Stratashield Construction Details - TNEMEC.com

SFS-19 Expansion/Isolation Joint Treatment Detail at Wall/. Floor Interface for Laminate and Mortar Systems with cove. SFS-20 Expansion/Isolation Join...

32 downloads 861 Views 1MB Size
TABLE OF CONTENTS SFS-01 Leading Edge Termination Detail for Self-Leveling and Laminate Flooring Systems SFS-02 Leading Edge Termination Detail for Mortar Flooring Systems SFS-03 Termination Detail for Mortar at Nose Angle Iron at Loading Dock or Building Joint SFS-04 Termination Detail at Nose Angle Iron at Stair Tread or Building Joint

DETAILS GUIDE STRATASHIELD STANDARD FLOORING

SFS-05 Control Joint Treatment Detail with No Potential Movement SFS-06 Control Joint Treatment Detail with Potential Movement SFS-07 Expansion/Isolation Joint Treatment Detail SFS-08 Treatment for Non-Moving Crack Treatment Detail SFS-09 Treatment for Moving Crack Treatment Detail SFS-10 Treatment for Bridging Multiple Non-Moving Hairline Cracks SFS-11 Cant Cove Detail SFS-12 Spoon Cove Detail SFS-13 Rolled Radius Cove SFS-14 Rolled Radius Cove Detail Eliminating Top Edge SFS-15 Cove Detail for Flush Transition FRP SFS-16 Cove Detail for Flush Transition Tile SFS-17 Expansion/Isolation Joint Treatment Detail at Wall/ Floor Interface for Laminate and Mortar Systems without cove SFS-18 Expansion/Isolation Joint Treatment Detail at Wall/ Floor Interface for Laminate and Mortar Systems with cove SFS-19 Expansion/Isolation Joint Treatment Detail at Wall/ Floor Interface for Laminate and Mortar Systems with cove

TNEMEC COMPANY INCORPORATED 6800 Corporate Drive, Kansas City, MO 64120 1-800-TNEMEC1 www.tnemec.com

SFS-20 Expansion/Isolation Joint Treatment Detail at Wall/ Floor Interface for Laminate and Mortar Systems with cove SFS-21 Floor Drain Detail without Sealant SFS-22 Floor Drain Detail with Sealant

Published techincal data, instructions, and pricing are subject to change without notice. Contact your Tnemec technical representative for current technical data, instructions, and pricing. Warranty information: The service life of Tnemec’s coatings will vary. For warranty, limitation of seller’s liability, and product information, please refer to Tnemec’s Product Data Sheets at www.tnemec.com or contact your Tnemec Technical Representative. 6/2014

SFS-23 Sleeved or Non-Sleeved Pipe Penetration in Floor Detail

TABLE OF CONTENTS

Rolled Radius Cove Detail..............................................................SFS-13 Rolled Radius Cove Detail Eliminating Top Edge...............................SFS-14 Cove Detail for Flush Transition FRP................................................SFS-15 Cove Detail for Flush Transition Tile................................................SFS-16 Expansion/Isolation Joint Treatment Detail at Wall/Floor Interface for Laminate and Mortar Systems without cove.....................................SFS-17 Expansion/Isolation Joint Treatment Detail at Wall/Floor Interface for Laminate and Mortar Systems with cove.........................................SFS-18 Expansion/Isolation Joint Treatment Detail at Wall/Floor Interface for Laminate and Mortar Systems with cove.........................................SFS-19 Expansion/Isolation Joint Treatment Detail at Wall/Floor Interface for Laminate and Mortar Systems with cove.........................................SFS-20 Floor Drain Detail without Sealant.................................................SFS-21 Floor Drain Detail with Sealant......................................................SFS-22 Sleeved or Non-Sleeved Pipe Penetration in Floor Detail..................SFS-23

STRATASHIELD FLOORING SYSTEM

1/4" WIDE (6.35mm) 1/4" DEEP (6.35mm)

SAWCUT TERMINATION 1/4” (6.35mm) DEEP

EXISTING CONCRETE SUBSTRATE

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS LEADING EDGE TERMINATION DETAIL FOR SELF-LEVELING AND LAMINATE FLOORING SYSTEMS

