www.lsis.biz
Pro-MEC
Vacuum Circuit Breakers Vacuum Interrupter
Vacuum Circuit Breaker & Vacuum Interrupter
LSIS Pro-MEC VCB is user-friendly to give more convenience and safety by providing high speed interrupting time (3cycles), adopting the rapid auto-reclosing method, and having wide range of accessories.
7.2kV Draw-out (F class)
24kV Draw-out (F class)
Pro-MEC
VCB/VI
Vacuum Circuit Breaker
Contents
H1
Ratings
H1-4
Constructional and operating characteristics
H1-8
Control circuit diagram
H1-9
7.2kV dimension
H1-10
12kV dimension
H1-19
17.5kV dimension
H1-24
24kV dimension
H1-27
Accessories
H1-35
Types and ordering information
H1-40
Vacuum Interrupter Features & Ordering information
H1-43
VI internal structure
H1-44
Basic functions and interrupting action
H1-45
VI endurance by interrupting current
H1-46
Dimensions
H1-48
Technical data
H1-50
Vacuum Circuit Breaker LSIS Pro-MEC VCB is user-friendly to give more convenience and safety by providing high speed interrupting time (3cycles), adopting the rapid auto-reclosing method, and having wide range of accessories.
7.2kV Draw-out (F class) 24kV Draw-out (F class)
Wide range of accessories (optional) � Key Lock � Padlock of earthing switch � Button padlock � Position switch of the earthing switch � Button cover � Locking coil of earthing switch � Position switch (Cell switch) � Shutter padlock � Preparatory trip coil (Secondary trip coil) � MOC (Mechanically operated cell switch) H1-2
� Latch checking switch � TOC (Truck operated cell switch) � Charge indicator � Code plate (Miss insertion prevention) � Position padlock � Capacitor trip device � Earthing switch Note 1) � Rectifier Note 1) The earthing switch is not available for 17.5kV VCB.
VACUUM CIRCUIT BREAKER
[ Compasion table for VCB (Short circuit test) ]
Compasion table for VCB (Short circuit test)
High reliability of the operating mechanism - Separate design of the main circuit from the operating mechanism. - Adopt the toggle link method. - Improved the reliability of electric circuit. - Adopt the rapid auto-reclosing method as a standard option. (O-0.3sec.-CO-3min.-CO)
High interrupting performance
Great operational safety
�Make short of the interrupting time. (3cycles) �Increase the rated short-circuit withstand characteristics. (1sec. to 3sec.)
�Reinforce the insulation in the conduct, by adopting the molded housing in each phase. �Built in the device making the contacts open first when draw in and out. �Adopt the tulip-shape connection between the cradle and the VCB.
H1-3
Vacuum Circuit Breaker Ratings Type
�-32D LVB-06�
Rated voltage
(kV)
Rated normal current
�-40D LVB-06�
7.2
(A)
1250
2000
7.2 3150
1250
2000
Rated frequency
(Hz)
50/60
50/60
Rated short-circuit breaking current
(kA)
31.5
40 500
Rated short-circuit breaking capacity
(MVA)
390
Rated short-time withstand current
(kA/3sec)
31.5
40
Rated short-circuit making current
(kAp)
82
104
Rated breaking time
(Cycle)
3
3
Rated opening time
(sec)
≤ 0.04
≤ 0.04
No-load closing time
(sec)
≤ 0.06
≤ 0.06
Withstand Power frequency voltage Impulse
(kV/min)
20
20
(kV/1.2×50㎲)
60
60
Rated operating sequence Type test
Mechanical Electrical
O-0.3s-CO-3min-CO
M2 (10,000 times)
M2 (10,000 times)
E2 (List1)
E2 (List1)
Capacitive current switching Note 1) Mechanical
Lifetime Electrical
C2
C2
Without maintenance (Time)
20000
20000
Maintenance
30000
30000
(Time)
Without maintenance (Time)
20000
20000
Maintenance
30000
30000
(Time)
Auxiliary switch
4a4b, 10a10b
Fixed
Draw-out type
Visible, Fixed
Visible, Fixed
Visible, Fixed
Visible, Tulip
Visible, Clip
Visible, Tulip
Visible, Tulip
Visible, Tulip
Visible, Tulip
Visible, Tulip
Visible, Tulip
Visible, Tulip
Visible, Tulip
Visible, Tulip
Visible, Tulip
Enclosed, Tulip
-
Enclosed, Tulip
-
F-type G-type Note 2)
T
M-type
Enclosed, Tulip -
E-type VCB
4a4b, 10a10b
Visible, Fixed E-type
Installing method
O-0.3s-CO-3min-CO
(kg)
3150
131.5
134.5
Enclosed, Tulip 210
135
-
138
210
F-type
(kg)
132.5
135.5
211
136
139
211
Weight
G, M-type
(kg)
132.5(159)
135.5(160)
220
136(162.5)
139(163.5)
220
Note 3)
E-type
(kg)
131
52
60
131
F-type
(kg)
54.5
62.5
135
G-type
(kg)
62.5(110)
135(117)
155
Cradle
52 60 54.5 62.5 62.5(110)
Applied standard Test laboratory
KERI Note 4)
135 135(117) 155 IEC 62271-100
IEC 62271-100
�
�
Note 1) Applied cable-charging current switching test 2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T” in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T) 3) ( )* indicates the weight of Enclosed Tulip installing method VCB. 4) KERI: Korea Electrotechnology Research Institute
▲ Enclosed VCB (Draw-out type, G-type)
H1-4
▲ G-type Cradle (Enclosed, Tulip contact)
▲ Visible, Clip contact
▲ Visible, Tulip contact
▲ Enclosed, Tulip contact
Type Rated voltage
�-32D/12, 20-T, 30 LVB-12�
�-40D/12, 20, 30 LVB-12�
�-40D/12, 20, 30 LVB-17�
12
12
17.5
(kV)
Rated normal current
(A)
Rated frequency Rated short-circuit breaking current Rated short-circuit breaking capacity
1250
2000
3150
1250
2000
3150
1250
50(E1,C2:KEMA), 60(M2,E2,C2: PT & T)
2000
(Hz)
60(E1,E2,C2: PT & T)
(kA)
31.5
40
40
(MVA)
650
831
1200
Rated short-time withstand current
(kA/3sec)
31.5
40
40
Rated short-circuit making current
(kAp)
81.9
104
104
Rated breaking time
(Cycle)
3
3
3
Rated opening time
(sec)
0.04
0.04
≤0.04
(sec)
0.06
0.06
≤0.06
28
28
38
No-load closing time Withstand Power frequency voltage Impulse
(kV/min) (kV/1.2×50㎲)
Rated operating sequence Type test
75
75
95
O-0.3s-CO-3min-CO
O-0.3s-CO-3min-CO
O-0.3s-CO-3min-CO
M2 (10,000 times)
M2 (10,000 times)
M2 (10,000 times)
E2 (List 1)
E2 (List 1)
E2 (List 1)
Mechanical Electrical
C2
C2
C2
Without maintenance (Time)
20,000
20,000
20,000
Maintenance
(Time)
30,000
30,000
30,000
Without maintenance (Time)
20,000
20,000
20,000
Capacitive current switching Note) Mechanical
Lifetime Electrical
Maintenance
(Time)
Auxiliary switch Fixed Installing Method
E-TYPE Draw-out type
F-TYPE M-TYPE
VCB Weight Cradle
30,000
30,000
30,000
4a4b, 10a10b
4a4b, 10a10b
4a4b, 10a10b
-
-
-
-
-
-
-
G-TYPE E-TYPE
(kg)
F-TYPE
(kg)
G, M-TYPE
(kg)
3150
60
-
Enclosed, Tulip
Visible, Tulip
Enclosed, Tulip
-
Enclosed, Tulip
159
160
Visible, Tulip
Visible, Tulip
-
-
-
-
220
162
163
220
200
205
260
E-TYPE
(kg)
-
-
-
-
-
-
-
-
-
F-TYPE
(kg)
-
-
-
-
-
-
-
-
-
G, M-TYPE
(kg)
110
117
155
110
117
155
175
175
200
Applied standard Test laboratory
IEC 62271-100 PT & T: E1, E2, C2, M2
KEMA, PT & T
Note) Applied cable-charging current switching test
H1-5
Vacuum Circuit Breaker Ratings Type
�-13D LVB-20� �-13D/T LVB-20� �-16D LVB-20� �-16D/T LVB-20� �-25D LVB-20� �-25D/T LVB-20�
Rated voltage Rated normal current
(kV)
24
24
24
(A)
630
630
630
1250
1250
1250
(Hz)
50/60
50/60
50/60
2000 Rated frequency Rated short-circuit breaking current
(kA)
12.5
16
25
(MVA)
520
665
1000
Rated short-time withstand current
(kA/3sec)
12.5
16
25
Rated short-circuit making current
(kAp)
32.5
40
65
3
3
3
Rated short-circuit breaking capacity
Rated breaking time
(Cycle)
Rated opening time
(sec)
≤ 0.04
≤ 0.04
≤ 0.04
(sec)
≤ 0.06
No-load closing time Withstand Power frequency voltage Impulse
≤ 0.06
≤ 0.06
(kV/min)
50
50
50
(kV/1.2×50㎲)
125
125
125
Rated operating sequence Type test
O-0.3s-CO-3min-CO
O-0.3s-CO-3min-CO
M2(10,000 times)
M2(10,000 times)
M2(10,000 times)
E2 (List1)
E2 (List1)
E2 (List1)
C2
C2
C2
Without maintenance (Time)
20000
20000
20000
Maintenance
30000
Mechanical Electrical Capacitive current switching Note 1) Mechanical
Lifetime Electrical
(Time)
30000
30000
Without maintenance (Time)
20000
20000
20000
Maintenance
30000
30000
30000
4a4b, 10a10b
4a4b, 10a10b
4a4b, 10a10b
(Time)
Auxiliary switch Fixed Installing method
O-0.3s-CO-3min-CO
Visible, Fixed
-
Visible, Fixed
-
Visible, Fixed
-
Visible, Clip
Enclosed, Tulip
Visible, Clip
Enclosed, Tulip
Visible, Clip
Enclosed, Tulip
E-type Draw-out
F-type
Visible, Clip
Enclosed, Tulip
Visible, Clip
Enclosed, Tulip
Visible, Clip
Enclosed, Tulip
type
G-type Note 2)
Visible, Tulip
Enclosed, Tulip
Visible, Tulip
Enclosed, Tulip
Visible, Tulip
Enclosed, Tulip
M-type VCB Weight Cradle
-
Enclosed, Tulip
-
Enclosed, Tulip
-
Enclosed, Tulip
E-type
(kg)
145
145
145
145
145
145
F-type
(kg)
145
145
145
145
145
145
G, M-type
(kg)
155
187
155
187
155
187/218 (2000A)
E-type
(kg)
80
80
80
80
80
80
F-type
(kg)
82
82
82
82
82
82
G-type
(kg)
110
120
110
120
110
120
Applied standard Test laboratory
IEC 62271-100
IEC 62271-100
IEC 62271-100
KERI
�
-
�
KEMA
-
�
�
Note 1) Applied cable-charging breaking current 2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T” in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)
▲ Fixed type VCB
H1-6
▲ E-type cradle
▲ F-type cradle
▲ G-type cradle (Withdrawable by lever)
▲ G-type cradle (Withdrawable by screw)
Motor When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w. The peak value of the
Rated voltage
inrush current (A)
Consumption power (W)
Rated current (A)
Charging time (Sec.)
