MEDIUM VOLTAGE SWITCHGEAR AND CONTROLGEAR MODEL

MS

Safety Precautions Please read the instruction manual before using the device.

G-199-3-C9173-A HQ1303 Printed in Japan (MDOC)

New Publication, effective Mar. 2013. Specifications are subject to change without notice.

Since the 1950s, Mitsubishi Electric has been providing power distribution equipment and systems matched to the needs of the era. Now, inheriting the technologies and reliability forged from this manufacturing record of over half a century, the MS Series switchgear realizes the next evolutionary step forward. Page

STANDARD & RATINGS

3

MP Series multi-relay ● Combining the MP23 and wide-range CT makes it easy to cope with the changes in load capacity by using only the CT ratio setting changes of the multi-relay (CT setting ranges are 60~600A and 200~2,000A). ● Display lights protrude from the panels to enhance visibility when viewing panels from side-on.

Easy maintenance

Consideration for easy maintenance ● Through vertical location of the main busbar, maintenance from the back of panels is simplified, reducing maintenance work. ● The number of bolts for busbar connection has been reduced. This contributes to easier maintenance to check the bolt condition.

Intelligent

VACUUM CIRCUIT BREAKER

SECTION VIEW OF “MS”

VACUUM MAGNETIC CONTACTOR

VPR-C Series VCBs ● Comply with Restriction of Hazardous Substances (RoHS). ● Long-life grease and non-lubricated bearing realize reduced maintenance.

F E ATURES HIGH RELIABILITY

6 7

SECTION VIEW OF “LSH”

8

CONSTRUCTION

9

Innovation

Ecoconscious

5

1. Operation for Vacuum Circuit Breaker 2. Grounding busbar 3. Control circuit 4. Single line diagram 5. Arrangement 6. System compatibility

OUTLINE DIMENSION

11

1. MS 2. LSH

MP Relay

13

9

14

ACCESSORIES

MS is designed with the benefit of Mitsubishi’s vast medium voltage panels production experience of hundreds of thousands of panels over the last almost 60 years. 3D-Thermo Fluid Analysis of the switchgear structure has led to a heat-resistant design in which circuit breakers up to 3150 A are self-cooled (i.e. cooling fans not required). The reduced number of parts decreases the chance of failure.

SAFETY Partitions between compartments and an automatic shutter system (for withdrawable equipment primary junctions) completely isolate live parts.

EASY INSTALLATION Installation and testing duration are considerably reduced as the panel is tested and adjusted in the factory and then delivered as a complete unit.

1

2

1

STANDARD & RATINGS Various construction grades Ratings

JEM

Type designation

MS

Applied standard

IEC 62271-200 , JEM1425

Rated voltage Rated frequency

3.6 7.2

[Hz] fr

50, 60

Rated short-time withstand current , symmetrical [kA, rms] Ik Rated peak withstand current Rated duration of short-circuit Control voltage

[kA, peak] Ip [sec] tk [V,AC/DC]

Loss of service continuity category

LSC2B-PM

PW/PWG

CW

LSC2B-PI

LSC1 LSC2A-PI LSC2A-PM

Circuit breaker compartment Cable compartment

Partition plate

1

[kV, rms] Ur

Bushing Shutter

Busbar compartment

2XCT VCB

16 22 45 60

10 16 30 45

[A, rms] Ir 630, 1250, 2000, 3150

IEC

IEC 62271-200 , JEM1225

1

Rated insulation level Short-duration power frequency withstand voltage, 1 min. [kV, rms] Ud Lightning impulse withstand voltage [kV, peak] Up Rated normal main busbar current

LSH

MW/MWG

R S

Sectional View

T VCB

Circuit breaker compartment

40

50 Hz: 2.5×Ik , 60 Hz: 2.6×Ik 0.5, 1

0.5

DC48, 100, 110, 125, 220

AC100/110, 200/220V

5

IEC:Max. LSC2B-PM

IEC:Max. LSC2A-PM

JEM:Metal-Clad

JEM:Class M5

Structure

R S

Busbar

T

2XCT

VCB

Partition plate

Busbar compartment

VCB

Busbar

400, 630, 800, 1250, (2000) 4

25, 31.5, 40

2XCT

(Example of feeder panel)

●All compartments for busbars, circuit breakers and cables are separated by partition plates made of metal.