NO. SFS - 01

REV.0

CHIP CONCRETE BACK A MINIMUM OF 3”(76.2mm) FOR TRANSITION WITH A 1/2” (12.7mm) DEPTH. MINIMUM 3" (76.2mm) STRATASHIELD FLOORING SYSTEM

1/2" (12.7mm) DEEP SAWCUT

SAWCUT TERMINATION 1/2” (12.7mm) DEEP EXISTING CONCRETE SUBSTRATE

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS LEADING EDGE TERMINATION DETAIL FOR MORTAR FLOORING SYSTEMS

NO. SFS - 02

REV.0

CHIP CONCRETE BACK A MINIMUM OF 3”(76.2mm) FOR TRANSITION WITH A 1/2” (12.7mm) DEPTH. EMBEDDED NOSING ANGLE IRON

MINIMUM 3" (76.2mm) STRATASHIELD FLOORING SYSTEM

1/2" (12.7mm) SAWCUT

EXISTING CONCRETE SUBSTRATE

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS TERMINATION DETAIL FOR MORTAR AT NOSE ANGLE IRON AT LOADING DOCK OR BUILDING JOINT

NO. SFS - 03

REV.0

TREAD NOSING

STRATASHIELD FLOORING SYSTEM

THICKNESS AS SPECIFIED

EXISTING CONCRETE SUBSTRATE

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS TERMINATION DETAIL AT NOSE ANGLE IRON AT STAIR TREAD OR BUILDING JOINT

NO. SFS - 4

REV.0

STRATASHIELD FLOORING SYSTEM

FILLER MATERIAL

EXISTING CONCRETE SUBSTRATE

NOTE: USE SERIES 215 OR STRATASHIELD 100% SOLIDS EPOXY MIXED WITH FUMED SILICA, SILICA FLOUR OR FINE AGGREGATE FOR FILLER MATERIAL

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS CONTROL JOINT WITH NO POTENTIAL MOVEMENT

NO. SFS - 5

REV.0

STRATASHIELD FLOORING SYSTEM

FLEXIBLE JOINT SEALANT

1/2" (12.7mm) DEEP SAWCUT

EXISTING CONCRETE SUBSTRATE

NOTE: FLEXIBLE JOINT SEALANT WIDTH TO DEPTH RATIO SHOWN IS APPROXIMATELY 2:1. DETAIL CAN BE BUILT BY INSTALLING FLOOR SYSTEM OVER JOINT, RESAWCUTTING, AND INSTALLING SEALANT.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS CONTROL JOINT WITH POTENTIAL MOVEMENT

NO. SFS - 06

REV.0

BACKER ROD AND FLEXIBLE JOINT SEALANT

STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

1/2" (12.7mm) 1/4" (6.35mm)

EXISTING EXPANSION/ ISOLATION JOINT MATERIAL

NOTE: FLEXIBLE JOINT SEALANT WIDTH TO DEPTH RATIO SHOWN IS APPROXIMATELY 2:1. DETAIL CAN BE BUILT BY INSTALLING FLOOR SYSTEM OVER JOINT, RESAWCUTTING, AND INSTALLING BACKER ROD AND SEALANT.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS EXPANSION/ISOLATION JOINT TREATMENT DETAIL

NO. SFS - 07

REV.0

PATCH WITH FILLER MATERIAL PRIOR TO INSTALLING STRATASHIELD FLOORING SYSTEM STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

NOTE: USE SERIES 215 OR STRATASHIELD 100% SOLIDS EPOXY MIXED WITH FUMED SILICA OR SILICA FLOUR FOR FILLER MATERIAL. ROUTE OUT CRACK PRIOR TO PATCHING IF CRACK IS LARGER THAN 1/16” (1.58mm).

