VSS, B3L, B6

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN 3 Piping Sizing Geometry Ball Valves LINE SIZE VALVE SIZE Cv TYPE MODEL # ...

9 downloads 597 Views 2MB Size
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Ball Valve Features and Benefits B2...VS/VSS, B3...L, B6...VS

● 2-way and 3-way configuration

● NPT and flanged connections

● Bronze with stainless steel trim (2-way)

● Wide Cv range

● Nickel plated brass body (3-way)

● Air gap for use with hot water and steam systems

● Reduced and full port capacities

● Live load low maintenance stem packing

● Two piece construction

● 2 year warranty

● Electronic actuation

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

1

Flow Pattern, Operation and Installation Ball Valves FLOW PATTERN

Open CCW

Flow Direction

B to A Open CW

Closed CW

B to AB Open CCW

NOTE: B3…L are piped differently than B3 CCV Valves.

VS SERIES BALL VALVE PIPING DIAGRAMS 2-way Valve Piping Diagram

3-way Diverting Valve Piping Diagram

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

NOTE: To avoid torque increase during off season shut down, or other periods of inactivity longer than 1 month - the valve should be exercised (actuator or manually driven full open-closed cycle) at least once per month. This is necessary to avoid any application problems after an off season shut down.

PIPING/MOUNTING ORIENTATION Assembly can be mounted horizontally or vertically for water applications. For steam applications the valve can be mounted vertically but if mounted horizontally the valve must be 90° off center of the pipe. Do not install with actuator below pipe.

(Water application only)

(Steam or water application)

800-543-9038 USA

2

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Piping Sizing Geometry Ball Valves

Cv

TYPE

MODEL #

¾” Fp Cv

1 2 4 15 30 51 43 68 48 84 177 108 389 503 370 6.4 12.8 11 34 57 87 330 420 600 1200 3300 9000 12400

2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 3W NPT 3W NPT 3W NPT 3W NPT 3W NPT 3W NPT 2W FLG 2W FLG 2W FLG 2W FLG 2W FLG 2W FLG 2W FLG

B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B219VS/VSS B220VS B224VS/VSS B225VS B232VS/VSS B239VS/VSS B240VS B249VS/VSS B250VS B265VS/VSS B280VS/VSS B315L B320L B325L B332L B340L B350L B650VS B665VS B680VS B6100VS B6150VS B6200VS B6250VS

1.0 2.0 3.8 8.9 30.0 51.0 — — — — — — — — — 5.5 12.8 — — — — — — — — — — —

1” Fp Cv

1¼” Fp Cv

1½” Fp Cv

2” Fp Cv

LINE SIZE 2½” 3” Fp Cv Fp Cv

1.0 1.9 3.6 7.2 21.6 26.5 43.0 68.0 — — — — — — — 5.0 11.8 11.0 — — — — — — — — — —

— — — — 17.4 19.9 36.1 48.3 48.0 — — — — — — 4.8 11.0 10.9 34.0 — — — — — — — — —

— — — — 15.6 17.3 30.5 36.7 44.6 84.0 177.0 — — — — — 10.5 10.7 32.8 57.0 — — — — — — — —

— — — — — — 25.8 29.2 37.9 69.7 102.7 108.0 389.0 — — — — 10.4 29.9 51.9 87.0 330.0 — — — — — —

— — — — — — — — 35.0 59.6 77.9 100.4 221.7 503.0 — — — — 28.2 47.4 82.8 207.9 420.0 — — — — —

— — — — — — — — — 55.4 67.3 91.8 159.5 352.1 370.0 — — — — 44.9 77.9 155.1 319.2 600.0 — — — —

4” Fp Cv

5” Fp Cv

6” Fp Cv

— — — — — — — — — — — 83.2 124.5 221.3 296.0 — — — — — 72.3 122.1 214.2 384.0 1200.0 — — —

— — — — — — — — — — — — — 186.1 251.6 — — — — — — — 184.8 300.0 804.0 — — —

— — — — — — — — — — — — — — 229.4 — — — — — — — — 264.0 600.0 3300.0 — —

8” Fp Cv

10” Fp Cv

— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 480.0 — 1716.0 1254.0 9000.0 3870.0 — 12400.0

