INSTALLATION INSTRUCTIONS

TWO STAGE HEAT PUMPS LOW VOLTAGE CONTROL CIRCUIT WIRING Models: T**S

T**S*D

Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com

C**H

Manual : 2100-554G Supersedes: 2100-554F Date: 4-18-16

Page

1 of 14

CONTENTS Installation Low Voltage Wiring................................................ 3 Figures

Tables

Figure 1 Basic HP w/Opt. Elec. Heat..................... 5

Table 1 Diagram to Use w/Unit and Vents............. 3

Figure 2 HP w/Opt. MFAD, CRV & ERV Vent. Pkg. ... w/Programmable T-Stat........................... 6

Table 2

Operating Voltage Range......................... 3

Table 3

Wall Thermostat..................................... 3

Figure 3 HP w/Opt. Economizer............................ 7

Table 4

Humidity Controls.................................. 4

Figure 4 HP w/Dehumidification Sequence & No Vent Pkg. Using T-Stat Comb................... 8

Table 5

CO2 Controller........................................ 4

Table 6

Thermostat Wire Size.............................. 4

Figure 5 HP w/Dehumidification Sequence & Opt. MFAD, CRV, & ERV Vent Pkg. Using Elec. T-Stat w/Combination Temp. & Humidity Control.................................................. 9 Figure 6 Dehum. HP with Opt. Economizer.......... 10 Figure 7 2 Stage HP w/Opt. Elec. Heat w/ ECONWM* Style Economizer................. 11 Figure 8 2 Stage HP w/Dehum. & Opt. Elec. Heat w/ECONWM* Style Economizer............. 12 Figure 9 2 Stage HP w/CHCRV-5 or CRVMWH-3 Vent Opt Pkg. w/Prog. T-Stat w/Opt. On/Off CO2 Controller........................... 13 Figure 10 2 Stage HP w/CHCRV-5 or CRVMWH-3 Vent Opt. Pkg. w/Prog. T-Stat w/Opt. Modulating CO2 Controller..................... 14

Manual 2100-554G Page 2 of 14

INSTALLATION TABLE 1 Diagram to Use With Unit and Vents Model Series

No Vents

ERV MFAD CRV

CRVMWH-3 CHCRV-5

Economizer “E” Vent Option

T, W, S ECONWMT

Vent Code

X

R, M, V, P

C

E

T, W, S

T**S / C**H

1

2

9 & 10

3

7

T**S*D

4

5

9 & 10

6

8

LOW VOLTAGE WIRING 230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240V and 208V taps are:

TABLE 2 Operating Voltage Range Tap

Range

240V

253 - 216

208V

220 - 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

“L” terminal is compressor lockout output. This terminal is activated on a high or low pressure trip by the electronic heat pump control. This is a 24 VAC output. “W2” terminal is second stage heat (if equipped). “O1” terminal is the ventilation input. This terminal energizes any factory installed ventilation option. “E” terminal is the emergency heat input. This terminal energizes the emergency heat relay. “W3” terminal is the dehumidification input. This terminal energizes compressor, blower and threeway valve. This applies only to models equipped for dehumidification sequence. LOW VOLTAGE CONNECTIONS FOR DDC CONTROL

Fan Only

Energize G

Cooling Mode 1 Stage

Energize Y, G

An 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Table 2.

Cooling Mode 2nd Stage

Energize Y, Y1, G

Heat Pump Heating 1 Stage

Energize Y, G, B

Heat Pump Heating 2 Stage

Energize Y, Y1, B, G

Low Voltage Connection These units use a grounded 24-volt AC low voltage circuit.

3 Stage Heating w/Heat Pump (if employed)

Energize G, W2, Y, B, Y1

The “R” terminal is the hot terminal and the “C” terminal is grounded.

Ventilation

Energize G, O1

Emergency Heat

Energize B, W2, E, G

Dehumidification

Energize W3

st

“G” terminal is the fan input.

st

nd

rd

“Y” terminal is the compressor input Stage 1.

TABLE 3 Wall Thermostat

“B” terminal is the reversing valve input. The reversing valve must be energized for heating mode. “R” terminal is the 24 VAC hot. “RT” terminal is the 24 VAC hot from transformer (used with “R” for fire/smoke shutdown). “C” terminal is the 24 VAC grounded. “Y1” terminal is the compressor input Stage 2.

Part Number

8403-060 (1120-445)

Predominate Features 3 stage Cool; 3 stage Heat Programmable/Non-Programmable Electronic HP or Conventional Auto or Manual changeover Dehumidification Output

Manual 2100-554G Page 3 of 14

TABLE 4 Humidity Controls Part Number

Predominate Features

8403-038 (H600A1014)

SPDT switching, pilot duty 50VA @ 24V Humidity range 20-80% RH

8403-047 Electronic dehumidistat SPST closes-on-rise (H200-10-21-10) Humidity range 10-90% with adjustable stops

TABLE 5 CO2 controller Part Number

Predominate Features

8403-067

Normally Open SPST relay closes-on-rise 24V dual wave length sensor. Default setting 950ppm, adjustable to 0-2000ppm Default off setting 1000ppm, adjustable to 0-200 ppm can be calibrated