●All compartments for busbars, circuit breakers and cables are separated by partition plates made of metal or insulation materials.

●Bushing for the main circuit passage between compartments (for the MWG Series, the main circuit has insulation coating).

●Bushing used for the main circuit passage between compartments (for the PWG Series, the main circuit has insulation coating).

2XCT

(Example of feeder panel) ●Small number of compartments ●No partition plates ●Low protective class even with partition plates

●Enclosure: IP2X (Ø12mm) or less

Location

Indoor, Outdoor

Degree of protection

IP codes

Indoor:max. IP4X, Outdoor:max. IP33

Ambient temperature

[℃]

-5 ~ 40

Altitude a.s.l.

[m]

max.1000

Humidity R.H. Water vapour pressure

[%] [kPa]

Earthquake protection2 Horizontal seismic withstand3 Vertical seismic withstand

[m/s ] [m/s2]

max. 95 average 2.2

Interface between Enclosure and Circuit Breaker

●Partition: IP2X (Ø12mm) or less (excluding CW, LSC1, LSC2A-PI, LSC2A-PM) ●Protective plates between control room and main circuit: IP1X (Ø50mm)

●Main circuit: Automatic connection

●Main circuit: Automatic connection

●Main circuit: Automatic connection

●Control circuit: Manual connection

●Auxiliary circuit: Manual connection

●Control circuit: Manual connection

●Automatic shutters for touch protection are applied between main contacts of circuit breaker and enclosure.

●Automatic shutters for touch protection are applied between main contacts of circuit breaker and enclosure.

Comparison table between JEM 1425 and IEC 62271-200 2

1. Internal Arc Classification will not be applicable. 2. General use, class B on the upper floor or roof of building according to JEM-TR 144. 3. Static acceleration of horizontal is 3.92 m/s2 at base of structure. 4. Please contact a Mitsubishi Electric representative regarding requirements for rated busbar currents of 2,000A. Select a product with a rating equal to or above the total of load current running on the vertical busbar. In addition, please consider future increases in unit capacity, additional system compatibility,and conditions for these installations. 5. Other control voltages including A.C. are also available.

9.80 3.23

JEM 1425

[kV, rms]

Ur

3.6

7.2

3.6

7.2

Rated Power Frequency Withstand Voltage [kV, rms]

Ud

16

22

10

20

Rated Lightning Impulse Withstand Voltage [kV, peak]

Up

45

60

40

60

Rated Voltage

Cubicle

Loss of Service Continuity Category

LSC1, LSC2A-PI, LSC2A-PM

Compartment

LSC2B-PI

Metalclad

LSC2B-PM

Rated Short-time Withstand Current [kA, rms]

Ik

25, 31.5, 40

25, 31.5, 40

Rated peak Withstand [kA, peak] Current

Ip

50Hz: 2.5×Ik, 60Hz: 2.6×Ik

50Hz: 2.5×Ik, 60Hz: 2.6×Ik

Internal Arc Classification (IAC)

3

IEC 62271-200

Optional type tests

Mandatory type tests, where applicable

4

3

VACUUM CIRCUIT BREAKER

Manufacturer

Mitsubishi Electric

Type designation

6/10-VPR-□□C

IEC 62271-100, JEC2300

630, 1250, 2000, 3150

25, 31.5, 40

Rated peak withstand current

[kA, rms] Ip

50 Hz: 2.5×Ik , 60 Hz: 2.6×Ik

Rated break time Rated short-circuit making current Rated control voltage

[A, rms] Ic

10, 25

[kA, rms] Isc

25, 31.5, 40

[cycles] [kA, peak]