DC 48V
21
4
350
13
DC 110V
20
3
330
12
DC 125V
20
3
330
12
DC 220V
17
2.6
374
12
Note 1) Range of the normal operating voltage: 85~110% 2) DC 24V is the underdeveloped rating.
Closing Coil (C)
Shunt coil (TC)
The coil operated only when the power is applied continuously over 45ms. It has built-in electrically anti-pumping circuit.
When the VCB is 'ON' position, even though the control power of a shunt coil is 'OFF', the VCB maintains the 'ON' position.
Rated voltage
Rated current (A)
Rated voltage
Rated current (A)
DC 48V
6
DC 48V
6
DC 110V
3
DC 110V
3
DC 125V
3
DC 125V
3
DC 220V
2.5
DC 220V
2.5
Note 1) Range of the normal operating voltage: 85~110% 2) DC 24V is the underdeveloped rating.
Note 1) Range of the normal operating voltage: 70~110% 2) DC 24V is the underdeveloped rating.
Auxiliary switch
�Position of the Aux.contact switch
Standard 4a4b / Optional 10a10b General load (A)
Classification AC Contact Ratings
Inductive load (A)
250V 10
5
125V 10
5
250V DC 125V 30V 10
10
5
10
5
Contact configuration
VCB
“a” contact
“b”contact
ON
ON
OFF
OFF
OFF
ON
4a4b 10a10b
5
Note) The contact capacity of the following accessories are the same with that of the Aux. switch. Position switch, Closing sp ring contact, Charging complete indicating contact, Position switch of the earthing switch, Mechanically operated cell switch, Truck operated cell switch.
Charge indicator of the closing spring
Position indicator of the main contacts
Indicating the condition of the closing spring.
Indicating the 'Close' or the 'Open' of the main contacts. � Open position:�OFF� � Close position:�ON�
Charged
Discharged Close position
Open position
Counter Mechanically counts the switching of the VCB by 5digits analog type counter (Standard option)
H1-7
Vacuum Circuit Breaker Constructional and operating characteristics ① Charge Indicator of the closing spring ② Close button ③ Key lock (Optional) ④ Trip button ①
⑤
⑤ Manual charge hole
②
⑪
⑥ Position indicator of the main contacts
③
⑨
⑦ Counter ⑧ Screw hole for draw-in and draw-out ⑨ Nameplate
④
⑩ Mounting hole ⑥
⑪ Safety cover
⑦
⑩ ⑧
Manual charge Insert the charge handle into the manual charge hole in the front of a VCB, and rotate it to clockwise over 40times and the charge complete with a metal sound.
Motor charge If you apply the control power to a VCB, the closing spring will be charged automatically by a motor and then the control power will be turned off by the built-in limit s/w. Please use the same control voltage for motor, Closing coil, Trip coil.
Sequence of the switching mechanism
H1-8
※ Above circuit diagram is based on ‘OFF’ status of VCB. and closing spring is charged.
5) In fixed type VCB, LS1 (Closing-coil limit switch) is not available.
4) TC1: Secondary trip coil (Preparatory trip coil Terminal No.: 82,83)
3) Position switch: 4a (Terminal No.: 1, 2, 3, 4, 5, 6, 7, 8)
Optional accessories
52b: Auxiliary switch (NC) LS1: Closing interlock limit switch (only withdrawable type) LS2: Motor stopping, closing spring charged indication LS3: Anti-closing, anti-pumping limit switch LCS1: Opening latch checking switch(preventing closing unless the trip latch is properly reset) LS4, LS5: Position s/w (close in test position) LS6, LS7: Position s/w (close in run position)
2) Trip coil supervision (Trip coil monitoring contact)
Note 1) LCS1: Latch checking switch
∅: External terminal of VCB 52: Vacuum circuit breaker M: Spring charging motor TC: Trip coil TC1: Secondary Trip coil C: Closing coil Y: Anti-pump relay 52a: Auxiliary switch (NO)
A Type
Connecting terminal arrangement B Type
Control circuit diagram
H1-9
Vacuum Circuit Breaker 7.2kV dimension (VCB) LVB-06P-32D, 40D (Visible, Fixed) - (1250/2000A)
(Unit: mm)
�Top
*125.5 applied to all 7.2kV VCB.
�Front
�Side
LVB-06P-32D, 40D (Visible, Fixed) - (3150A) �Front
H1-10
�Side
�Top
LVB-06E, F, G-32D, 40D E, F, G class - (1250/2000A) �Top
�Front
(Unit: mm)
�Side
LVB-06G- 32D/T, 40D/T G class (Enclosed, Tulip contact) - (1250/2000A) �Front
�Side
H1-11
Vacuum Circuit Breaker 7.2kV dimension (VCB) LVB-06E-32D, 40D �Front
LVB-06F-32D, 40D �Front
H1-12
E class (Visible, Tulip contact) - (3150A) �Side
�Top
F class (Visible, Tulip contact) - (3150A) �Side
�Top
(Unit: mm)
LVB-06G-32D, 40D �Front
G class (Visible, Tulip contact) - (3150A)
(Unit: mm)
�Side
�Top
H1-13
Vacuum Circuit Breaker 7.2kV dimension (Cradle) LCL-06E-32D, 40D �Front
E class (Visible, Tulip contact)
(Unit: mm)
�Side Rating
1250A
2000A
A
10
20
�Top
LCL-06E-32D, 40D �Front
H1-14
E class (Visible, Tulip contact) - (3150A) �Side
�Top
LCL-06F-32D, 40D �Front
F class (Visible, Tulip contact) - (1250/2000A)
(Unit: mm)
�Side Rating
1250A
2000A
A
10
20
�Top
LCL-06F-32D, 40D �Front
F class (Visible, Tulip contact) - (3150A) �Side
�Top
H1-15
Vacuum Circuit Breaker 7.2kV dimension (Cradle) LCL-06G-32D, 40D G class(Visible, Tulip contact) - (31.5/40kA 1250/2000A) �Front
�Side
�Top Rating A
1250A 2000A 10
20
H1-16
(Unit: mm)
LCL-06G-20D/T, 25D/T, 32D/T, 40D/T G class (Enclosed, Tulip contact) - (630/1250/2000A) �Front
(Unit: mm)
�Side
�Top
Rating A B
31.5/40kA 1250A 2000A 12
25 ∅48
H1-17
Vacuum Circuit Breaker 7.2kV dimension (Cradle) LCL-06G-32D, 40D
G class (Visible, Tulip contact) - (3150A)
�Side
�Top
*To connect with VCB ’s bushing terminals user busbar should have below dimensions and two holes.
