MEDIUM VOLTAGE SWITCHGEAR AND CONTROLGEAR MODEL
MS
Safety Precautions Please read the instruction manual before using the device.
G-199-3-C9173-A HQ1303 Printed in Japan (MDOC)
New Publication, effective Mar. 2013. Specifications are subject to change without notice.
Since the 1950s, Mitsubishi Electric has been providing power distribution equipment and systems matched to the needs of the era. Now, inheriting the technologies and reliability forged from this manufacturing record of over half a century, the MS Series switchgear realizes the next evolutionary step forward. Page
STANDARD & RATINGS
3
MP Series multi-relay ● Combining the MP23 and wide-range CT makes it easy to cope with the changes in load capacity by using only the CT ratio setting changes of the multi-relay (CT setting ranges are 60~600A and 200~2,000A). ● Display lights protrude from the panels to enhance visibility when viewing panels from side-on.
Easy maintenance
Consideration for easy maintenance ● Through vertical location of the main busbar, maintenance from the back of panels is simplified, reducing maintenance work. ● The number of bolts for busbar connection has been reduced. This contributes to easier maintenance to check the bolt condition.
Intelligent
VACUUM CIRCUIT BREAKER
SECTION VIEW OF “MS”
VACUUM MAGNETIC CONTACTOR
VPR-C Series VCBs ● Comply with Restriction of Hazardous Substances (RoHS). ● Long-life grease and non-lubricated bearing realize reduced maintenance.
F E ATURES HIGH RELIABILITY
6 7
SECTION VIEW OF “LSH”
8
CONSTRUCTION
9
Innovation
Ecoconscious
5
1. Operation for Vacuum Circuit Breaker 2. Grounding busbar 3. Control circuit 4. Single line diagram 5. Arrangement 6. System compatibility
OUTLINE DIMENSION
11
1. MS 2. LSH
MP Relay
13
9
14
ACCESSORIES
MS is designed with the benefit of Mitsubishi’s vast medium voltage panels production experience of hundreds of thousands of panels over the last almost 60 years. 3D-Thermo Fluid Analysis of the switchgear structure has led to a heat-resistant design in which circuit breakers up to 3150 A are self-cooled (i.e. cooling fans not required). The reduced number of parts decreases the chance of failure.
SAFETY Partitions between compartments and an automatic shutter system (for withdrawable equipment primary junctions) completely isolate live parts.
EASY INSTALLATION Installation and testing duration are considerably reduced as the panel is tested and adjusted in the factory and then delivered as a complete unit.
1
2
1
STANDARD & RATINGS Various construction grades Ratings
JEM
Type designation
MS
Applied standard
IEC 62271-200 , JEM1425
Rated voltage Rated frequency
3.6 7.2
[Hz] fr
50, 60
Rated short-time withstand current , symmetrical [kA, rms] Ik Rated peak withstand current Rated duration of short-circuit Control voltage
[kA, peak] Ip [sec] tk [V,AC/DC]
Loss of service continuity category
LSC2B-PM
PW/PWG
CW
LSC2B-PI
LSC1 LSC2A-PI LSC2A-PM
Circuit breaker compartment Cable compartment
Partition plate
1
[kV, rms] Ur
Bushing Shutter
Busbar compartment
2XCT VCB
16 22 45 60
10 16 30 45
[A, rms] Ir 630, 1250, 2000, 3150
IEC
IEC 62271-200 , JEM1225
1
Rated insulation level Short-duration power frequency withstand voltage, 1 min. [kV, rms] Ud Lightning impulse withstand voltage [kV, peak] Up Rated normal main busbar current
LSH
MW/MWG
R S
Sectional View
T VCB
Circuit breaker compartment
40
50 Hz: 2.5×Ik , 60 Hz: 2.6×Ik 0.5, 1
0.5
DC48, 100, 110, 125, 220
AC100/110, 200/220V
5
IEC:Max. LSC2B-PM
IEC:Max. LSC2A-PM
JEM:Metal-Clad
JEM:Class M5
Structure
R S
Busbar
T
2XCT
VCB
Partition plate
Busbar compartment
VCB
Busbar
400, 630, 800, 1250, (2000) 4
25, 31.5, 40
2XCT
(Example of feeder panel)
●All compartments for busbars, circuit breakers and cables are separated by partition plates made of metal.