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS TREATMENT FOR NON-MOVING CRACKS

NO. SFS - 08

REV.0

FLEXIBLE JOINT SEALANT

ROUTE OUT EXISTING CRACK AND PATCH WITH FILLER MATERIAL PRIOR TO INSTALLING STRATASHIELD FLOORING SYSTEM

STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

NOTE: USE SERIES 215 OR STRATASHIELD 100% SOLIDS EPOXY MIX WITH FUMED SILICA, SILICA FLOUR OR FINE AGGREGATE FOR FILLER MATERIAL FLEXIBLE JOINT SEALANT WIDTH TO DEPTH RATIO SHOWN IS APPROXIMATELY 2:1. DETAIL CAN BE BUILT BY INSTALLING FLOOR SYSTEM OVER CRACK, RESAWCUTTING, AND INSTALLING SEALANT.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS TREATMENT FOR MOVING CRACKS

NO. SFS - 09

REV.0

SERIES 206 FLEXIBLE UNDERLAYMENT 30-40 MILS

STRATASHIELD FLOORING SYSTEM

HAIRLINE CRACKS

EXISTING CONCRETE SUBSTRATE

NOTE: USE FLEXIBLE UNDERLAYMENT TO BRIDGE HAIRLINE CRACKS IN FLOORS WHERE NO EVIDENCE OF SETTLEMENT OR MOVEMENT AND WHERE FLOOR IS NOT EXPOSED TO DRASTIC THERMAL CHANGE.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS TREATMENT FOR BRIDGING MULTIPLE NON-MOVING HAIRLINE CRACKS

NO. SFS - 10

REV.0

CONCRETE, CMU, WALL BOARD, ETC.

45 DEGREE CANT COVE

1" - 2" HEIGHT (25.4mm - 50.8mm)

STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

NOTE: USE DRY MIXED TROWELABLE MORTAR VERSION OF FLOORING MATERIAL TO BUILD COVE.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS CANT COVE DETAIL

NO. SFS -11

REV.0

CONCRETE, CMU, WALL BOARD, ETC.

SPOON COVE

COVE HEIGHT 3/4”-1” (19mm-25mm)

STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

NOTE: USE DRY TROWELABLE MORTAR VERSION OF FLOORING MATERIAL TO BUILD COVE.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS SPOON COVE DETAIL

NO. SFS - 12

REV.0

CONCRETE, CMU, WALL BOARD, ETC.

METAL OR PLASTIC COVE STRIP (OPTIONAL)

ROLLED RADIUS COVE COVE HEIGHT 4”-6” (100mm-150mm) STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

NOTE: USE DRY MIXED TROWELABLE MORTAR VERSION OF FLOORING MATERIAL TO BUILD COVE.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS ROLLED RADIUS COVE DETAIL

NO. SFS - 13

REV.0

CONCRETE, CMU, WALL BOARD, ETC.

SERIES 215 SURFACING EPOXY METAL OR PLASTIC COVE STRIP

COVE HEIGHT 4”-6” (100mm-150mm)

ROLLED RADIUS COVE STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

NOTE: USE DRY MIXED TROWELABLE MORTAR VERSION OF FLOORING MATERIAL TO BUILD COVE.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS ROLLED RADIUS COVE DETAIL ELIMINATING TOP EDGE

NO. SFS - 14

REV.0

FRP PANEL

CONCRETE, CMU, WALL BOARD, ETC.

FRP TRIM STRIP

COVE HEIGHT 4”-6” (100mm-150mm)

ROLLED RADIUS COVE STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

NOTE: USE DRY MIXED TROWELABLE MORTAR VERSION OF FLOORING MATERIAL TO BUILD COVE AND BASE.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS COVE DETAIL FOR FLUSH TRANSITION FRP

NO. SFS - 15

REV.0

CONCRETE, CMU, WALL BOARD, ETC.

COVE HEIGHT 4”-6” (100mm-150mm)

TILE

ROLLED RADIUS COVE STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

NOTE: USE DRY MIXED TROWELABLE MORTAR VERSION OF FLOORING MATERIAL TO BUILD COVE AND BASE.

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS COVE DETAIL FOR FLUSH TRANSITION TILE

NO. SFS - 16

REV.0

CONCRETE, CMU, WALL BOARD, ETC.