H1-18
(Unit: mm)
12kV dimension (VCB) LVB-12G-32D/T
G class (Enclosed, Tulip contact) - (1250/2000A)
�Front
(Unit: mm)
�Side
LVB-12G-40D
G class (Enclosed, Tulip contact) - (1250/2000A)
�Front
�Side 470
�Top 330
150
150
496 549
288
33.5
10
69
355
668
726.5
295
325
438
40kA 1250/2000A
G class
H1-19
Vacuum Circuit Breaker 12kV dimension (VCB) LVB-12G-40D
G class (Enclosed, Tulip contact) - (3150A)
�Front
(Unit: mm)
�Side 620
336
290
714 747
502
�Top 210
676
210
40kA 3150A
H1-20
G class
10
348.5
806.6
360
325
12kV dimension (Cradle) LCL-12G-25D/T, 32D/T �Front
G class (Enclosed, Tulip contact) - (630/1250/2000A)
(Unit: mm)
�Side
�Top
Rating A B
25kA 1250A 2000A 12
25 ∅48
H1-21
Vacuum Circuit Breaker 12kV dimension (Cradle) LCL-12G-40D
G class (Enclosed, Tulip contact) - (1250/2000A)
�Front
(Unit: mm)
�Side 1250A:12t
630
1235
295
2000A:25t
731.5 946
40kA 1250/2000A
G class
150
150 26
83
60
26
�Top
150 150
560
600
RUN 4-∅14 Mount hole
100
H1-22
662
LCL-12G-32D/LCL-12G-40D �Front
G class (Enclosed, Tulip contact) - (3150A)
(Unit: mm)
�Side 12
439
1100
360
12
764 1014
40kA 3150A
G class
�Top
230
230 120
145
210
760
800
210
35
70
4-∅14 Mount hole
100
724
H1-23
Vacuum Circuit Breaker 17.5kV dimension (Cradle) LVB-17G-40D �Front
LVB-17G-40D �Front
H1-24
G class (Visible, Tulip contact) - (1250/2000A) �Side
(Unit: mm)
�Top
G class (Visible, Tulip contact) - (3150A) �Side
�Top
H1-24
LCL-17G-40D
G class (Visible, Tulip contact) - (1250/2000A)
(Unit: mm)
�Side
�Top
H1-25
Vacuum Circuit Breaker 17kV dimension (VCB) LCL-17G-40D
G class (Visible, Tulip contact) - (3150A)
�Side
�Top
H1-26
(Unit: mm)
24kV dimension (VCB) LVB-20P-13D, 16D, 25D (Visible, Fixed) - (630/1250/2000A) �Front
(Unit: mm)
�Side
LVB-20E, F-13D/(T), 16D/(T), 25D/(T) �Front
E, F class - (630/1250/2000A)
�Side
Note ) In case of 12.5kA & 16kA 630A, the dimension shown in parenthesis should be applied.
H1-27
Vacuum Circuit Breaker 24kV dimension (VCB) LVB-20G-13D, 16D, 25D
G class (Visible, Tulip contact) - (630/1250A)
�Front
LVB-20G-13D/T, 16D/T, 25D/T �Front
(Unit: mm)
�Side
G class (Enclosed, Tulip contact) - (630/1250/2000A) �Side
Note 1) (
): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T, LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm. 2) IP Cover applied both sides in case of 265mm phase distance.
H1-28
H1-28
24kV dimension (Cradle) LCL-20E-13D, 16D, 25D
E class (Visible, Clip contact) - (630/1250/2000A)
�Front
�Side Rating
�Top
(Unit: mm)
A
B
T
630, 1250A
768 190.5 10
2000A
778 185.5 20
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-29
Vacuum Circuit Breaker 24kV dimension (Cradle) LCL-20E-13D/T, 16D/T, 25D/T
E class (Enclosed, Tulip contact) - (630/1250/2000A) �Side Rating
A
B
T
768 190.5 10
2000A
778 185.5 20 10(630/1250A)
630, 1250A
340 1033
15
265
280
404.5
115
265
20(2000A)
�Front
947.5
730 960
1120 1167
20
400
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
210
100
300
40
7-∅14
400
300
42 100 45
40 80 210.5
20
90
40
245
20
40
265
40
4-∅14
4-∅14
40
820
2-∅14
145
265
25
90 47
660 ST: 260
2000A
40.5
20 40 67
1250A
40 80
630A
202
�Top
H1-30
∅6.5
97.5
972
110
(Unit: mm)
LCL-20F-13D, 16D, 25D
F class (Visible, Clip contact) - (630/1250/2000A)
�Front
(Unit: mm)
�Side Rating
A
B
T
630, 1250A
768 190.5 10
2000A
778 185.5 20
�Top
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-31
Vacuum Circuit Breaker 24kV dimension (Cradle) LCL-20F-13D/T, 16D/T, 25D/T F class(Enclosed, Tulip contact) - (630/1250/2000A) �Front
�Side Rating
A
B
T
630, 1250A
768 190.5
10
2000A
778 185.5
20
�Top
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-32
(Unit: mm)
LCL-20G-13D, 16D, 25D �Front
G class (Visible, Tulip contact) - (630/1250A)
(Unit: mm)
�Side
�Top
H1-33
Vacuum Circuit Breaker 24kV dimension (Cradle) LCL-20G-13D/T, 16D/T, 25D/T G class (Enclosed, Tulip contact) - (630/1250/2000A) �Front
�Side
�Top
210mm Note) (
): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T, LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.
�Earthing Switch
H1-34
(Unit: mm)
Accessories Accessories for VCB Key lock When it is locked by a key, the closing operation is not available (electrically and mechanically) without a Key.
Button padlock Button padlock protects 'ON' or 'OFF' button when accident is occurred by operation at discretion. It is available to operate after release button padlock.
Button cover Button cover protects 'ON' of 'OFF' button when accident is occurred by operation at discretion. It is available to operate by push bar.
Position switch (Cell switch) Indicating the position (Run or Test) of a VCB, by mechanically pressing the switch when a VCB change the position. - RUN: 2a - TEST: 2a
Note) In case that position of VCB changed to “Run” or “Test” position, “a” contact will be closed.
H1-35
Vacuum Circuit Breaker Accessories Accessories for VCB Secondary coil (Preparatory trip coil) The main coil and the preparatory coil is connected in parallel. So even though there happens a fault in the trip coil, the VCB can be tripped by one of the two trip coils.
Latch checking switch When the Latch is in abnormal position, the Latch checking switch prevents the closing operation even though there is the 'Closing' signal.
Charge indicator Remotely indicates the charging is completed. (Standard Feature) - Terminal No.: 9, 10
Position padlock The hole to prevent the draw-in and out of a VCB from the present position.('Run' or 'Test') Standard option in the interlock lever of the E, F class draw-out type VCB. (Hole size = ∅ 8)
H1-36
Accessories for Cradle Earthing switch (for G class draw-out type only) For the safety during the maintenance of a VCB panel, discharge the charging current in the load side of a VCB with this earthing switch.
Padlock of earthing switch (for G class draw-out type only) The hole to prevent the accident through carelessness earthing switch operation, the locking of the earthing switch is available when the switch is in 'OFF' position. (Hole size = ∅8)
Position switch of the earthing switch (for G class draw-out type only) Indicates the 'ON' or 'OFF' status of the earthing switch. (5a5b)
Locking coil of earthing switch (for G class draw-out type only)
To prevent the accident through carelessness earthing switch operation, the earthing switch can be changed to 'ON' position after releasing the lock by magnetizing the coils.
H1-37
Vacuum Circuit Breaker Accessories Accessories for Cradle Shutter padlock The hole to lock the shutters (load and line side) in close position, to increase the safety during the maintenance of a VCB draw-out position. (Hole size = ∅8)
Mechanically operated cell switch (MOC) -for G class draw-out type only The auxiliary switch (3a4b), which Indicate the 'ON' or 'OFF' condition of a VCB, but operated only when the VCB is in 'Run' state. (Installed in the bottom of a cradle)
Note) #11, 21 are Early “b” contact
Truck operated cell switch (TOC) -for G class draw-out type only The auxiliary switch (3a4b), which indicate the 'Run' state of a VCB and is operated by the movement of a VCB frame. (Installed in the bottom of a cradle)
Note) #11, 21 are Early “b” contact
Code plate (Miss insertion prevention) -for E, F class draw-out type only To prevent the insert a VCB to a cradle, when the ratings of VCB and cradle are different.
Padlock To prevent the insert draw-in/out handle to a screw hole by operating G class VCB temporarily
H1-38
Optional accessories Capacitor trip device (CTD)
�Dimension
When the control power is off, the CTD supply the power for tripping a VCB.
Ratings
Specification
Type CB-T1 Rated input voltage
CB-T2 AC100/110V
AC200/220V
Freguency (Hz)
50/60
50/60
Charging volt(V)
140/155
280/310
Charging time
�Connection diagram
�CDT
Within 10 Sec. after the AC power off
Tripping time
Within 30 Sec. after the AC power off
Allowable Input voltage range
85% ~ 100%
85% ~ 110%
Capacitor rating(μF)
1000
560
Rectifier
�Dimension
When the DC power is not available, rectify the AC power and get the DC power for closing coil. 40A DC
Rating time 10 sec.