●All compartments for busbars, circuit breakers and cables are separated by partition plates made of metal or insulation materials.
●Bushing for the main circuit passage between compartments (for the MWG Series, the main circuit has insulation coating).
●Bushing used for the main circuit passage between compartments (for the PWG Series, the main circuit has insulation coating).
2XCT
(Example of feeder panel) ●Small number of compartments ●No partition plates ●Low protective class even with partition plates
●Enclosure: IP2X (Ø12mm) or less
Location
Indoor, Outdoor
Degree of protection
IP codes
Indoor:max. IP4X, Outdoor:max. IP33
Ambient temperature
[℃]
-5 ~ 40
Altitude a.s.l.
[m]
max.1000
Humidity R.H. Water vapour pressure
[%] [kPa]
Earthquake protection2 Horizontal seismic withstand3 Vertical seismic withstand
[m/s ] [m/s2]
max. 95 average 2.2
Interface between Enclosure and Circuit Breaker
●Partition: IP2X (Ø12mm) or less (excluding CW, LSC1, LSC2A-PI, LSC2A-PM) ●Protective plates between control room and main circuit: IP1X (Ø50mm)
●Main circuit: Automatic connection
●Main circuit: Automatic connection
●Main circuit: Automatic connection
●Control circuit: Manual connection
●Auxiliary circuit: Manual connection
●Control circuit: Manual connection
●Automatic shutters for touch protection are applied between main contacts of circuit breaker and enclosure.
●Automatic shutters for touch protection are applied between main contacts of circuit breaker and enclosure.
Comparison table between JEM 1425 and IEC 62271-200 2
1. Internal Arc Classification will not be applicable. 2. General use, class B on the upper floor or roof of building according to JEM-TR 144. 3. Static acceleration of horizontal is 3.92 m/s2 at base of structure. 4. Please contact a Mitsubishi Electric representative regarding requirements for rated busbar currents of 2,000A. Select a product with a rating equal to or above the total of load current running on the vertical busbar. In addition, please consider future increases in unit capacity, additional system compatibility,and conditions for these installations. 5. Other control voltages including A.C. are also available.
9.80 3.23
JEM 1425
[kV, rms]
Ur
3.6
7.2
3.6
7.2
Rated Power Frequency Withstand Voltage [kV, rms]
Ud
16
22
10
20
Rated Lightning Impulse Withstand Voltage [kV, peak]
Up
45
60
40
60
Rated Voltage
Cubicle
Loss of Service Continuity Category
LSC1, LSC2A-PI, LSC2A-PM
Compartment
LSC2B-PI
Metalclad
LSC2B-PM
Rated Short-time Withstand Current [kA, rms]
Ik
25, 31.5, 40
25, 31.5, 40
Rated peak Withstand [kA, peak] Current
Ip
50Hz: 2.5×Ik, 60Hz: 2.6×Ik
50Hz: 2.5×Ik, 60Hz: 2.6×Ik
Internal Arc Classification (IAC)
3
IEC 62271-200
Optional type tests
Mandatory type tests, where applicable
4
3
VACUUM CIRCUIT BREAKER
Manufacturer
Mitsubishi Electric
Type designation
6/10-VPR-□□C
IEC 62271-100, JEC2300
630, 1250, 2000, 3150
25, 31.5, 40