W=800*2

W=800*2

Feeder panel-1

Feeder panel-2

63, 78.8, 100

[V DC] Ua

48, 100, 110, 125, 2202 O – 3 min – CO – 3 min – CO O – 0.3 sec – CO – 3 min – CO CO –15 sec – CO

[A] [sec] [A]

3.4

Tripping control current (at 110 V DC)

[A]

3.4

Auxiliary switch (contacts)

1970

1970

1.2 (peak 6 A) Approx. 6 (after closing)

Closing control current (at 110 V DC)

Weight

VT

3

Rated operating sequence Closing operation Motor current (at 110 V DC) Spring charging time

3

EVT

SAR

5a, 5b [kg] M

630, 1250 A: 140 2000 A: 160 3150 A: 210

1. Rated short-circuit breaking current 2 5 25 kA □□ 3 2 31.5 kA □□ 4 0 40 kA □□ 2. Other control voltages including A.C. are also available

CT

CT

VCB 31.5/40kA 1250A

VCB 20kA 630A

VCB 20kA 630A

2300

Rated short-circuit breaking current

VCB 20kA 2000A

VCB 31.5/40kA 1250A

CT

CT

W=800*3

50

Rated cable-charging breaking current

VCB 20kA 2000A

22 60

[kA, rms] Ik [sec] tk

CT

2300

50, 60

[A] Ir

Rated short-time withstand current

Rated duration of short-circuit

1970

50

[Hz] fr

Rated insulation level Short-duration power frequency withstand voltage, 1 min. [kV, rms] Ud Lightning impulse withstand voltage [kV, peak] Up

1970

3.6 7.2

2300

[kV, rms] Ur

50

Rated normal current (self-cooling)

Bus Tie/EVT panel

2300

Rated frequency

Incoming panel*1

1

Applied standard Rated voltage

SECTION VIEW OF “MS”

50

2

W=800

*1 When rated current is 3,150A or higher, the circuit breaker installation position changes to the lower part of the panel. *2 When rated current is 3,150A or higher, W=1,000. *3 According to the rated current, W=700 is available.

VPR-25C/32C/40C

5

6

4

VACUUM MAGNETIC CONTACTOR

5

SECTION VIEW OF “LSH” Structure Standard

Manufacturer

Multi-tier (3.3kV)

Mitsubishi Electric

Type designation

□□F○VN

Applied standard

IEC 60470

*For 6.6kV models, the maximum number of tiers is 3.

Multi-tier (6.6kV)

1

Rated operational current (self-cooling)

[Hz] fr

50, 60

[A] Ie

200, 400

Rated insulation level Short-duration power frequency withstand voltage, 1 min. [kV, rms] Ud Lightning impulse withstand voltage [kV, peak] Up Rated short-circuit breaking current Rated control voltage

CT

20 60

[kA, rms] Isc

40 (Power fuse)

[V AC/DC] Ua

100, 110, 200, 220

ZCT

Closing control current (at 100V DC)

[A]

4.8

Tripping control current (at 100V DC)

[A]

3.5 (Mechanical latch type)

Electrical hold type, Mechanical latch type

Weight

200 A: 90 400 A: 90 (for 3.3 kV) 100 (for 6.6 kV) 1. Power fuse rating 20 A 50 A 100 A 150 A 200 A 300 A 400 A Contactor rating 200 A 400 A

Unit

W700 Note: The unit is equipped with a ventilation duct when the vertical busbar rating of the panel is 700A.

Option

Operation system [kg] M

W700 Note: 4-tier units are equipped with a ventilation duct.