25
29.5
70
1∅ 100/110V 1∅ 200/220V
100
VCB-X
AC Input voltage Output current
150
Type
40
80
�Connection diagram
E, F class
+
Standard tool
-
~
~
G class
Handle for draw-in and out
Manual charging handle
Handle for draw-in and out the VCB (Standard feature in the draw-out type)
Handle for charging the spring manually. (Standard feature) H1-39
Vacuum Circuit Breaker Types and ordering information 12kV LVB LS VCB
12
G
32
Installation method G M
D
12
1A
1A
DC110V
G class draw-out type
1B
DC220V
+ Bushing
1C
DC48V
1E
DC125V
D
B, C1, D1
Control voltage
Revision No.
G class draw-out type
Pro-MEC
Rated voltage 12
2B
12kV
Breaking current
Auxiliary switch
Rated current
32
31.5kA
12
1250A
2B 4a4b(A type connector)
Accessories
40
40kA
20
2000A
2E 10a10b(A type connector)
B Position Switch (RUN/TEST:2a2a)
30
3150A
2G 4a4b(B type connector)
C1 Button Padlock (ON)
2H 10a10b(B type connector)
C2 Button Padlock (OFF) C3 Button Padlock (ON/OFF) D1 Button Cover (ON) D2 Button Cover (OFF) D3 Button Cover (ON/OFF) E Button padlock (ON)+ Button cover (OFF) F Button padlock (OFF)+ Button cover (ON) G Key Lock H Secondary Trip Coil(Preparatory trip coil) J Fire-endurable wiring cable ass’y K Opening Latch Checking Switch S Pad Lock (G class) T Enclosed type, Tulip contact
Cradle LCL LS Cradle
12
G Installation method G
Rated voltage 12
H1-40
12kV
32 Breaking current
G class
32
31.5kA
draw-out type
40
40kA
D Revision No. D
Pro-MEC
12 Rated current 12
1250A
20
2000A
30
3000A
A, B, C Accessories T Enclosed type, Tulip contact
17.5kV LVB LS VCB
Rated voltage 17
17
G
40
D
12
1A
Revision No.
Installation method
D
2B
B, C1, D1
Control voltage
Pro-MEC
P
Fixed type
1A
DC110V
E
E class draw-out type
1B
DC220V
F
F class draw-out type
1C
DC48V
G
G class draw-out type
1E
DC125V
17.5kV
Breaking current 40
40kA
Auxiliary switch
Rated current 12
1250A
2B 4a4b(A type connector)
Accessories
20
2000A
2E 10a10b(A type connector)
B Position Switch (RUN/TEST:2a2a)
30
3150A
2G 4a4b(B type connector)
C1 Button Padlock (ON)
2H 10a10b(B type connector)
C2 Button Padlock (OFF) C3 Button Padlock (ON/OFF) D1 Button Cover (ON) D2 Button Cover (OFF) D3 Button Cover (ON/OFF) E Button padlock (ON) + Button cover (OFF) F Button padlock (OFF) + Button cover (ON) G Key Lock H Secondary Trip Coil(Preparatory trip coil) K Opening Latch Checking Switch S Pad Lock (G class) J Fire-endurable wiring cable ass’y
Cradle LCL LS Cradle
Rated voltage 17
17
G
Installation method E
E class draw-out type
F G
40 Breaking current
D Revision No. D
12 Rated current 12
1250A
F class draw-out type
20
2000A
G class draw-out type
30
3150A
Pro-MEC
A, B, C Accessories A
MOC (3a4b) + TOC (3a4b)
Note) ‘A’ is for ‘G’ class only
17.5kV
H1-41
Vacuum Circuit Breaker Types and ordering information 24kV LVB
20
G
LS VCB
13
Installation method P
Fixed type
E
E class draw-out type
Rated voltage
F
F class draw-out type
20
G
24kV
D
M
06
Revision No.
1A
2B
Control voltage
D Pro-MEC
00
-
1A
DC110V
1B
DC220V
G class draw-out type
1C
DC48V
G class draw-out type + Bushing
1E
DC125V
Note1)
E
B, C, D
Pro-MEC (Minimized type)
AC220(M),
1F
DC110(TC)
Accessories B C1 C2 C3 D1 D2 D3 E
AC220(M),
1H
DC220(TC)
1T
AC110(M),
F
DC110(TC)
G H
Auxiliary switch
Rated current
Breaking current 13
12.5kA
06
630A
16
16kA
12
1250A
25
25kA
20
2000A
Note2)
00
-
2B 4a4b(A type connector) 2E 10a10b(A type connector) 2G 4a4b(B type connector) 2H 10a10b(B type connector)
J K P1 P2 Q R S T
Position Switch (RUN/TEST:2a2a) Button Padlock (ON) Button Padlock (OFF) Button Padlock (ON/OFF) Button Cover (ON) Button Cover (OFF) Button Cover (ON/OFF) Button padlock (ON) + Button cover (OFF) Button padlock (OFF) + Button cover (ON) Key Lock Secondary Trip Coil (Preparatory trip coil) Fire-endurable wiring cable ass’y Opening Latch Checking Switch Dummy VCB(AMP Jack) Dummy VCB(Phoenix Jack) Earthing Truck(Lower terminal earthing) Earthing Truck(Upper terminal earthing) Pad Lock (G class) Enclosed type, Tulip contact Option
Note) 1. Version E is available only at 24kV G class and its distance between phases is 210mm. 2. "00" is used for ordering Earthing Truck and Dummy VCB 4. Accessory only for versions D and E
N CTD(Capacitor Trip Device) O Rectifier
Cradle LCL
20
G
LS Cradle
Rated voltage 20
Installation method
13
D Revision No.
Breaking current
E
E class draw-out type
13
12.5kA
F
F class draw-out type
16
16kA
G G class draw-out type
25
25kA
24kV
06
Note1)
A, B, C Accessories
Rated current
A Conventional
06
630A
Note2)
A MOS(3a4b)+ TOC(3a4b)
D
Pro-MEC
12
1250A
Note2)
B Earthing Switch
Pro-MEC
20
2000A
Note2)
C
E
(Minimized type)
T PS
Note) 1. Version E is available only at 24kV G class and its distance between phases is 210mm. 2. Versions A, B and C are available only at G class VCB.
H1-42
Earthing Switch Position Switch+ Earthing Switch Locking coil Enclosed type, Tulip contact Position S/W Block (24kV E/F class only)
Vacuum Interrupter Features & Ordering information Features Accumulation of more than 20 years of vacuum-related technologies Simplified arc extinguishing system Spiral contact structure with Radial magnetic field provides effective dispersing of the acr energy. Simple structure and high quality Sealing after complete removal of gas in the vacuum chamber in order to secure a long vacuum confidentiality Small size and light weight The new contact material used to enhance the competitiveness of the size Wide rated coverages Wide interrupting range from 6kV up to 40.5kV 40kA High reliability and electrical life Certification by KERI and KEMA according to the latest standard IEC62271-100 (2008) E2, LIST3, M2
Modeling system LV7
Basic type
A
-
P
Revision No A, B…
ETC.
L
LS
Null
Straight type
V
Vacuum
P
Potting type
7
Series No.
C
Wave type
E
Embedded type
G
Gas Insulation type
H1-43
Vacuum Interrupter VI internal structure Largely movable and fixed electrodes and main shield compose the Susol VI. The main components are shown in the following.
Fixed electrode
Fixed seal cup
Fixed shield
Contacts
Bellows shield
Arc shield
Ceramic
Bellows
Movable seal cup
The vacuum rate within the VI is very high(approximately 5x10-5 Torr) and the spacing between fixed contact and movable contact is about 6 ~ 20mm, depending on the voltage. The contacts are in a structure that arc can easily be extinguished and the surfaces of the contacts are made of special alloy (copper - chromium) and the interior is completely sealed to prevent loss of vacuum. Therefore the wearing of the contacts can be minimized in the event of short-circuit and the arc energy by overvoltage or switching can be reduced effectively.
H1-44
Basic functions and interrupting action Interrupting action by VI
In case of using the flat contact any of the designs do not reflect on when contacts are opening the arc with high temperature is contracted and fixed in the center of the contacts, Which is called pinch effect. To prevent the effect two kinds of contact shapes are designed. One is Axial magnetic field which spreads the arc before its contraction, and the other is Radial magnetic field which permits the contraction of the arc but makes it rotated to disperse the energy. Because contracted arc is shaped like a cylinder it is called Contracted arc or columnar arc. Arc voltage waveforms and arc image captured during arcing time
Spiral contact structure (Radial magnetic field ), using the force (F = j ×B) generated by the interaction of the radial magnetic field caused by the current flowing through the arc between two contacts, disperse the arc energy evenly on the surface of contact by rotating the arc that is contracted by the pinch effect so as to minimize contact damage. The images show arc behavior during the arcing time of about 8ms by shooting with high-speed camera capable of shooting 10,000 frames per sec. (0.1ms/frame) by focusing on parts of the arcing time on the above graph and simultaneously measured arc voltage also represented to show arc state by section
Radial magnetic field type contact
Direction of rotating arc
Columnar arc Current
Arc driving principle in the contacts of Radial magnetic field
H1-45
Vacuum Interrupter
Number[ops.]