TABLE 6 Thermostat Wire Size Transformer VA

55

Manual 2100-554G Page 4 of 14

FLA

2.3

Wire Gauge 20 18 16 14 12

gauge gauge gauge gauge gauge

Maximum Distance In Feet 45 60 100 160 250

FIGURE 1 Low Voltage Wiring Diagram: Heat Pump With Optional Electric Heat No Economizer or Ventilation Packages

Thermostat Bard part #8403-060

C

G

R

24V Low Voltage Terminal Block

C

G

R

MIS-2965 A

RT

Y2

Y1 O/B

Y1

Y

B

W2

W1 W2

Y O/D W1/E

W3

E

L

L

A

DH

O1

Factory Installed Jumper

1

1

Factory installed jumper (on applicable models). Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

Manual 2100-554G Page 5 of 14

Unit

FIGURE 2 Low Voltage Wiring Diagram: Heat Pump With Optional Figure 2 MFAD, CRV & ERV Ventilation Packaging With Programmable Thermostat

Low Voltage Wiring Diagram Heat Pump with Optional MFAD, CRV, and ERV Ventilation Packaging with Programmable Thermostat (Recommended) Thermostat Bard part #8403-060

C

G

R

Y1

Y2 W1/E W2 O/B

1

L

Y O/D

2

3

4

5

A

Electronic Programmable Optional CO2 Controller Bard part #8403-067

6

2 24V Low Voltage Terminal Block

C

G

R

RT 4

3

Black

Orange

Y

Y1

E

B

W1 W3 DH

L

O1

Unit

1

Red

Black

W2

CRV ERV MFAD

Brown/White Ventilation Packages

Red MIS-2966 D

1 Factory Jumper Installed 2 Do not connect "A" from tstat #8403-060 if optional CO2 controller is used.

Connect orange wire to "G" only if 3 optional CO controller is used. 2

Factory installed jumper (on applicable models). 4 Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

Manual 2100-554G Page 6 of 14

FIGURE 3 Low Voltage Wiring Diagram: Heat Pump With Optional Economizer

Low Voltage Wiring Diagram

Thermostat Bard part #8403-060

C

R

24V Low Voltage Terminal Block

C

R

O/B

RT

B

W1

W1/E

W2

L

G

W3

E

W2

L

G

Y

A

Y2

Y1 YO/D

Y1 DH O1 W3

Pink

F

Yellow

E

Orange

1

Black

4

Blue

Black

Y2

Y1

Unit

Purple

2

3

MIS-2967 B

Economizer Wiring Harness 1 Factory Jumper Installed. Must be configured for economizer with YO/D output to 2 be active as first stage cooling. 3 These wires are used in special control applications only. Factory installed jumper (on applicable models). 4 Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

Manual 2100-554G Page 7 of 14

FIGURE 4 Low Voltage Wiring Diagram: Heat Pump With Dehumidification Sequence and No Ventilation Package Using Thermostat #8403-060 Combination Temperature & Humidity Controller

Low Voltage Wiring Diagram Thermostat Bard part #8403-060

C

G

R

C

G

R

Y2

Y1 W1/E

Y1

Y

1

W2 YO/D O/B

L

A

L

O1

MIS-2968 B

24V Low Voltage Terminal Block

RT

E

W1 W2 W3

2

Manual 2100-554G Page 8 of 14

B

DH

Factory Installed Jumper

1

Must be configured for "no economizer" to make YO/D output active for humidity control.

2

Factory installed jumper (on applicable models). Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

Unit

FIGURE 5 Low Voltage Wiring Diagram: Heat Pump With Dehumidification Sequence Figure 8 & Optional MFAD, CRV & ERV Ventilation Packaging Using Electronic Thermostat With Combination Temperature & Humidity Control Pump with Dehumidification Sequence and Optional MFAD, CRV, and ERV Ventilation With Optional CO2 Controller

Heat Packaging using Electronic Thermostat with Combination Temperature and Humidity Control with Optional CO2 Controller 2 Thermostat Bard part #8403-060

Low Voltage Wiring Diagram C

G

Y2

R

Y1 O/B W2 YO/D

A W1/E

L

3 1

24V Low Voltage Terminal Block

C

G

R

RT

4 3

Black Black

Orange

Y1

Y

B

2

W2 W3 W1

3

4

DH

5

6

Optional CO2 Controller Bard part #8403-067

O1

E

L

Unit

1

Red CRV ERV

Brown/White Ventilation Packages MFAD Red

1 Factory Jumper Installed Must be configured for "no economizer" to make YO/D 2 output active for humidity control. Do not connect "A" from thermostat if optional CO 3 controller is used. Connect orange wire to "G" only2 when optinal CO 2 controller is used. Factory installed jumper (on applicable models). 4 Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

MIS-2969 C

Manual 2100-554G Page 9 of 14

FIGURE 6 Low Voltage Wiring Diagram: Dehumidification Heat Pump With Optional Economizer

HUMIDITY CONTROLLER CONNECTIONS USED ONLY FOR OPTIONAL DEHUMIDIFICATION CIRCUIT THAT MUST BE FACTORY INSTALLED IN HEAT PUMP YELLOW