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

VALVE SIZE ½” ½” ½” ½” ¾” ¾” 1” 1” 1¼” 1½” 1½” 2” 2” 2½” 3” ½” ¾” 1” 1¼” 1½” 2” 2” 2½” 3” 4” 6” 8” 10”

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

3

Wiring Instructions Ball Valves GENERAL WIRING INSTRUCTIONS

Always read the controller manufacturer’s installation literature carefully before making any connections. Follow all instructions in this literature. If you have any questions, contact the controller manufacturer and/or Belimo. Transformer(s) Typically actuators require a 24 VAC class 2 transformer and draw a maximum of 10 VA per actuator. The actuator enclosure cannot be opened in the field, there are no parts or components to be replaced or repaired. – EMC directive: 89/336/EEC – Software class A: Mode of operation type 1 – Low voltage directive: 73/23/EEC Typical transformer sizing Actuator Series Voltage AF 24 LF 24 AR 24 NR 24 LR 24

Max. VA Per Actuator 10 6 6 4 3

CAUTION It is good practice to power electronic or digital controllers from a separate power transformer than that used for actuators or other end devices. The power supply design in our actuators and other end devices use half wave rectification. Some controllers use full wave rectification. When these two different types of power supplies are connected to the same power transformer and the DC commons are connected together, a short circuit is created across one of the diodes in the full wave power supply, damaging the controller. Only use a single power transformer to power the controller and actuator if you know the controller power supply uses half wave rectification. Multiple actuators, one transformer Multiple actuators may be powered from one transformer provided the following rules are followed: 1. The TOTAL current draw of the actuators (VA rating) is less than or equal to the rating of the transformer. 2. Polarity on the secondary of the transformer is strictly followed. This means that all No. 1 wires from all actuators are connected to the common leg on the transformer and all No. 2 wires from all actuators are connected to the hotleg. Mixing wire No. 1 & 2 on one leg of the transformer will result in erratic operation or failure of the actuator and/or controls. Multiple actuators, multiple transformers Multiple actuators positioned by the same control signal may be powered from multiple transformers provided the following rules are followed: 1. The transformers are properly sized. 2. All No. 1 wires from all actuators are tied together and tied to the negative leg of the control signal. See wiring diagram. Wire type and wire installation tips For most installations, 18 or 16 Ga. cable works well with Belimo actuators. Use code-approved wire nuts, terminal strips or solderless connectors where wires are joined. It is good practice to run control wires unspliced from the actuator to the controller. If splices are unavoidable, make sure the splice can be reached for possible maintenance. Tape and/or wire-tie the splice to reduce the possibility of the splice being inadvertently pulled apart. Wire length for actuator installation Keep power wire runs below the lengths listed in the following tables. If more than one actuator is powered from the same wire run, divide the allowable wire length by the number of actuators to determine the maximum run to any single actuator. See section 1 for specific transformer sizing information for the actuator selected. Example: 3 actuators, 16 Ga wire 350 Ft ÷ 3 Actuators = 117 Ft. Maximum wire run

800-543-9038 USA

4

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

WARNING The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment to the actuator must be made with flexible conduit.

Nomenclature Ball Valves B2

24

VS

AMX

Valve

Valve Size

B2 = 2-way B3 = 3-way B6 = 2-way Flanged

15-80 = ½” to 3” Construction/ 1-370 50-250 = 2” to Material 10” VS = Bronze Body, (Flanged) Stainless Steel Ball and Stem VSS = Stainless Steel Body, Ball and Stem L = Nickel Plated Brass Body, Chrome Plated Brass Ball and Stem

Industrial

24

-MFT-X1

Actuator Type Power Supply Control

Cv

Non-Spring Return 24 = 24 VAC/DC LM… 120 = 120 VAC NM… 230 = 230 VAC AM… GM… SY… SY…P Spring Return LF… NF… AF… Electronic Fail-Safe GK...

