non, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 1.0)×[ICT] (10 modes)
Tg I Ig2t on Ig2t off
tt Ig
Earth leakage trip (ELT) Ig2t on Ig2t off
I
Ig t
I∆ n
Standard current setting
•L type - The scale is marked as magnification of OCR rated primary current [ZCT]. - Setting range: (Non, 0.5, 1, 2, 3, 5, 10, 20, 30[A]) (9 modes)
Tg
T∆T g
II
Time delay setting
•L type - Settings within its alarm range will prevent its breaker from tripping but activating its alarm. - Trip time: 60, 140, 230, 350, 800msec (5 modes) - Alarm time: 140, 230, 350, 800, 950msec (5 modes)
I∆ n
t t
∆T
I
I∆ n Tp(S type) Ip ∆T tPre-trip alarm (PTA) I Tp I
Tp(S type) t Ip
I Tp(S type) Ip Tp I
Standard current setting
•L type - The scale is marked as magnification of [In] with definite time operation. - Setting range: (Non, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0)×In (10 modes) •S type - The scale is marked as magnification of [In] with inverse time operation. - Setting range: (Non, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 1.1)×In (10 modes)
Tp
22
Time delay setting
•L type - Standard operating time (sec) is based on the time of 100%×[Ip]. - Setting range: 5, 10, 15, 20, 40, 60, 80, 120, 160, 200sec (10 modes) •S Type - Standard operating time (sec) is based on the time of 120%×[Ip]. - Setting range: 1, 5, 10, 15, 20, 25, 30, 35, 40sec (9 modes)
ACB
| Circuit diagrams | UPR-1L-GL NCT k ℓ T
S
R
R
S
T
21
29 30
N L/S I/G
NCT NCT 1 2
UPR-1L-GL
CT3
Rn Sn Tn Nn Ac
A
C TN T P TP
CT2
MHT
CT1
TN
1a for MCR Rn
Sn
22
Tn
UPR-2L-GS AC,DC100-250V
S0 - S2 Source
NCT k ℓ S
R
T
R
S
T
N
+
21 23
29 30
19
L PT
NCT NCT 1 2
S2
-
UPR-2L-GS
CT3
Rn Sn Tn Nn Ac S/I G/E ZI 1
ZI 2
ZO ZO 2 1
A
C TN TP S 0 TP
CT2
MHT
CT1
TN
1a for MCR Rn
Sn
Tn
22 24 26 31 32 33 34 +
In
ZSI
20
+ Out
U-Series Air Circuit Breaker_ 23
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR) | Circuit diagrams | UPR-1D-GT AC,DC100-250V
S0 - S2 Source
ZCT NCT k ℓ k ℓ T
S
R
21 23
R
S
T
N
L P/T
+
-
27 28 29 30
19
ELT ELT NCT NCT 2 1 2 1
S2
UPR-1D-GT
CT3
ZI ZO 2 1
Rn Sn Tn Nn Ac S/I G/E ZI 1
ZO COM COM 2
A
C TN TP S 0 TP
CT2
MHT
CT1
TN
1a for MCR Rn
Sn
20
22 24 26 31 32 33 34 35 36
Tn
+
In
ZSI
+ - + Out Communication
UPR-2L-GM AC,DC100-250V
S0 - S2 Source
NCT k ℓ S
R
T
R
S
T
+
21 23
29 30
19
N L/S PT I/G
NCT NCT 1 2
S2
UPR-2L-GM
CT3
ZI Rn Sn Tn Nn Ac1 Ac2 L/S I/G 1
ZI 2
ZO ZO 2 1
A
C TN TP S 0 TP
CT2
MHT
CT1
TN
1a for MCR Rn
Sn
Tn
22 24 26 31 32 33 34 +
24
In
ZSI
+ Out
20
-
ACB
UPR-1S-AL
T
S
R
21
R
S
T
L/ N SI
UPR-1S-AL
CT3
Rn Sn Tn Nn Ac
A
C TN T P TP
CT2
MHT
CT1 TN
1a for MCR Rn
Sn
22
Tn
UPR-2S-AS AC,DC100-250V
S 0 - S2 Source +
S
R
T
R
S
T
N
21 23
19
L PT
S2
-
UPR-2S-AS
CT3
Rn Sn Tn Nn Ac S/I ZI 1
ZI 2
ZO ZO 1 2
A
C TN TP S 0 TP
CT2
MHT
CT1
TN
1a for MCR Rn
Sn
Tn
22 24 31 32 33 34 +
In
ZSI
20
+ Out
U-Series Air Circuit Breaker_ 25
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR) | Characteristic curves |
Hour
General feeder
4 3
❶
❹
2 1 50 40 30
❺ ❷
Minute
20 10 8 6 5 4 3
❸
2