2a, 2b

Auxiliary switch (contacts)

ZCT

2300

Rated frequency

VMC

50

7.2

busbar

3.3kV, 3-tier

1300

VMC CT VT PF

6.6kV, 2-tier

busbar

0 2 □□ 0 5 □□ 1 0 □□ 1 5 □□ 2 0 □□ 3 0 □□ 4 0 □□

1500

VMC CT

VT PF

busbar

ZCT

2 ○ 4 ○

2300

[kV, rms]

PF

2300

Rated insulating voltage

VT PF

VT

2300

6.6

50

[kV, rms] Ur

VMC CT 210

Rated voltage

1500

1300 360

ZCT

Vacuum Magnetic Contactor

Power fuse CT CTD

(power supply with draw-out capacitor tripping device)

3.3kV, 4-tier (unit depth: 1,500)

1500 360

VT PF

210

VT

50

50

Combination unit (power fuse and vacuum contactor)

busbar

VMC CT

Control power supply switch ●Normal/Test

Vacuum contactor

ZCT

2300

Interlock lever

50

Notes:

7

*1 For 3-tier units, a ventilation duct is equipped when the vertical busbar rating of the panel is 700A . *2 When the busbar rating is 2,000A, the unit is equipped with a partition in the horizontal busbar compartment and ventilation ducts in upper and lower parts of the rear cover.

8

6

CONSTRUCTION 1. Operation for Vacuum Circuit Breaker

4. Single line diagram

VMC 2×CT

VMC 2×CT

2×VT

CR

VCB

ZCT

S INGLE L INE

3×LA

2×CT

VMC 2×CT

ZCT

100/5A

VMC 2×CT VCB

VCB

VCB

ZCT

ZCT 3×CT

3×CT

VMC 2×CT

CR

ZCT

ZCT

VMC 2×CT

CR

ZCT

ZCT

ZCT

E. BUS INCOMING

1. TEST/DISCONNECTED position.

2. Connect the plug so as to may move to the CONNECTED position.

5. Arrangement S IDESPACE 700

700

450

A N P

4. The plug cannot be pulled out at the CONNECTED position.

Grounding busbars installed in each panel can be easily connected onsite using bolts.

3. Control circuit The auxiliary relay, terminal block and other devices are mounted in the control room at the front of the panel. For connections between panels and across doors, this is designed to enable simple connections via connectors.

Connection point between panels



N P



800



N P

50

N P

700

S IDESPACE 700

A N P

B N P



N P

C N P

C N P

FL PANEL NO.

2. Grounding busbar

N P



800

B N P

FRONT V I EW

3. Move to the CONNECTED position.

800













LSH

BUS Transfer Panel

MS

MS

MS

LSH

6. System compatibility Connection with Mitsubishi Electric Type “MS” switchgear (1) When the position of horizontal busbar in the MS switchgear is same as that of LSH

(2) When the position of horizontal busbar in the MS switchgear is not same as that of LSH

Example: Top view

Connector for connections between panels M/C

Grounding busbar

50

M/C LSH

Bus transfer panel

LSH

700

450

700

● An

Grounding busbar connection

9

Control circuit connection between panels

auxiliary frame (W=50) is required to connect the MS switchgear with the LSH

● The

depth of the auxiliary frame must be same as that of the MS switchgear.

●A

bus transfer panel (W=450) is required.

● The

depth of the bus transfer panel must be same as that of the MS switchgear.

10

7

OUTLINE DIMENSION 2. LSH

1. MS

〈Standard Outline dimensions〉 〈標準外形寸法〉

〈Standard Outline dimensions〉 Indoor

Outdoor

2000

910/940

1340

500

250×1 line

2

2000

2

800 *3

1970

2300

980/1010

1470

600

250×1 line

1200/1250

2

800

1670

2000

970

1370

1000

325×1 line

2000

1200 3000/3150

3150

Indoor

4

Outdoor

600

1200

750

1350

950

900

1600

1200

600

1200

1200

750

1350

1700

700

2300

1040

1500

1100

325×1 line

2300

1200

1660

1000

Bus duct*5

2

800

1970

2300

1250

1710

1000

325×1 line duct*5

4

900

1600

2200

2

700

1300

1200

3

900

1500

1700

2300*4

2730

1

800

1970

2300

1200

1670

1100

Bus

1

1000

1970

2300

1360

1940

1500

Bus duct*5

3kV

2

*1 *2 *3 *4

800 *1

700

2300 *4

3

∼1250A

∼1250A

1659 *3

1500

2720

For side panel of both ends. 30mm should be added to each ends. Roof depth is 1,729mm. Roof depth is 1,929mm. Excluding a height of 50mm for the channel base.