Number[ops.]
VI endurance by interrupting current
Interrupting current [kA]
Interrupting current [kA]
VI model LV2 at 7.2kV
VI model LV3 at 7.2kV �N : Operation numbers �I : Interrupting current
Number[ops.]
Number[ops.]
�N : Operation numbers �I : Interrupting current
Interrupting current [kA]
Interrupting current [kA]
VI model LV4 at 24kV �N : Operation numbers �I : Interrupting current
H1-46
VI model LV5 at 17.5kV �N : Operation numbers �I : Interrupting current
Number[ops.]
Number[ops.]
Interrupting current [kA]
Interrupting current [kA]
VI model LV8 at 17.5kV
VI model LV7-P1 at 24kV �N : Operation numbers �I : Interrupting current
Number[ops.]
�N : Operation numbers �I : Interrupting current
Interrupting current [kA]
VI model LV8 at 36kV �N : Operation numbers �I : Interrupting current
Note) 1. Above graphs represent the characteristics of the electrical life of LS Susol VCB. 2. Life characteristics of each model in each rating represents the LOG-LOG graphs.
H1-47
Vacuum Interrupter Dimensions LV4
0 17 -0.3
LV3
0 17-0.3
0 21-0.3
LV2
LV5A
LV8
6 +0.1 0
5.2+0.1 0
LV5-P
20 +0.5 0
30 +0.5 0
30 +0.3 0
0 -0.1
+0.1 0
H1-48
+0.1 0
LV7-C
LV10404
6 +0.1 0
LV7-P1 / LV8-P
30 +0.5 0
0 -0.1
30 +0.3 0
0 -0.1
× 90
O
+0.1 0
4
H1-49
Vacuum Interrupter Technical data Type
LV2
LV3
LV4-E
LV5-P
7.2 7.2
24/25.8
12/17.5
(kV, rms)
20 20
50
42
(kV, crest)
60 60
135
95
50/60
50/60
630
630/1250
Outer view
Rated voltage
(kV)
Electrical ratings
Rated power frequency withstand voltage Rated impulse withstand voltage Rated frequency
(Hz)
Rated normal current
(Amp)
Rated short circuit current
8
(kA, peak)
20.8
Rated duration of short-circuit
Mechanical data
400/630 630/1250
(Sym.) (kA)
Rated short circuit making current
Mechanical requirements
50/60 50/60
(sec)
12.5 20 32.5
25 52
16
65 41.6
33
20
25
52
65
3
3
Interrupter weight
(kg)
0.8
Moving part weight
(kg)
0.3 0.7
0.5
0.7
a
132 158
208
220
b
91 105
159
163
c
62 80
62
90
Outline dimension (mm)
Contact stroke
(mm)
Opening speed, average 0 to 75% of full stroke
(m/s)
Overtravel during opening, Max.
(mm)
Closing speed, average last 33% of full stroke
(m/s)
Contact bounce duration, Max.
(sec)
6±1 10 0 7~1.0
0 7~1.0
80 154
Contact force from atmospheric pressure
(kg∙f)
8.5 12.6
Mechanical life
H1-50
(mm)
0 7~1.0
0 7~1.0
22
(kg∙f)
(×10 4, Operations)
±1 12
22
Added force from atmospheric pressure
Contact erosion limit
1.4 1.2
33 M2 M2
227
2.4
±1
10±1
1.3~1.5
0.7~1.0
2
2
0 7~1.0
0.7~1.0
2
2
120
154
227
9
12.6
3
3
M2
M2
LV5A
LV7-P1
LV7-C
LV8
LV8-P
40.5 17.5
12/17.5 24/25.8
LV10404
36
7.2/12
25.8
42 65
95 38
70
20/28
70
95 125
185 95
170
60/75
150
50/60 50/60 2500
2000
~3150
20
25
25
31.5 40
52
65
65
81.9
104
50/60 50/60
50/60
~3150 ~3150
~3150
50/60 4000
3150
25
31.5
40
50
25
31.5
40
40
50
40
65
81.9
104
130
65
81.9
104
104
130
104
44
34
4
4
3
3.0
7.3
9.8 6.6
7.3
8.7
1.0
2.2
2.6 2.2
2.2
2.0
390 272
272
317
220 272 160
216
329 210
216
210
80
145
145 135
145
135
10±1 12
17~19 12
±1
0.7~1.0
10±1 17
1.3~1.5 1.0~1.3
1.0~1.3
22
22
0.7~1.0 0.7~1.0
0.7~1.0 0.7~1.0
22
22 154
±1 17~19
227 12.6 25.5 33 M2 M2
227
306 367
227
306 25.1 25.8 33 M2 M2
367
460
227
1.3~1.5
1.0~1.3
2
1.5
0.7~1.0
0.7~1.0
2
2
306
367
367
406
25
25.8
3
3
M2
M2
±1
367
H1-51
Pro-MEC MCSG
VCB
Vacuum Circuit Breaker for MCSG Features and Structure
Contents
H2
H2-2
Control circuit diagram
H2-4
Dimensions
H2-5
Vacuum Circuit Breaker for MCSG Features and Structure Features �Module type VCB �Convenient especially for fabricating MCSG - Housing is designed like VCB compartment style - MCSG panel can be easily constructed if combined with Low voltage compartment, Busbar compartment and Cable compartment.
�Convenient for maintenance and offering high safely - Earthing switch can be operated from outside of the panel, and which makes earthing of 3 phases at the same time. - Without opening the compartment panel door, breaker can be drawn in or out electrically or manually
�Main functions - Breaker : draw- in or out electrically or manually - Compartment : 3-positions
�Standard - IEC 62271-100
① Name plate ② Manual closing button ③ Keylock ④ Manual trip button ⑤ Manual charging hole ⑥ Contact position indicator ⑦ Closing spring
⑦ ②
charge indicator ⑤
③
⑧ Operation counter ⑨ Insertion &
④
⑧
⑥
Draw-out screw
①
⑩ Geared Mechanism
⑨ ⑩
Electrical drive unit
Compartment
H2-2
Earthing switch
Bushings
Shutter
Ratings Type
‐25□ □-25□ □/06 LVB‐
Rated voltage (kV) Rated normal current (A) Rated frequency (Hz) Rated short-circuit breaking current (kA) Rated short-circuit breaking capacity (MVA) Rated short-time withstand current (kA) Rated short-circuit making current (kA) Rated breaking time (Cycles) Withstand Power frequency (kV) ×50㎲ ) voltage Impulse (kV/1.2× TRV rising rate (kV/㎲ ) TRV max. (kV) Rated operating sequence Mechanical lifetime Electrical lifetime Rated control voltage (V) Rated trip voltage( V) Standard auxiliary switch Rated opening time (s) No-load closing time (s) Rated charging motor current (A) Rated closing coil current (A) Rated trip coil current (A) Closing spring charging time (s) Draw-in/out motor voltage (V) Draw-in/out motor current (A) Distance between phases (mm) breaker Weight (kg) compartment Installing Applied standard
‐25□ □-25□ □/20 LVB‐ 25.8
630 2000
60 25 1100 25/3s 65 3 50/1min 125 0.47 41 O-0.3s-CO-3min-CO 10,000operations 10,000operations DC 110V DC 110V 4a4b, 8a8b ≤ 0.04 ≤ 0.06 ≤7 ≤5 ≤5 ≤ 12 DC 110V ≤5 265
205 281 293
236.5
G IEC 62271-100
�Breaker
LVB
25
G
25
Installation method
LS VCB
06
1A
2B
Control voltage
Version
B,C,D Accessories
1A DC110V
B Position Switch
1B DC220V
C1 Button Padlock(ON)
1C DC48V
C2 Button Padlock(OFF)
1E DC125V
C3 Button Padlock(ON/OFF)
1F AC220(M), DC110(TC)
D1 Button Cover(ON)
Breaking current
1H AC220(M), DC220(TC)
D2 Button Cover(OFF)
25
1T AC110(M), DC110(TC)
D3 Button Cover(ON/OFF)
G
Gclass draw-out Rated current
Rated voltage 25
I
25.8kV
06
630A
20
2000A
25kA
E Button Padlock(ON)+Button Cover(OFF) F Button Padlock(OFF)+Button Cover(ON)
Auxiliary switch 2G 4a4b(B type connector)
G Key Lock
2H 8a8b(B type connector)
H Secondary Trip Coil
�Cradle(Compartment)
LCL LS VCB
25
C
13
D
06
Rated voltage
Installation method
Breaking current
Version
Rated current
25
25.8kV
C
Bushing
25
25kA
06
630A
20
2000A
A,B,C Accessories B Earthing Switch E Door
H2-3 3
H2-4
A2
6
M
5
LS2 3 4
A1
10
9
1 2
30 31
1 5
1 3 2 4
4
Ya
8
7
Y
6
4
CLOSING POWER SOURCE
N
52a
2
A6
TC
1
6'
6
CS A5
N
P
Indication for closing spring "charged" is available.