-3-X1 = On/Off, Floating Point -MFT-X1 = Multi-Function Technology -MFT95-X1 = 0-135 Ω

-S = Built-in Auxiliary Switch

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Ordering Example 3 1

For MFT orders only - select programming code

Choose the valve actuator combination.

B224VS+AMX24-MFT-X1

+NO

+Tagging (if needed) 4

2

Specify preference or configuration.

Does order require tagging?

Set-Up

P-10001 (A01)

Non-Spring Models NO = Normally Open NC = Normally Closed

P-100xx (Axx) P-200xx (Wxx)

Spring Return Models NO/FO = Normally Open/Fail Open NO/FC = Normally Open/Fail Closed NC/FO = Normally Closed/Fail Open NC/FC = Normally Closed/Fail Closed Refers to valve ports A to AB.

5

Complete Ordering Example:

800-543-9038 USA

P-300xx (Fxx) P-400xx (Jxx) X-XXXXX X-XXXXX

Control voltage applications Pulse width modulation applications Floating point applications On/off applications Create custom MFT configuration code Create custom MFT configuration in the field with MFT actuator PC software

Tagging: Valves may be tagged per customer specification. ($10.00 per tag) Example: AHU-1 FCU-2 Part number for tagging: 99981-00101

B224VS+AMX24-MFT-X1+NO+A01 866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

5

B2...VS Series, 2-way, Ball Valve Bronze Body, Stainless Steel Ball and Stem • Live-load packing set • Stainless steel ball & stem • Blow-out proof stem design

Application This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV Box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionality which facilitates the use of various control input.

½ ½ ½ ½ ¾ ¾ 1 1 1¼ 1½ 1½ 2 2 2½ 3

15 15 15 15 20 20 25 25 32 40 40 50 50 65 80

B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B219VS B220VS B224VS B225VS B232VS B239VS B240VS B249VS B250VS B265VS B280VS

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

1 2 4 15 30 51 43 68 48 84 177 108 389 503 370

LM Series

2-way NPT

NM

DN [mm]

AM Series

Inches

LF Series

Cv

Suitable Actuators Spring Non-Spring Return Return

10

Pressure rating Media temp. range Close-off pressure Maximum differential pressure (ΔP)

600 psig WOG -22°F to +280°F (-30°C to +138°C) 600 psig @ 100°F <600 psig

Flow Patterns

800-543-9038 USA

6

SY Series

Gland Stem Jam nut Body seal Body

Type

GM Series

6 7 8 9 10

reinforced PTFE reinforced PTFE 316 stainless steel reinforced PTFE w/ Durafill B16 (¾” - 1”) stainless steel B584 (1¼” - 3”) stainless steel B16 brass 316 stainless steel stainless steel PTFE (1-1/4” to 3”) B584-C84400 bronze

Valve Nominal Size

NF

Sizes Type of end fitting Materials: 1 Stem packing 2 Stem bearing 3 Ball 4 Seat (x2) 5 Retainer

chilled or hot water, glycol, 35# steam modified equal percentage 90° rotation valve open CW, valve closed CCW ½”, ¾”, 1”, 1¼”, 1½”, 2”, 2½”, 3” SAE NPT (female connections)

AF Series

Technical Data Media Flow characteristic Action

• Up to 35 psi steam • ½” - 600 PSIG WOG, Cold Non-Shock. • Federal Specification: WW-V-35C,Type II Composition: BZ Style: 3

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

B2...VSS Series, 2-way, Ball Valve Stainless Steel Body, Ball and Stem • Live-load packing set • Stainless steel ball & stem • Blow-out proof stem design

Application These threaded valves are designed to provide modulating or two position control of hot or chilled water and saturated steam systems under 50 psi. Typical applications include reheat coils, vav terminal control, unit ventilators, and air handlers, especially in areas which have minimum profile requirements. • Up to 50 psi steam • ½” - 2000 PSIG WOG, Cold Non-Shock. • Federal Specification: WW-V-35C,Type II, Composition: SS Style: 3