Rated peak withstand current
[kA, rms] Ip
50 Hz: 2.5×Ik , 60 Hz: 2.6×Ik
Rated break time Rated short-circuit making current Rated control voltage
[A, rms] Ic
10, 25
[kA, rms] Isc
25, 31.5, 40
[cycles] [kA, peak]
W=800*2
W=800*2
Feeder panel-1
Feeder panel-2
63, 78.8, 100
[V DC] Ua
48, 100, 110, 125, 2202 O – 3 min – CO – 3 min – CO O – 0.3 sec – CO – 3 min – CO CO –15 sec – CO
[A] [sec] [A]
3.4
Tripping control current (at 110 V DC)
[A]
3.4
Auxiliary switch (contacts)
1970
1970
1.2 (peak 6 A) Approx. 6 (after closing)
Closing control current (at 110 V DC)
Weight
VT
3
Rated operating sequence Closing operation Motor current (at 110 V DC) Spring charging time
3
EVT
SAR
5a, 5b [kg] M
630, 1250 A: 140 2000 A: 160 3150 A: 210
1. Rated short-circuit breaking current 2 5 25 kA □□ 3 2 31.5 kA □□ 4 0 40 kA □□ 2. Other control voltages including A.C. are also available
CT
CT
VCB 31.5/40kA 1250A
VCB 20kA 630A
VCB 20kA 630A
2300
Rated short-circuit breaking current
VCB 20kA 2000A
VCB 31.5/40kA 1250A
CT
CT
W=800*3
50
Rated cable-charging breaking current
VCB 20kA 2000A
22 60
[kA, rms] Ik [sec] tk
CT
2300
50, 60
[A] Ir
Rated short-time withstand current
Rated duration of short-circuit
1970
50
[Hz] fr
Rated insulation level Short-duration power frequency withstand voltage, 1 min. [kV, rms] Ud Lightning impulse withstand voltage [kV, peak] Up
1970
3.6 7.2
2300
[kV, rms] Ur
50
Rated normal current (self-cooling)
Bus Tie/EVT panel
2300
Rated frequency
Incoming panel*1
1
Applied standard Rated voltage
SECTION VIEW OF “MS”
50
2
W=800
*1 When rated current is 3,150A or higher, the circuit breaker installation position changes to the lower part of the panel. *2 When rated current is 3,150A or higher, W=1,000. *3 According to the rated current, W=700 is available.
VPR-25C/32C/40C
5
6
4
VACUUM MAGNETIC CONTACTOR
5
SECTION VIEW OF “LSH” Structure Standard
Manufacturer
Multi-tier (3.3kV)
Mitsubishi Electric
Type designation
□□F○VN
Applied standard
IEC 60470
*For 6.6kV models, the maximum number of tiers is 3.
Multi-tier (6.6kV)
1
Rated operational current (self-cooling)
[Hz] fr
50, 60
[A] Ie
200, 400
Rated insulation level Short-duration power frequency withstand voltage, 1 min. [kV, rms] Ud Lightning impulse withstand voltage [kV, peak] Up Rated short-circuit breaking current Rated control voltage
CT
20 60
[kA, rms] Isc
40 (Power fuse)
[V AC/DC] Ua
100, 110, 200, 220
ZCT
Closing control current (at 100V DC)
[A]
4.8
Tripping control current (at 100V DC)
[A]
3.5 (Mechanical latch type)
Electrical hold type, Mechanical latch type
Weight
200 A: 90 400 A: 90 (for 3.3 kV) 100 (for 6.6 kV) 1. Power fuse rating 20 A 50 A 100 A 150 A 200 A 300 A 400 A Contactor rating 200 A 400 A
Unit
W700 Note: The unit is equipped with a ventilation duct when the vertical busbar rating of the panel is 700A.
Option
Operation system [kg] M
W700 Note: 4-tier units are equipped with a ventilation duct.