BLUE

Low Voltage Wiring Diagram

8403-038 H600A1014 HUMIDITY CONTROLLER

RED 6

5

4

8403-047 H200-10-21-10 DEHUMIDSTAT

3

2 C

R

24V Low Voltage Terminal Block

C

R

O/B

RT

B

W1

W1/E

W2

L

G

E

W2

L

G

A

Y

Y2

Y1 YO/D

Y1 DH O1 W3

Pink

F

Yellow

E

Orange

1

Black

4

Blue

Black

Y2

Y1

Unit

Purple

Thermostat Bard part #8403-060

3

MIS-2970 B

Economizer Wiring Harness 1 Factory Jumper Installed. Must be configured for economizer with YO/D output to 2 be active as first stage cooling. 3 These wires are used in special control applications only. Factory installed jumper (on applicable models). 4 Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

Manual 2100-554G Page 10 of 14

FIGURE 7 Low Voltage Wiring Diagram: 2 Stage Heat Pump With Optional Electric Heat With ECONWM Style Economizer

R

Black

Red

RT

4

B

W1

W2

L

G

E

W2

L

G

3

Y1

Y2

A

Y

DH O1 W3

1

Economizer Wiring Harness

Y1 YO/D

Purple

C

W1/E

Pink

24V Low Voltage Terminal Block

O/B

Yellow/red

R

Brown/white Orange

C

Blue

Thermostat part #8403-060

Yellow

Low Voltage Wiring Diagram

2

Yellow/White

1

Must be energized to enable minimum position. NOTE: Economizer Control Default Setting is 10V (100%). Depending upon application may require setting to lower value.

2

Must be configured for heat pump and economizer to enable YO/D output to be active as 1st-stage cooling

3

Factory Jumper Installed.

Factory installed jumper (on applicable models). 4 Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

MIS-2982 C

Manual 2100-554G Page 11 of 14

FIGURE 8 Low Voltage Wiring Diagram: 2 Stage Heat Pump With Dehumidification & Optional Electric Heat With ECONWM Style Economizer

Low Voltage Wiring Diagram

R

RT

4

W1

L

G

E

W2

L

G

3

A

Y1

Y

Brown/white Orange

Blue

B

W2

YO/D

Y2

Y1

DH O1 W3

1

Purple

C

W1/E

Pink

24V Low Voltage Terminal Block

O/B

Yellow/red

R

Yellow

C

Black

Thermostat part #8403-060

Red

2

Economizer Wiring Harness

Manual 2100-554G Page 12 of 14

1

Must be energized to enable minimum position. NOTE: Economizer Control Default Setting is 10V (100%). Depending upon application may require setting to lower value.

2

Must be configured for heat pump to enable YO/D output to be active dehumidification output

3

Factory Jumper Installed.

4

Factory installed jumper (on applicable models). Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

MIS-2999 A

FIGURE 9 Low Voltage Wiring Diagram: 2 Stage Heat Pump With CHCRV-5 or CRVMWH-3 Vent Option Package With Programmable Thermostat With Optional On/Off CO2 Controller

Low Voltage Wiring Diagram

4 Thermostat Bard part #8403-060

C

G

R

Y1

Y2 W1/E W2 O/B

L

Y O/D

A

Electronic Programmable

3 1

2

4

3

5

Optional CO2 Controller Bard part #8403-067

6

2 24V Low Voltage Terminal Block

C

G

Black 1 Factory Jumper Installed

R

RT

Y

Y1

E

W2

B

5 Yellow Purple Red CHCRV-5 OR CRVMWH-3 Ventilation Package

W1 W3 DH

L

O1

Unit

1 Orange

MIS-3135 B

2 Do not connect "A" from tstat #8403-060 if optional CO2 controller is used. 3 Wire only needed for dehumidification units Must be configured to programmable and fan 4 set to programmed for the "A" output to function during scheduled occupied periods Factory installed jumper (on applicable models). 5 Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

Manual 2100-554G Page 13 of 14

FIGURE 10 Low Voltage Wiring Diagram: 2 Stage Heat Pump With CHCRV-5 or CRVMWH-3 Vent Option Package With Programmable Thermostat With Optional Modulating CO2 Controller

Low Voltage Wiring Diagram

3 Thermostat Bard part #8403-060

C

G

R

Y2 W1/E W2 O/B

Y1

A

L

Y O/D

Electronic Programmable

2 1

24V Low Voltage Terminal Block

C

G

R

RT

4 Black

Y Yellow

Red

E

Y1

Purple

CHCRV-5 OR CRVMWH-3

1 Factory Jumper Installed 2 Wire only needed for dehumidification units 3 Must be configured to programmable and fan set to programmed for the "A" output to function during scheduled occupied periods Factory installed jumper (on applicable models). 4 Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.

Manual 2100-554G Page 14 of 14

W2

B

2

3

4

5

Optional CO2 Controller Bard part #8403-067

6

L

W1 W3 DH

O1

Unit

1 Orange

Ventilation Package

IA CR IA CC

+

-

CRV CONTROL

MIS-3334 A