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

6 7 8 9 10

Gland Stem Jam nut Body seal Body

20

B219VSS

1

25

B224VSS

48



32

B232VSS

84



40

B239VSS

108

2

50

B249VSS

503



65

B265VSS

SY Series

¾

43

AM NM Series Series

30

Suitable Actuators Spring Non- Spring Return Return

GM Series

reinforced PTFE reinforced PTFE 316 stainless steel reinforced PTFE w/ Durafill B16 (¾” - 1”) stainless steel B584 (1¼” - 3”) stainless steel A276-316 316 stainless steel stainless steel PTFE (1¼” to 3”) A351-CF8M 316 stainless steel

Cv 15

Valve Nominal Size Type DN Inches 2-way NPT [mm] ½ 15 B2050VSS-15

LF Series

Sizes Type of end fitting Materials: 1 Stem packing 2 Stem bearing 3 Ball 4 Seat (x2) 5 Retainer

chilled or hot water, glycol, 50# steam modified equal percentage 90° rotation valve open CW, valve closed CCW ½”, ¾”, 1”, 1¼”, 1½”, 2”, 2½” SAE NPT (female connections)

AF Series

Technical Data Media Flow characteristic Action

10

Pressure rating Media temp. range Close-off pressure Maximum differential pressure (ΔP)

2000 psig WOG (½” - 1”) -22°F to +298°F (-30°C to +148°C) 600 psig @ 100°F <600 psig

Flow Patterns

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

7

B3...L Series, 3-way, Ball Valve Chrome Plated Brass Ball and Nickel Plated Stem

Application This valve is typically used in air handling and fan coil units on heating or cooling coils, unit ventilators, VAV box re-heat coils, and bypass loops. This valve is suitable for use as a diverting valve only.

15

B315L

12.8

¾

20

B320L

11

1

25

B325L

34



32

B332L

57



40

B340L

87

2

50

B350L

Sizes Type of end fitting Materials: Body Ball Stem Stem seal Valve seat Leakage Pressure rating

Media temp. range Close-off pressure Maximum differential pressure (ΔP)

chilled or hot water, 60% glycol modified linear 90° rotation B to A open CW, B to AB open CCW ½”, ¾”, 1”, 1¼”, 1½”, 2” NPT female ends nickel plated brass chrome plated brass nickel plated brass o-ring EPDM PTFE ANSI VI 600 psig WOG 600 psi DN 15-25 (B3...L) 400 psi DN 32-50 (B3...L) 0°F to 250°F [-18°C to +120°C] 200 psi 50 psi

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Technical Data Media Flow characteristic Action

NR

w

½

LR Series

6.4

Suitable Actuators Non-Spring Electronic Return Fail-Safe

AR Series

Inches DN [mm]

Spring Return LF Series

Cv

Type 3-way NPT

AF Series

Valve Nominal Size

Flow Patterns

B to A Open CW

800-543-9038 USA

8

B to AB Open CCW

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

B6...VS Series, 2-way, Ball Valve Cast Iron Body, Stainless Steel Ball and Stem • • • • •

Same end to end dimension as conventional flanged iron gate valve Fast quarter turn open or closed operation Stainless steel ball and stem Positive shut-off Two-piece body construction

Application • Ideal for water service where a non-corrosive, clean cosmetic appearance is required. • Optional FDA approval, suitable for potable water and food contact. • Sizes: 2”-10” (50-250mm) • 200 psi CWP (cold water pressure) (non-shock) Approved valves shall comply with the American Standard for face-to-face dimensions (ANSI B16.10) for Class 125 cast iron flanged gate valves.

Sizes Type of end fittings Materials: 1 Body 2 End cap 3 Ball 4 Seats 5 Stem 6 Packing 7 Gland 8 Gasket 9 Nut

Pressure rating Media temp. range Close-off pressure Maximum differential pressure (ΔP)

chilled or hot water, glycol, 50# steam modified equal percentage 90% rotation valve open CW, valve closed CCW 2”, 2½”, 3”, 4”, 6”, 8”, 10” flanged 125# ANSI bolt pattern cast iron - ASTM A126 Class B cast iron - ASTM A126 Class B 304 stainless steel - ASTM A351 PTFE 304 stainless steel - AISI 304 PTFE cast iron - ASTM A126 Class B PTFE steel - ASTM A6

Cv 330

Valve Nominal Size Inches DN [mm] 2 50

Type 2-way NPT B650VS

420



65

600

3

80

B680VS

1200

4

100

B6100VS

3300

6

150

B6150VS

9000

8

203

B6200VS

12400

10

254

B6250VS

Suitable Actuators Non-Spring Return

B665VS SY Series

Technical Data Media Flow characteristic Action

The dimensions and drilling of end flanges conform to the American cast iron flange standard, Class 125 (ANSI B16.1).