2a, 2b
Auxiliary switch (contacts)
ZCT
2300
Rated frequency
VMC
50
7.2
busbar
3.3kV, 3-tier
1300
VMC CT VT PF
6.6kV, 2-tier
busbar
0 2 □□ 0 5 □□ 1 0 □□ 1 5 □□ 2 0 □□ 3 0 □□ 4 0 □□
1500
VMC CT
VT PF
busbar
ZCT
2 ○ 4 ○
2300
[kV, rms]
PF
2300
Rated insulating voltage
VT PF
VT
2300
6.6
50
[kV, rms] Ur
VMC CT 210
Rated voltage
1500
1300 360
ZCT
Vacuum Magnetic Contactor
Power fuse CT CTD
(power supply with draw-out capacitor tripping device)
3.3kV, 4-tier (unit depth: 1,500)
1500 360
VT PF
210
VT
50
50
Combination unit (power fuse and vacuum contactor)
busbar
VMC CT
Control power supply switch ●Normal/Test
Vacuum contactor
ZCT
2300
Interlock lever
50
Notes:
7
*1 For 3-tier units, a ventilation duct is equipped when the vertical busbar rating of the panel is 700A . *2 When the busbar rating is 2,000A, the unit is equipped with a partition in the horizontal busbar compartment and ventilation ducts in upper and lower parts of the rear cover.
8
6
CONSTRUCTION 1. Operation for Vacuum Circuit Breaker
4. Single line diagram
VMC 2×CT
VMC 2×CT
2×VT
CR
VCB
ZCT
S INGLE L INE
3×LA
2×CT
VMC 2×CT
ZCT
100/5A
VMC 2×CT VCB
VCB
VCB
ZCT
ZCT 3×CT
3×CT
VMC 2×CT
CR
ZCT
ZCT
VMC 2×CT
CR
ZCT
ZCT
ZCT
E. BUS INCOMING
1. TEST/DISCONNECTED position.
2. Connect the plug so as to may move to the CONNECTED position.
5. Arrangement S IDESPACE 700
700
450
A N P
4. The plug cannot be pulled out at the CONNECTED position.
Grounding busbars installed in each panel can be easily connected onsite using bolts.
3. Control circuit The auxiliary relay, terminal block and other devices are mounted in the control room at the front of the panel. For connections between panels and across doors, this is designed to enable simple connections via connectors.
Connection point between panels
A
N P
A
800
A
N P
50
N P
700
S IDESPACE 700
A N P
B N P
B
N P
C N P
C N P
FL PANEL NO.
2. Grounding busbar
N P
A
800
B N P
FRONT V I EW
3. Move to the CONNECTED position.
800
1
2
3
4
5
6
LSH
BUS Transfer Panel
MS
MS
MS
LSH
6. System compatibility Connection with Mitsubishi Electric Type “MS” switchgear (1) When the position of horizontal busbar in the MS switchgear is same as that of LSH
(2) When the position of horizontal busbar in the MS switchgear is not same as that of LSH
Example: Top view
Connector for connections between panels M/C
Grounding busbar
50
M/C LSH
Bus transfer panel
LSH
700
450
700
● An
Grounding busbar connection
9
Control circuit connection between panels
auxiliary frame (W=50) is required to connect the MS switchgear with the LSH
● The
depth of the auxiliary frame must be same as that of the MS switchgear.
●A
bus transfer panel (W=450) is required.
● The
depth of the bus transfer panel must be same as that of the MS switchgear.
10
7
OUTLINE DIMENSION 2. LSH
1. MS
〈Standard Outline dimensions〉 〈標準外形寸法〉
〈Standard Outline dimensions〉 Indoor
Outdoor
2000
910/940
1340
500
250×1 line
2
2000
2
800 *3
1970
2300
980/1010
1470
600
250×1 line
1200/1250
2
800
1670
2000
970
1370
1000
325×1 line
2000
1200 3000/3150
3150
Indoor
4
Outdoor
600
1200
750
1350
950
900
1600
1200
600
1200
1200
750
1350
1700
700
2300
1040
1500
1100
325×1 line
2300
1200
1660
1000
Bus duct*5
2
800
1970
2300
1250
1710
1000
325×1 line duct*5
4
900
1600
2200
2
700
1300
1200
3
900
1500
1700
2300*4
2730
1
800
1970
2300
1200
1670
1100
Bus
1
1000
1970
2300
1360
1940
1500
Bus duct*5
3kV
2
*1 *2 *3 *4
800 *1
700
2300 *4
3
∼1250A
∼1250A
1659 *3
1500
2720
For side panel of both ends. 30mm should be added to each ends. Roof depth is 1,729mm. Roof depth is 1,929mm. Excluding a height of 50mm for the channel base.