A4
1 2
C
3
52b
Yb
LS1
LS3
CS A3
P
TRIP POWER SOURCE
MOTOR POWER SOURCE
LS6
2 2
3 3
4 4
5
6
7
8
9
36 37 38 39 B
C
10 11 12 13 14 15 16 9 10 D
2 2
3 3
4 4
5
6
7
8
9
36 37 38 39 B
A A1 A2 A3 A4 A5 A6 22 23 24 25 26 27 28 29 40 41 A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ( 8a 8b ) SECONDARY DISCONNECT WIRING ( TOP VIEW )
B 13 14 15 16 17 42 43 44 45 46 47
C
10 11 12 13 14 15 16 9 10 D
C 50 51 52 53 54 55 56 57 58 59 70 71
1 D 1
A A1 A2 A3 A4 A5 A6 22 23 24 25 26 27 28 29 A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ( 4a 4b )
B 13 14 15 16 17
C 50 51 52 53
1 D 1
35
52b
9 34
89Y
22 8
89X
LS5
9
89Y
1 2 21
89X
89X
22 8
2 21
1
44
43
15
13
14
CCW (인출)
CW (인입)
Note. Diagram shows the circuit breaker in position“OFF”with closing spring“Charged”
N
P
34
33
44
43
16
89Y 34
33
2
13
89X
14
89X
89M
1
14
89Y 13
17
89Y
P
37 39 51 53 55 57 59 71
37 39 51 53 55 57 59 71
36 38 50 52 54 56 58 70 PS1
2
2
1 PS2
4
3
4
3
Run
Position S/W Test 1
∅ : External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil TC1 : Secondary trip coil C : Closing coil Y : Anti-pump relay 52a : Auxiliary switch (NO) 52b : Auxiliary switch (NC) LS1 : Closing interlock limit switch(only withdrawable type) LS2 : Motor stopping, closing spring charged indication LS3 : Anti-closing, Anti-pumping limit switch LS5 : "Off" at Test Position LS6 : "Off" at Run Position PS1 : Position S/W("On" at Test Position) PS2 : Position S/W("On" at Run Position) 89X : Auxiliary Relay for Inserting 89Y : Auxiliary Relay for withdrawing 89M : Motor for withdrawing and Inserting
23 25 27 29 41 43 45 47
23 25 27 29 41 43 45 47
22 24 26 28 40 42 44 46
4b
8b
36 38 50 52 54 56 58 70
Auxiliary switch
22 24 26 28 40 42 44 46
4a
8a
Vacuum Circuit Breaker for MCSG
Control circuit diagram
Dimensions Cradle(Compartment) - w/o Earthing Switch
894 1000
410
�Top
963
553
1
30 86 340
190
86 265 175 (Earthing) ∅6.5
45
1
53
425
652.4
95
183.4
(212.4)
(183.4)
53
A
265
RUN
35
15.4
B TEST
60
30
265 B
2-∅13
95
1082
265
3-∅10 1365
1365
26.8
60 425
st:310
425
10
C
45
263.8
70 103 75
A
�Rear
293.8
180
372.6
Lead wire (2m)
340
�Front
968 1000
Earthing
410 65
3-∅11 (Mounting Hole)
3-∅11×22 (Mounting Hole)
513
16.8
128 50
40
700
370
700 175 103
20
600 950
265
205
User Bus
844
20-M8 POP NUT (DP:18)
50
340
40
963
483
50
15
(15)
933
G type breaker + track(electric draw-in/out) 630A 265
445
265
445
608
340
1013
340
2000A
860 886 912
350 481
50 785
H2-5
Vacuum Circuit Breaker for MCSG Dimensions Cradle(Compartment) - w/ Earthing Switch
�Side
35
238.8
125
25t(2000A) 10t(630/1250A) st:310 Run
Test 340
74
500
1750
36
39
963
�Top
415
320.9
968
60
2-∅13 26
17
25
26
83
9-∅11Mounting Hole 15
∅19
700 950
17
20-M8 POP NUT (DP:18)
50
140 150
26
25
H2-6
340
40
483
50
60 70
50
340
65
16.8
83
513
600
40
26
20 370
100
763
454
265
265 45
35
(Earthing S/W) **Option
244
125 A
175
415
B
265
(Earthing) ∅6.5
M12 TAP (DP:24)
500
Test
265 767.4
User Bus
1000
3-∅10 415
(Door) **Option
190
500
Test
45
35
A
�Rear 10-M8 POP NUT (DP:18)
415
16-∅10 (Mounting Hole Side)
398.6
�Front
100
Power Plants
VCB
Vacuum Circuit Breaker for Power Plants
Contents
H3
Ratings
H3-4
Ratings of Accessories
H3-5
Accessories
H3-6
Control circuit diagram
H3-8
Dimensions H3-9 Types and ordering information
H3-14
Vacuum Circuit Breaker Power Plants A product developed for water and thermal power plants due to the revision and application of Kepco’s standard (ES150) followed by the IEC standard revision. It has completed the high capacity (40~50kA) VCB series for power plants by securing higher breaking capacity, safety and reliability.
VCB Full Option To prevent fatal error, property and life loss caused from operator during operation, it is equipped with safety mechanisms such as shutter padlock.
Bushing applied for Window CT adaptation The bushing provides sufficient strength to collaborate with the internal insulation and is adaptable with CT offering safety mechanically and electrically when applying large current.
H3-2
Vacuum Circuit Breakers for Power Plants
It is recognized for reliability by acquiring new IEC 62271-100 and ES150 (KEPCO standard specification on AC breakers)
H3-3
Vacuum Circuit Breaker for Power Plants Ratings Type
LVB-06G-40H
Rated voltage
LVB-06G-40J
(kV)
Rated normal current
(A)
Rated frequency
LVB-06G-50J
7.2 1200
2000
3000
1250
(Hz)
2000
2500
3150
1250
2000
60
Rated short-circuit breaking current (kA)
40
50
Rated short-circuit breaking capacity (MVA)
500
624
Rated short-time withstand current (kA/3sec)
40
50
Rated short-circuit making current (kAp)
104
130
Rated breaking time
(Cycle)
Rated opening time
(sec)
≤ 0.04
No-load closing time
(sec)
≤ 0.06
Withstand
Power frequency
voltage
Impulse (kV/1.2
3
(kV/min)
20
×50㎲ )
60
Rated operating sequence
CO-15s-CO
O-0.3s-CO-3min-CO
Rated charging motor current
(A)
5 (at DC125V)
5 (at DC110V)
Rated closing coil current
(A)
3 (at DC125V)
3 (at DC110V)
Rated shunt coil current
(A)
3 (at DC125V)
3 (at DC110V)
Type
Mechanical
test
Electrical
Lifetime
M2 E2 (Maintenance free)
E2 (List1)
Capacitive current switching
C2
Mechanical Without maintenance
10000 operations
Electrical
Maintenance
20000 operations
Without maintenance
10000 operations
Maintenance
20000 operations
Auxiliary switch Installing
3a3b
Draw-out G-type
Weight Breaker Cradle
G-type G-type (kg)
Visible, Tulip (kg)
200
260
200
260
200
260
190
230
190
230
190
230
Applied standard Type test laboratory Note) ES150: KEPCO's standard in which IEC62271-100 is applied KERI: Korea Electrotechnology Research Institute
H3-4
3150
IEC 62271-100
ES150 NOTE) KERI
Ratings and auxiliary devices Motor When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w. The peak value of the
Rated voltage
inrush current (A)
Consumption power (W)
Rated current (A)
Charging time (Sec.)
DC 110V
20
3
330
12
DC 125V
20
3
330
12
Note) Range of the normal operating voltage: 85~110% of rated voltage
Closing Coil (C)
Shunt coil (TC)
When the rated volt is applied to the coil the breaker is closed. The electrical anti-pumping circuit is built-in it.
When the rated volt is applied to the coil the breaker is opened.
Rated voltage
Rated current (A)
Rated voltage
Rated current (A)
DC 110V
3
DC 110V
3
DC 125V
3
DC 125V
3
Note) Range of the normal operating voltage: 75~125% of rated voltage
Note) Range of the normal operating voltage: 60~125% of rated voltage
Auxiliary switch Standard configuration : 3a3b1b of early-b contact function exists inside Resistive load (A)
Classification Contact Ratings
DC
Inductive load (A)
110V 10
5
125V 10
5
Contact configuration 3a3b
Position of the Auxiliary switch Switch Breaker a RUN
Note) The contact ratings of Mechanical Operated Cell Switch(MOC) are the same with that of the Aux. switch.
TEST
Truck Operated Cell Switch(TOC) Resistive load (A)
Classification Contact Ratings
DC
Inductive load (A)
110V 10
5
125V 10
5
Contact configuration
Mechanism b
MOC
TOC
a
b
a
b
CLOSE
ON OFF
ON
OFF
ON
OFF
OPEN
OFF ON
OFF
ON
OFF
ON
CLOSE
ON
ON * OFF * ON OFF
OPEN
OFF ON
OFF
OFF * ON * OFF ON
Note) * applied in the VCB of which MOC is operable at the TEST position.