200 psig WOG -22°F to +298°F (-30°C to +148°C) 200 psig @ 140°F <200 psi

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

9

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

This Page Intentionally Left Blank

800-543-9038 USA

10

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Ball Valve Product Range Overview VS/VSS Ball Valve Product Range B2...VS/VSS, B3...L, B6...VS

Type

½

15

B2050VS-15

30

¾

20

B219VS

51

¾

20

B220VS

43

1

25

B224VS

68

1

25

B225VS

48



32

B232VS



40

B239VS



40

B240VS

108

2

50

B249VS

389

2

50

B250VS

190



65

B265VS

370

3

80

B280VS

15

½

15

B2050VSS-15

30

¾

20

B219VSS

43

1

25

B224VSS

48



32

B232VSS

84



40

B239VSS

108

2

50

B249VSS

190



65

B265VSS

370

3

80

B280VSS

6.4

½

15

B315L

12.8

¾

20

B320L

11

1

25

B325L

34



32

B332L

57



40

B340L

87

2

50

B350L

330

2

50

B650VS

420



65

B665VS

600

3

80

B680VS

1200

4

100

B6100VS

3300

6

150

B6150VS

9000

8

200

B6200VS

12400

10

250

B6250VS

Product Features Modified equal percentage of flow for B2, B3 and B6. Modified linear flow for B3.

AR Series

NR

LR Series

GM Series

AM Series

NM Series

GK

GM Series

84 177

Mode of Operation The control valve is operated by an electronic actuator that responds to a standard voltage for on/off control, by a proportional VDC/4…20 mA, or 3-point control system. The actuator will then move the ball of the valve to the position dictated by the contol signal thus changing the flow.

GK

15

Actuator Specifications Control type on/off, floating point, proportional, 2-10 VDC multi-function technology (MFT) Manual override LM, NM, GM, AM, SY, AF, NF, GK Electrical connection 3 ft [1m] cable with ½” conduit fitting Valve Specifications Service Flow characteristic

GK

B2050VS-04

LF Series

B2050VS-02

15

NF Series

15

½

AF Series

½

4

LF

2

Electronic Fail-Safe

NF

B2050VS-01

Spring Return

AF Series

15

Non-Spring Return

LFR Series

½

2-Way Flanged

Sizes End fitting Materials Body

Ball

AFR Series

1

3-way NPT

SY Series

2-way NPT

LM Series

DN [mm]

NM Series

Inches

AM Series

Cv

Suitable Actuators

SY Series

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Valve Nominal Size

Stem Seats 2-way 3-way Packing 2-way NPT 2-way flanged Media temp range B2..VS, B6..VS B2..VSS B3...L Body pressure rating 3-way Maximum inlet pressure Steam Water Leakage

800-543-9038 USA

866-805-7089 CANADA

chilled or hot water, (60% glycol), steam modified equal percentage (2-way), modified linear (3-way)

½” to 10” NPT (B2...VS & B3.. L) flanged (B6...VS) bronze (B2..VS), stainless steel (B2..VSS), nickel plated brass (B3...L), cast iron (B6..VS) stainless steel, bronze (½”) chrome plated brass (B3...L) stainless steel, bronze (½”) nickel plated brass (B3...L) MPTFE LPTFE RPTFE PTFE -22°F to +280°F [-30°C to +138°C] -22°F to +298°F [-30°C to +148°C] 0°F to 250°F [-18°C to +120°C] up to 2000 psig WOG 600 psi DN 15-25 (B3...L) 400 psi DN 32-50 (B3...L) 35 psi B2..VS 50 psi B2..VSS, B6..VS 50 psi B3...L ANSI class VI