Detailed view of foundation
50
31
Channel base*1 Foundation bolt: M12*1
1300(1500)
80
FL
Embedded frame*3
M16 bolt*3
Hole for control cable
Maintenance space (min.)(mm) Front: 1,800 Rear : 1,200 Side : 700
(Dimension of indoor type + 159) 192
275
200
192
Front
150
*4 Panel width
Front
150
50
400 283
Outdoor type
(Dimension of indoor type + 150)
Depth
150
225
100
Maintenance space (min.)(mm) Front: 1,800 Rear : 1200*1 Side : 700
30 52 Hole for power cable*2
*1 For insertion/removal of devices from the rear, dimensions shall be decided according to separate arrangements. *2 Size of lead-in hole may vary from these dimensions when the lead-in cable has more than three lines. *3 Available as an option. *4 This dimension is the panel width minus 200mm for the main circuit cable holes.
103
Hole for power cable
Outdoor type
80
Maintenance space (min.)(mm) Front: 1,800 Rear : 700 Side : 700
Front
Hole for power cable*2
Hole for control cable
275
M16 bolt*3
53
90
700
Channel base*3
50
*4 Panel width
Front FL
122
Cover
Door
Hole for control cable
Hole for control cable
105
103
50
400
Indoor type 100
Maintenance space (min.)(mm) Front: 1,800 Rear : 700*1 Side : 700
150
75 75
3
∼800A
J/S(=W)
Indoor
1970
83
75
Weight (kg) Outdoor
1970
133 90
75
1300
1459 *2
Indoor
800
Depth
11
Outdoor
800
Indoor type
Exterior door
Indoor
1
Detailed view of foundation
283
Outdoor
Height
2
Depth increases by 300mm when applying two cable lines. Depth increases by 30mm (optional) in the case of a rear door. For indoor panels only, a 700mm configuration is possible. For two-tier panels with cable lead-in from the top of the panel, the cable processing box (500×500mm [H×D]) may be mounted at the top of the panel. For rated current of 2,000A and above, bus duct connections are standard.
Interior door
Panel weight/Calorific value
Depth
2
6kV
*1 *2 *3 *4 *5
Width
50
2000
Outdoor
1200/1250
2000 VPR32/40C 31.5/40
1670
Indoor
800 *3
No. of tiers
Current
Voltage
560
1200
Outdoor
Panel dimensions
Max. lead-in cable size (XLPE mm2)×No. of lines
145
25
Indoor*2
J/S(=W)
145
VPR25C
Indoor Outdoor
Weight (kg)
Height
Depth*1
70
VCBs
Width
145
600
Panel busbar No. current installed (A)
105
Rated current (A)
35
Breaking current (kA)
35
Model
Panel weight/Calorific value (incl. circuit breakers)
500
Installed switchgear
Panel external dimensions (mm)
Panel dimensions (mm)
30 Hole for power cable
52
Embedded frame*1 Foundation bolt: M12*1
*1 Available as an option.
12
8
9
MP Relay 9
8
7
1. STANDARD ACCESSORIES
6
10
1 2 160
ACCESSORIES Draw-out handle for withdrawable equipment
11
Manual charging handle for VCB closing spring
12
Test Terminals test plug set for secondary circuit of VT & CT
13
Lifter with bucket for withdrawable equipment
3
14
4
15
5
16 17
250 Lifter 1 Liquid-crystal display (LCD)
When there is a failure with the liquid crystal or lamps, it is possible to replace the LCD only.