3a3b
Charge indicator of the closing spring
Position indicator of the main contacts
Indicating the condition of the closing spring.
Indicating the 'Close' or the 'Open' of the main contacts. � Open position:�OFF� � Close position:�ON�
Charged
Discharged Close position
Open position
Counter Mechanically counts the operation of the VCB by 5digits
H3-5
Vacuum Circuit Breaker for Power Plants Accessories Accessories for breakers �Position padlock It is located at the screw hole to prevent the draw-in and out of a breaker from the present position(Disconnected, Test or Connected)
�Mechanical position indicator It is located in the lower part of a breaker to check the present position Disconnected, Test or Connected- easily.
�Position interlock The breaker is locked in each position-Disconnected, Test or Connected, thus it is necessory to release the lock before draw-in or out of a breaker from the present position.
�Auto connection When the breaker is moved to Test position from Disconnected position the connector for control powers is automatically connected. In case of reverse moving of the breaker the connector is automatically disconnected.
�Code plate When the breaker is inserted to the cradle, if the ratings does not match with the cradle, it mechanically prevents the breaker from being inserted into the cradle.
H3-6
Accessories for breakers �Mechanically operated cell switch (MOC) It is auxiliary switch (6a6b), which indicates the 'ON' or 'OFF' condition of a VCB, and operated when the VCB is in 'Run' state.
�Truck operated cell switch (TOC) It is auxiliary switch (6a6b), which indicates the 'Run' state of a VCB and is operated by the movement of a VCB frame.
H3-7
H3-8
B
A
7 23 25 27 29 41
22 23 24
N
P
A2
2
∅ 52 M TC C Y 52a 52b LS1 LS2 LS3 LS4
: : : : : : : : : : : :
External terminal of VCB Vacuum circuit breaker Spring charging motor Trip coil Closing coil Anti-pump relay Auxiliary switch (NO) Auxiliary switch (NC) Closing interlock limit switch Motor stopping Anti-closing, Anti-pumping limit switch Motor Charging interlock limit switch
LS1
A4
2
1
4
1
6
C
1 3 2 4 1 Yb 5 52b 30 31 3
LS3
CS A3
M
5
3 4
LS4
LS2
A1
Note) Diagram shows the circuit breaker in position“OFF”with closing spring“Charged”
6 22 24 26 28 40
12 13 14
31 35 37 39 51 53
25 26 27
30 34 36 38 50 52
15 16 17
22 23 24
12 13 14
25 26 27
15 16 17
8
7
Y
4 Ya 6
Cell switch in service position
MOTOR POWER SOURCE
N
P
52a
A6
TC
2
1
7
6
25
56 57
B
27
27
26
54 55 58 59
24
4
5
6
12
10 11
3
9
22 23
54 56 58 2
7 8
21
1
18 19 20
55
55
54
54
A1 A3 A5 22 24 26
16 17
(12P TAP PLUG)
A
A1 A3 A5 A2 A4 A6 22 24 26 23 25 27
23
25
24
26
Auxiliary switch
55 57 59
14 15
N
23
22
22
3a 24
A2 A4 A6 23 25 27
13
TRIP POWER SOURCE
57
59
59
58
58
Early b
57
56
3b 56
SECONDARY DISCONNECT WIRING (FRONT VIEW OF RECEPTACLE PLUG)
CS A5
P
Vacuum Circuit Breaker for Power Plants
Control circuit diagram
CLOSING POWER SOURCE
Dimensions - Breakers LVB-06G-40H, 40J G class (Visible, Tulip contact)-(1200, 1250, 2000A) �Side 336
368.2
351.3
130
815.2
360
722
54(male conductor)
�Front
(unit : mm)
10
60
696
686.2
717
�Top 254
685.2
532
584
254
1200/1250/2000A 745
H3-9
Vacuum Circuit Breaker for Power Plants Dimensions - Breakers LVB-06G-40H, 40J G class (Visible, Tulip contact)-(2500, 3000, 3150A) �Side 336
349.8
130
815.2
360
722
79(male conductor)
�Front
10
368.2
60
696
686.2
717
�Top
685.2
584
254
532
254
2500/3000/3150A 745
H3-10
(unit : mm)
Heat sink (only for 3150A)
LVB-06G-50J G class (Visible, Tulip contact)-(1250, 2000A) �Side
54(male conductor)
�Front
(unit : mm)
722 115.5
336
140
Moving contact
368.2
60 10
341.3
403.8
815.7
130
360
Fixed contact
696
677.2
717
�Top
584
532
676.2
254
254
745
H3-11
Vacuum Circuit Breaker for Power Plants Dimensions - Breakers LVB-06G-50J G class (Visible, Tulip contact)-(3150A) �Side
722 115.5
79(male conductor)
�Front
(unit : mm)
336
140
358.7
815.7
150.2
267.8
341.8
136.5
130
107
360
Moving contact
541 677.2
717
�Top
H3-12
676.2
584
254
532
254
10
445.8 696
Fixed contact
Cradles
374
252 50
35
150
500
361
∅79 ∅148
∅14 (Earthing)
123
816 776 103.5 175
140
2500/3000/3150A 252
240
∅54
∅148
235.5
36
436.5 140
Mounting 6-∅12
544
123
Autocon(3a3b) M.O.C(6a6b)
1200/1250/2000A
449.5 151.5
61
644
59 61(레일폭)
1035
360
338
T.O.C(6a6b)
75.8
310
254
374 35
∅218
2-M12 DP20
254
50
310
1134
240
∅218
4-M12 DP20
(unit : mm)
1038.5
H3-13
Vacuum Circuit Breaker for Power Plants Types and ordering information Breaker
LVB LS VCB
06
G
40
J
Installation method G
G class draw-out
12
1A
2L
P3,Q,R
Control voltage
Standard H
ESB150
1A
DC110V
J
IEC
1B
DC220V
C1 Button padlock(ON)
1E
DC125V
C2 Button padlock(OFF)
Option
C3 Button padlock(ON/OFF) D1 Button Cover(ON) Rated voltage 06
7.2kV
Breaking current
NOTE2)
Auxiliary switch
Rated current
40
40kA
12
1200/1250A
50
50kA
20
2000A
25
2500A
30
3000/3150A
2L
3a3b(Autocon)
D2 Button Cover(OFF) D3 Button Cover(ON/OFF) E
NOTE1)
F
Button padlock(ON)+ Button cover(OFF) Button padlock(OFF)+ Button cover(ON)
G Key Lock P3 Dummy VCB
Note) 1.Rated current 2500A is available only at 7.2kV 40kA, IEC version(J) 2.Control voltage and Auxiliary switch are not applied to Dummy VCB and Earthing Truck
Q Earthing Truck(lower terminal) R Earthing Truck(upper terminal)
Cradle
LCL
06
G
LS Cradle
40
J
Installation method G
G class draw-out
12
A1, A2
standard H
ESB150
J
IEC
Option MOC(6a6b)+TOC(6a6b) A1
MOC active only at RUN position MOC(6a6b)+TOC(6a6b)
A2 Rated voltage 06
H3-14
7.2kV
Rated current
Breaking current 40
40kV
12
1200/1250A
50
50kV
20
2000A
25
2500A
30
3000/3150A
MOC active only at TEST and RUN position
Nuclear Power Plants
VCB
Vacuum Circuit Breaker for Nuclear Power Plants
Contents
H4
Ratings
H4-4
Ratings of Accessories
H4-5
Accessories
H4-6
Control circuit diagram
H4-8
Dimensions
H4-9
Types and ordering information
H4-11
Vacuum Circuit Breaker Nuclear Power Plants It was developed for KEPCO nuclear power stations. This breaker satisfies quality, safety measures (secure from earthquake and other environments), and surge protection class complies with “1E-CLASS” ±provisions. It is featured with high breaking technologies, safety, and reliability by applying our own vacuum interrupters (50KA) approved by ANSI standard tests.
H4-2
Vacuum Circuit Breakers for Nuclear Power Plants
VCB Full Option To prevent fatal error, property and life loss caused from operator during operation, it is equipped with safety mechanisms such as shutter padlock.
Bushing applied for Window CT adaptation The bushing provides sufficient strength to collaborate with the internal insulation and is adaptable with CT offering safety mechanically and electrically when applying large current.