Operating time
1 50 40 30 20 10 8 6 5 4 3
Second
2 1 0.8 0.6 0.5 0.4 0.3
500ms
500ms
50ms
50ms
0.2 0.1 0.08 0.06 0.0 0.05 0.04 0.03 0.02
Percent for rated primary current of OCR [ICT]
❶ Long time delay current setting range ❷ Short time delay current setting range
26
2500 3000
2000
1500
600 700 800 900 1000
500
400
250 300
200
150
125
60 70 80 90 100
50 60 70 80 90 100
40
30
20
15
7 8 9 10
0.01 0.008 0.006 0.005
Percent for base current of OCR [Io]
❸ Instantaneous tripping current setting range ❹ Ground fault trip current setting range
❺ Pre-trip alarm current setting range
ACB
Hour
Generator
❶
4 3 2 1 50 40 30
❹
Minute
20 10 8 6 5 4 3
❷
2
Operating time
1 50 40 30
❸
20 10 8 6 5 4 3
Second
2 1 0.8 0.6 0.5 0.4 0.3
500ms
0.2 0.1 0.08 0.06 0.05 0.0 0.04 0.03
50ms
0.02
2500 3000
2000
1500
600 700 800 900 1000
500
400
250 300
200
150
125
50 60 70 80 90 100
40
30
20
15
7 8 9 10
0.01 0.008 0.006 0.005
Percent for base current of OCR [Io]
❶ Long time delay current setting range ❷ Short time delay current setting range
❸ Instantaneous tripping current setting range ❹ Pre-trip alarm current setting range
U-Series Air Circuit Breaker_ 27
U-Series
/ Air Circuit Breaker
Protection Trip Relay (OCR) | Zone selective interlock function | Zone selective interlocking drops delay time that eliminates faults for breakers. It minimizes the shock that all kinds of electric machinery get under fault conditions.
Example In case of that short time-delay or ground fault accident occurs at ZSI built in system, the breaker at accident site sends ZSI signal to halt upstream breaker’s operation. To eliminate a breakdown, trip relay of ACB at accident site activates trip operation without time delay. The upstream breaker that received ZSI signal adhere to pre-set short time-delay or ground fault time delay for protective coordination in the system. However upstream breaker that did not receive its signal will trip instantaneously. For ordinary ZSI operation, it should arrange operation time accordingly so that downstream circuit breakers will react before upstream ones under overcurrent/short time delay/ground fault situations. ZSI connecting line needs to be maximum 3m.
ACB 1 Out
Zone 1
In
ACB 2-1
ACB 2-2 Out
Zone 2
Fault A
In
ACB 3-1
Zone 3
ZSI connecting
28
ACB 3-2
ACB 3-N
Out
Out
In
In
Fault B
Out In
ACB
| System diagram |
R
S
T
N ACB trip
ACB
Display (LCD, LED) MHT Rogowski CT
Measurement part
Trip operation
Relay selection
PTA contact
MCU processing
LTD contact External contact
STD/INST contact GFT contact
Power CT
Self power
COMMON contact
Trip relay ZSI
ZCT
110V - 220V
Earth leakage
COMM.
SMPS power
Test terminal
ZSI output + ZSI output ZSI input + ZSI input -
RS-485 + RS-485 -
| Communication function | Modbus-RTU / RS-485
•Operation mode: Differential •Distance: Max.1.2km •Cable: RS-485 shielded twist 2-pair cable •Baud rate: 9,600, 19,200, 38,400 bps •Transmission method: Half-duplex •Termination: 150Ω
SCADA system
Modbus/RS-485
U-Series Air Circuit Breaker_ 29