2 Circuit breaker On lamp (red or green) 3 Circuit breaker Off lamp (green or red) 4 Failure display lamp 5 6 7 8
Minor failure: Orange; Serious failure: Red System emergency lamp (red) Select switch (next, up) Mode switch (right) Mode switch (left)
9 Select switch (back, down) 10 11 12 13 14 15 16 17 18 19
Circuit breaker On switch Circuit breaker Off switch Remote switch Local switch Reset switch Test switch Set switch Circuit breaker forced off switch Input/Output 16P connector (connector No. CN2) Input/Output 20P connector (connector No. CN3)
Function Protection Measurement Control CB monitoring
20
21
22
23
Connector for transmission, transducer communications CC-Link: 5P connector; Transducer: 18P connector Optional unit An optional unit for transducer or CC-Link transmission can be installed.Empty case when no optional unit is installed. Power supply part When there is a power-supply failure, it is possible to replace the power-supply part only. Separated terminal block (power supply, VT, CT, ZCT) The terminal block can be removed by loosening screws at both ends. However, with the terminal block removed, there is no short-circuit function of the CT input part.
Description '50, 51, 67, 51G(using ZM-type ZCT or 3 x CT residual circuit), 27, 59, 64 46, 49(Motor Protection only)
Bucket
Draw-out handle
Test plug set
Lifter with bucket
Standard accessories
2. OPTIONAL ACCESSORIES
3. EARTHING DEVICES
Control circuit extension cable for withdrawn
Optional earthing devices are available for
A, DA, DAmax, V, W, DW, DWmax, Wh, var, varh, Hz, cosΦ, A0, V0, V0max
VCB / VMC ON / OFF testing
safety during cable and busbar maintenance
ON/OFF of circuit breaker, REMOTE/LOCAL control mode selection, enable trip output contact, enable CB closing during a fault, setting of general purpose inputs and outputs, CB-ON delay timer
Earthing switch operating handle
and/or inspection. Earthing truck for switchgear
Circuit breaker operation monitoring ON/OFF output of circuit breaker, TRIP output monitoring (using sequential logic), CPU condition, memory, AD converter, internal power supply, ratio check of analogue circuit
An earthing truck with fault-making
History
Time-to-trip and fault voltage/current of last 5 faults (time-to-trip is the elapsed time from detection of the fault to the protective relay operation)
mechanism as the circuit breaker.
CC-Link transmission (option)
Transmission of various measurements, protection data, ON/OFF status of circuit breaker, and reception of remote control signals
CDL transmission (option)
Transmission of various measurements, protection data, ON/OFF status of circuit breaker, and reception of remote control signals
Fail-safe and self-diagnostics
Transducer outputs (option)
capability which has the same operating
4~20mA DC output of various measurements (Wh and varh are pulse outputs)
Control circuit extension cable
Standard equipping of MP Series digital multi-relays realizing even higher reliability For the protective control device, MP Series digital multi-relays equipped with protection/control functions are adopted. Failsafe/Accident diagnosis functions are equipped, realizing an even high level of reliability. Furthermore, adding an optional transducer/transmission function and overall computerization of the power distribution equipment simplifies the interface with the central monitoring and control equipment.
High reliability ●The MP Series digital multi-relay centralizes measurements, protection and control functions into one unit, reducing wiring inside the panel by 50%.
High functionality ●As a result of adopting the MP Series digital multi-relay and wide-range CT, it is not necessary to replace the CT in response to load changes. In addition, through adopting a composite CT*1 (optional), it is possible to achieve simplification of the ZCT high-voltage cable processing.
Optional accessory
Earthing truck ( Upper Terminal*1 ) *1 Lower terminal is also available.
●MP Series digital multi-relays have five kinds of overcurrent protection properties equipped as standard, and it is not necessary to replace the relay. *1 Composite CT: A molded multi-type CT combining the wide-range CT and ZCT.
13
14