BACKER ROD AND FLEXIBLE JOINT SEALANT STRATASHIELD FLOORING SYSTEM

EXISTING EXPANSION / ISOLATION

EXISTING CONCRETE SUBSTRATE

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS EXPANSION/ISOLATION JOINT TREATMENT AT WALL/FLOOR INTERFACE FOR LAMINATE AND MORTAR SYSTEMS WITHOUT COVE

NO. SFS - 17

REV.0

METAL OR PLASTIC COVE STRIP (OPTIONAL) CONCRETE, CMU, WALL BOARD, ETC.

*BOND BREAKER

EXISTING EXPANSION / ISOLATION

STRATASHIELD FLOOR TOPPING SAW CUT AND FILL WITH FLEXIBLE SEALANT

POLYETHYLENE BACKER ROD EXISTING CONCRETE SUBSTRATE

NOTE: *BOND BREAKER - EXCEED RECOAT WINDOW ON PRIMER 201, 222, 237, ETC. OR USE DUCT TAPE

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS EXPANSION/ISOLATION JOINT TREATMENT AT WALL/FLOOR INTERFACE FOR LAMINATE AND MORTAR SYSTEMS WITH COVE

NO. SFS - 18

REV.0

CONCRETE, CMU, WALL BOARD, ETC. METAL OR PLASTIC COVE STRIP (OPTIONAL)

STRATASHIELD FLOOR TOPPING SAW CUT AND FILL WITH FLEXIBLE SEALANT

EXISTING CONCRETE SUBSTRATE

EXISTING EXPANSION / ISOLATION

KEY IN WITH STRATASHIELD TOPPING 1/4” (6.35mm) TO 1/2”(12.7mm) DEEP

POLYETHYLENE BACKER ROD (OPTIONAL)

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS EXPANSION/ISOLATION JOINT TREATMENT AT WALL/FLOOR INTERFACE FOR LAMINATE AND MORTAR SYSTEMS WITH COVE

NO. SFS - 19

REV.0

CONCRETE, CMU, WALL BOARD, ETC. METAL OR PLASTIC COVE STRIP (OPTIONAL)

STRATASHIELD FLOOR TOPPING METAL OR PLASTIC TERMINATION STRIP

EXISTING CONCRETE SUBSTRATE

EXISTING EXPANSION / ISOLATION

KEY IN WITH STRATASHIELD FLOOR TOPPING 1/4” (6.35mm) TO 1/2”(12.7mm) DEEP POLYETHYLENE BACKER ROD (OPTIONAL)

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS EXPANSION/ISOLATION JOINT TREATMENT AT WALL/FLOOR INTERFACE FOR LAMINATE AND MORTAR SYSTEMS WITH COVE

NO. SFS - 20

REV.0

CAST-IN-PLACE CIRCULAR FLOOR DRAIN

CHIP CONCRETE BACK A MINIMUM OF 3”(76.2mm) FOR TRANSITION WITH A 1/2” (12.7mm) DEPTH.

MIN. 3" (76.2mm) STRATASHIELD FLOORING SYSTEM

EXISTING CONCRETE SUBSTRATE

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS FLOOR DRAIN DETAIL WITHOUT SEALANT

NO. SFS - 21

REV.0

CAST-IN-PLACE CIRCULAR FLOOR DRAIN

CHIP CONCRETE BACK A MINIMUM OF 3”(76.2mm) FOR TRANSITION WITH A 1/2” (12.7mm) DEPTH.

MIN. 3" (76.2mm) STRATASHIELD FLOORING SYSTEM

FLEXIBLE JOINT SEALANT EXISTING CONCRETE SUBSTRATE

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS FLOOR DRAIN DETAIL WITH SEALANT

NO. SFS - 22

REV.0

EXISTING PIPE OR SLEEVE

1” - 2” (25.4mm - 50.5mm) HEIGHT

FLEXIBLE JOINT FILLER STRATASHIELD FLOORING SYSTEM

BACKER ROD

EXISTING CONCRETE SUBSTRATE

TNEMEC STR ATASHIELD STANDARD FLOORING DETAILS SLEEVED OR NON-SLEEVED PIPE PENETRATION IN FLOOR DETAIL

NO. SFS - 23

REV.0