Detailed view of foundation

50

31

Channel base*1 Foundation bolt: M12*1

1300(1500)

80

FL

Embedded frame*3

M16 bolt*3

Hole for control cable

Maintenance space (min.)(mm) Front: 1,800 Rear : 1,200 Side : 700

(Dimension of indoor type + 159) 192

275

200

192

Front

150

*4 Panel width

Front

150

50

400 283

Outdoor type

(Dimension of indoor type + 150)

Depth

150

225

100

Maintenance space (min.)(mm) Front: 1,800 Rear : 1200*1 Side : 700

30 52 Hole for power cable*2

*1 For insertion/removal of devices from the rear, dimensions shall be decided according to separate arrangements. *2 Size of lead-in hole may vary from these dimensions when the lead-in cable has more than three lines. *3 Available as an option. *4 This dimension is the panel width minus 200mm for the main circuit cable holes.

103

Hole for power cable

Outdoor type

80

Maintenance space (min.)(mm) Front: 1,800 Rear : 700 Side : 700

Front

Hole for power cable*2

Hole for control cable

275

M16 bolt*3

53

90

700

Channel base*3

50

*4 Panel width

Front FL

122

Cover

Door

Hole for control cable

Hole for control cable

105

103

50

400

Indoor type 100

Maintenance space (min.)(mm) Front: 1,800 Rear : 700*1 Side : 700

150

75 75

3

∼800A

J/S(=W)

Indoor

1970

83

75

Weight (kg) Outdoor

1970

133 90

75

1300

1459 *2

Indoor

800

Depth

11

Outdoor

800

Indoor type

Exterior door

Indoor

1

Detailed view of foundation

283

Outdoor

Height

2

Depth increases by 300mm when applying two cable lines. Depth increases by 30mm (optional) in the case of a rear door. For indoor panels only, a 700mm configuration is possible. For two-tier panels with cable lead-in from the top of the panel, the cable processing box (500×500mm [H×D]) may be mounted at the top of the panel. For rated current of 2,000A and above, bus duct connections are standard.

Interior door

Panel weight/Calorific value

Depth

2

6kV

*1 *2 *3 *4 *5

Width

50

2000

Outdoor

1200/1250

2000 VPR32/40C 31.5/40

1670

Indoor

800 *3

No. of tiers

Current

Voltage

560

1200

Outdoor

Panel dimensions

Max. lead-in cable size (XLPE mm2)×No. of lines

145

25

Indoor*2

J/S(=W)

145

VPR25C

Indoor Outdoor

Weight (kg)

Height

Depth*1

70

VCBs

Width

145

600

Panel busbar No. current installed (A)

105

Rated current (A)

35

Breaking current (kA)

35

Model

Panel weight/Calorific value (incl. circuit breakers)

500

Installed switchgear

Panel external dimensions (mm)

Panel dimensions (mm)

30 Hole for power cable

52

Embedded frame*1 Foundation bolt: M12*1

*1 Available as an option.

12

8

9

MP Relay 9

8

7

1. STANDARD ACCESSORIES

6

10

1 2 160

ACCESSORIES Draw-out handle for withdrawable equipment

11

Manual charging handle for VCB closing spring

12

Test Terminals test plug set for secondary circuit of VT & CT

13

Lifter with bucket for withdrawable equipment

3

14

4

15

5

16 17

250 Lifter 1 Liquid-crystal display (LCD)

When there is a failure with the liquid crystal or lamps, it is possible to replace the LCD only.