Satisfies earthquake and other internal environment specifications During the lifespan of power stations (40yrs), it is designed to operate its fundamental breaking functions even under the most severe conditions like earthquake, which is critical from safety perspectives. These technologies proven through tests that comply with KEPIC standard and relevant specifications are to guarantee nuclear reactor safety. H4-3
Vacuum Circuit Breaker for Nuclear Power Plants Ratings Type Rated voltage
(kV)
Rated normal current
(A)
LVB-05G-50B
LVB-15G-40B
4.76
15
1200
1200
2000
2000
3000
-
Rated frequency
(Hz)
60
60
Rated short-circuit breaking current
(kA)
50
40
(MVA)
410
1040
Rated short-time withstand current
(kA/3sec)
50
40
Rated short-circuit making current
(kA)
130
104
3
3
Rated short-circuit breaking capacity
Rated breaking time
(Cycle)
Rated opening time
(sec)
≤ 0.04
≤ 0.04
No-load closing time
(sec)
≤ 0.06
≤ 0.06
(kV/1min)
19
36
× 50㎲ ) (kV/1.2×
60
95
Withstand
Power frequency
voltage
Impulse
Rated operating sequence
0-0.3s-CO-3min-CO
Rated charging motor current
DC 125V
(A)
5
5
Rated closing coil current
DC 125V
(A)
3
3
Rated shunt coil current
DC 125V
(A)
3
3
Mechanical(w/o maintenance)
10000 operations
10000
Electrical(w/o maintenance)
10000 operations
10000
5a3b
5a3b
G-type
G-type
Lifetime
Auxiliary switch Installing
Weight
Applied standard Type test laboratory
H4-4
1200,2000A
(kg)
300
300
3000A
(kg)
350
-
ANSI C37
ANSI C37
KERI
KERI
Ratings of Accessories Motor When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
Rated voltage
The peak value of the inrush current (A)
Ratedcurrent(A)
4.76kV
15kV
4.76kV
15kV
50kA
40kA
50kA
40kA
15
15
5
5
DC 125V
Range of the normal operating voltage
Consumption power (W)
Charging time (sec)
90~140
360
8
Closing Coil (C)
Shunt Coil (TC)
When the rated volt is applied to the coil the breaker is closed. The electrical anti-pumping circuit is built-in it.
When the rated volt is applied to the coil the breaker is opened.
Rated voltage
The peak value of the inrush current (A) 4.76kV
15kV
50kA
40kA
3
3
DC 125V
Range of the normal operating voltage
Rated voltage
90 ~ 140
The peak value of the inrush current (A) 4.76kV
15kV
50kA
40kA
3
3
DC 125V
Range of the normal operating voltage
70 ~ 140
Auxiliary switch Standard configuration : Reversible 8C(5a3b) and 2c(2b) with early-b contact function Resistive load(A)
Inductive load(A)
250V
10
5
125V
10
5
Classification AC Contact Ratings DC
Position of the Auxiliary switch
250V
10
5
125V
10
5
30V
10
5
Contact configuration
Switch Breaker RUN
8c
TEST
Mechanism a
b
MOC ab
TOC ab
CLOSE
ON OFF
ON
OPEN
OFF
ON
OFF ON
CLOSE
ON
OFF
ON OFF
ON OFF
OPEN
OFF
ON
OFF ON
OFF ON
OFF
ON
OFF
OFF ON
Note) The contact ratings of Mechanical Operated Cell Switch(MOC) are the same with that of the Aux. switch.
Charge indicator of the closing spring
Position indicator of the main contacts
Indicating the condition of the closing spring.
Indicating the 'Close' or the 'Open' of the main contacts. � Open position:�OFF� � Close position:�ON�
Charged
Discharged Close position
Open position
Counter Mechanically counts the operation of the VCB by 5digits
H4-5
Vacuum Circuit Breaker for Nuclear Power Plants Accessories Accessories for breakers �Position padlock It is located at the screw hole to prevent the draw-in and out of a breaker from the present position(Disconnected, Test or Connected)
�Mechanical position indicator It is located in the lower part of a breaker to check the present position Disconnected, Test or Connected- easily.
�Auto connection When the breaker is moved to Test position from Disconnected position the connector for control powers is automatically connected. In case of reverse moving of the breaker the connector is automatically disconnected.
�Reversible contact 10 auxiliary switches are provided. 8 of them consist of reversible 8c which can be changed from a(b) to b(a). Factory composition is 5a3b. And the other 2 switches are supplied as 2b with early-b contact function
�Code plate When the breaker is inserted to the cradle, if the ratings does not match with the cradle, it mechanically prevents the breaker from being inserted into the cradle.
�Auto discharge In case the breaker is drawn-out when the closing spring is charged in the position-Disconnected, Test or Connected, or the breaker is moved to Disconnected position from Test position the closing spring shall be automatically released.
H4-6
Accessories for cradles �Mechanically operated cell switch (MOC) This 6a6b switch indicates the 'ON' or 'OFF' condition of a VCB and is operated in the positions of 'Run' and 'Test"..
�Truck operated cell switch (TOC) This 6a6b switch indicates the 'Run' state of a VCB and is operated by the movement of a VCB frame.
H4-7
H4-8
A2
6
M
5
4
LS2 3
A1
Yb
4
LS1
4
2 1
31
5 30
3
1
A4
2
1
C
3
52b
LS3
A3
CS
8
Y
7
4 Ya 6
CLOSING POWER SOURCE
MOTOR POWER SOUREC
N
P
Note) Diagram shows the circuit breaker in position“OFF”with closing spring“Charged”
∅ : External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil C : Closing coil Y : Anti-pump relay 52a : Auxiliary switch (NO) 52b : Auxiliary switch (NC) LS1 : Closing interlock limit switch (only withdrawable type) LS2 : Motor stopping, closing spring charged indication LS3 : Anti-closing, Anti-pumping limit switch
N
P
52a
2
A6
TC
1
6’
6
A5
CS
N
P
24
26
5a 28
40
23
18
19
20
1
22
4
5
6
7
8
10
58
24
11
12
56 58
57 59
23
55
57
early b
59
42 55 44 57 46 59
SECONDARY DISCONNECT WIRING
3
3b 56
43 54 45 56 47 58
54
(FRONT VIEW OF RECEPTACLE PLUG)
2
9
21
54
16 17
41
A1 A3 A5 22 24 26 28 40
15
29
55
14
27
A2 A4 A6 23 25 27 29 41
13
25
23 34 25 36 27 38 29 50 41 52
22 35 24 37 26 39 28 51 40 53
22
Auxiliary switch
Vacuum Circuit Breaker for Nuclear Power Plants
Control circuit diagram
TRIP POWER SOURCE
Dimensions Breaker 722 254
254
722 745
228
369
816
817
228
360
109
360
109
3000A
86.5 109.5
442.5 713
1200/2000A
H4-9
Vacuum Circuit Breaker for Nuclear Power Plants Dimensions Cradle 936 254
254
644 850
137
100
343
252
203 36
310
213
1070
360
4-M12 DP18 2-M12 DP24
449
1200/2000A
157
50
195
630 1020
H4-10
3000A
2-M12 DP24
Types and ordering information Breaker
LVB
05
G
40
B
G
G class draw-out
1A
B
2K
1
Control voltage Note)
Version
Installation method
LS VCB
20
Pro-MEC
Nuclear class
1A
DC110V
1
1E class
1B
DC220V
2
Non 1E class
1C
DC48V
1E
DC125V
Note) 1A,1B,1C are only available at 15kV class
Rated voltage 05
4.76kV
15
15kV
40 50
Auxiliary switch
Rated current
Breaking current 40kA
12
1200A
50kA
20
2000A
30
3000A
2K
8c 접점
Cradle
LCL
05
G
40
B
Installation method
LS Cradle G
G class draw-out
1
Nuclear class
Version B
Pro-MEC
1
1E class
2
Non 1E class
Rated current
Breaking current
Rated voltage
20
05
4.76kV
40
40kA
12
15
15kV
50
50kA
20
2000A
30
3000A
1200A
H4-11
Memo
H4-12
� For your safety, please read user's manual thoroughly before operating. � Contact the nearest authorized service facility for examination, repair, or adjustment. � Please contact a qualified service technician when you need maintenance. Do not disassemble or repair by yourself!
Safety Instructions
� Any maintenance and inspection shall be performed by the personnel having expertise concerned.
ⓒ 2008.11 LSIS Co.,Ltd. All rights reserved.
� HEAD OFFICE
Korea Gyeonggi-do Anyang-si dongan-gu LS-ro 127 (Hogye-dong) Tel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648
� CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea
www.lsis.biz
� Global Network �LSIS (Middle East) FZE � �Dubai, U.A.E.
Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: [email protected]
�Dalian LSIS Co., Ltd. � �Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: [email protected]
�LSIS (Wuxi) Co., Ltd. � �Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: [email protected]
�LSIS-VINA Co., Ltd. � �Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected]
�LSIS-VINA Co., Ltd. � �Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: [email protected]
�LSIS Shanghai Office � �Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: [email protected]
�LSIS Beijing Office � �Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: [email protected]
�LSIS Guangzhou Office � �Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: [email protected]
�LSIS Chengdu Office � �Chengdu, China
Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: [email protected]
�LSIS Qingdao Office � �Qingdao, China
Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: [email protected]
�LSIS NETHERLANDS Co.Ltd � �Qingdao, Netherlands
Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: [email protected]
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.
2011. 10
�LSIS Gurgaon Office � �Gurgaon ,India
Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, India
Vacuum Circuit Breakers/Vacuum Interrupter(E) 2008. 11/(05) 2011. 10 Printed in Korea
STAFF