2 Circuit breaker On lamp (red or green) 3 Circuit breaker Off lamp (green or red) 4 Failure display lamp 5 6 7 8

Minor failure: Orange; Serious failure: Red System emergency lamp (red) Select switch (next, up) Mode switch (right) Mode switch (left)

9 Select switch (back, down) 10 11 12 13 14 15 16 17 18 19

Circuit breaker On switch Circuit breaker Off switch Remote switch Local switch Reset switch Test switch Set switch Circuit breaker forced off switch Input/Output 16P connector (connector No. CN2) Input/Output 20P connector (connector No. CN3)

Function Protection Measurement Control CB monitoring

20

21

22

23

Connector for transmission, transducer communications CC-Link: 5P connector; Transducer: 18P connector Optional unit An optional unit for transducer or CC-Link transmission can be installed.Empty case when no optional unit is installed. Power supply part When there is a power-supply failure, it is possible to replace the power-supply part only. Separated terminal block (power supply, VT, CT, ZCT) The terminal block can be removed by loosening screws at both ends. However, with the terminal block removed, there is no short-circuit function of the CT input part.

Description '50, 51, 67, 51G(using ZM-type ZCT or 3 x CT residual circuit), 27, 59, 64 46, 49(Motor Protection only)

Bucket

Draw-out handle

Test plug set

Lifter with bucket

Standard accessories

2. OPTIONAL ACCESSORIES

3. EARTHING DEVICES

Control circuit extension cable for withdrawn

Optional earthing devices are available for

A, DA, DAmax, V, W, DW, DWmax, Wh, var, varh, Hz, cosΦ, A0, V0, V0max

VCB / VMC ON / OFF testing

safety during cable and busbar maintenance

ON/OFF of circuit breaker, REMOTE/LOCAL control mode selection, enable trip output contact, enable CB closing during a fault, setting of general purpose inputs and outputs, CB-ON delay timer

Earthing switch operating handle

and/or inspection. Earthing truck for switchgear

Circuit breaker operation monitoring ON/OFF output of circuit breaker, TRIP output monitoring (using sequential logic), CPU condition, memory, AD converter, internal power supply, ratio check of analogue circuit

An earthing truck with fault-making

History

Time-to-trip and fault voltage/current of last 5 faults (time-to-trip is the elapsed time from detection of the fault to the protective relay operation)

mechanism as the circuit breaker.

CC-Link transmission (option)

Transmission of various measurements, protection data, ON/OFF status of circuit breaker, and reception of remote control signals

CDL transmission (option)

Transmission of various measurements, protection data, ON/OFF status of circuit breaker, and reception of remote control signals

Fail-safe and self-diagnostics

Transducer outputs (option)

capability which has the same operating

4~20mA DC output of various measurements (Wh and varh are pulse outputs)

Control circuit extension cable

Standard equipping of MP Series digital multi-relays realizing even higher reliability For the protective control device, MP Series digital multi-relays equipped with protection/control functions are adopted. Failsafe/Accident diagnosis functions are equipped, realizing an even high level of reliability. Furthermore, adding an optional transducer/transmission function and overall computerization of the power distribution equipment simplifies the interface with the central monitoring and control equipment.

High reliability ●The MP Series digital multi-relay centralizes measurements, protection and control functions into one unit, reducing wiring inside the panel by 50%.

High functionality ●As a result of adopting the MP Series digital multi-relay and wide-range CT, it is not necessary to replace the CT in response to load changes. In addition, through adopting a composite CT*1 (optional), it is possible to achieve simplification of the ZCT high-voltage cable processing.

Optional accessory

Earthing truck ( Upper Terminal*1 ) *1 Lower terminal is also available.

●MP Series digital multi-relays have five kinds of overcurrent protection properties equipped as standard, and it is not necessary to replace the relay. *1 Composite CT: A molded multi-type CT combining the wide-range CT and ZCT.