203-791-8396 LATIN AMERICA / CARIBBEAN

11

LF Actuators, On/Off Dimensions with 2-Way Valve

Models w/built-in Aux. Switch

on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 120 VAC ± 10% 50/60 Hz

Dimensions with 3-Way Valve

w/built-in Aux. Switch

Technical Data Control Power supply LF24(-S) US LF120(-S) US Power consumption LF24(-S) US

A 6.75 6.75 6.75 6.70 6.70

Dimensions (Inches) B C D F 2.00 6.75 2.25 4.00 2.00 6.75 2.25 4.00 2.00 6.75 2.25 4.00 2.00 8.00 2.25 6.25 2.00 8.00 2.25 6.25

running holding running holding

5W 2.5 W LF120(-S) US 5.5 W 3.5 W Transformer sizing 7 VA, class 2 power source Electrical connection ½” conduit connector (-S models have 2 cables) 3 ft. [1m], 18 GA appliance cable Electrical protection 120V actuators double insulated Overload protection electronic throughout rotation Angle of rotation 95° Spring return direction reversible with CW/CCW mounting Position indication visual indicator 0° to 90° Running time <40 to 75 sec. (on/off) spring <25 sec. @ -4°F to +122°F [-20°C to +50°C] <60 sec. @ -22°F [-30°C] Ambient temperature -22° F to +122° F [-30° C to +50° C] Housing NEMA 2 Agency listings† UL 873, CSA C22.2 No. 24 certified, CE Quality standard ISO 9001 Noise level max. 62 dB(A) LF...-S US Auxiliary switch

COP 50 50 50 50 1000

Valve Nominal Size Inches DN [mm] ½ 15 ½ 15 ½ 15 ½ 15 ½ 15

Valve Body B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B2050VSS-15

Valve Body

COP

B315L B320L B325L

50 50 50

Valve Nominal Size DN Inches [mm] ½ 15 ¾ 20 1 25

Dimensions (mm) A

B

C

2.63” [67] 1.73” [44] 1.42” [36] 3.01” [78] 1.81” [46] 1.63” [42] 3.42” [87] 1.81” [46] 1.77” [45]

1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed, adjustable 0° to 95° (double insulated)

† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3, Type of action 1.AA (1.AA.B for -S models)

800-543-9038 USA

12

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

LF24 US LF24-S US LF120 US LF120-S US

LF Actuators, On/Off W047

Wiring Diagrams 24 VAC Transformer

2

Provide overload protection and disconnect as required.

2 + Hot

CAUTION Equipment damage!

LF24 US

Actuators may be connected in parallel. Power consumption must be observed.

3

2

On/Off wiring for 24 VAC/DC

3

Actuator may also be powered by 24 VDC.

4

For end position indication, interlock control, fan startup, etc., LF24-S US and LF120-S US incorporates a built-in auxiliary switch: 1 x SPDT, 6A (1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.

W049-LF-08

1

1 Common

Line Volts

Meets cULus or UL and CSA requirements without the need of an electrical ground connection.

WARNING Live Electrical Components! On/Off wiring for 120 VAC W048-AUX

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Auxiliary Switch

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

13

LF24-MFT US Actuators, Multi-Function Technology Dimensions with 2-Way Valve

Models w/built-in Aux. Switch

Technical Data Control Control signal Power consumption

running holding

Transformer sizing Electrical connection (-S models have 2 cables) Overload protection Input impedance

Feedback Angle of rotation Direction of rotation

spring motor

Position indication Running time spring Ambient temperature Housing Agency listings Noise level Quality standard LF24-MFT-S US Auxiliary switch

MFT 2 to 10 VDC (4-20mA with 500 Ω resistor) 2.5 W 1W 5 VA (class 2 power source) ½” conduit connector 3 ft. [1m], 18 GA appliance cable electronic throughout 0° to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20mA 750 Ω for PWM 500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max 95° reversible with CW/CCW mounting reversible with built-in visual indicator <40 to 75 sec. (on/off) 150 sec. independent of load (proportional) <25 sec. @ -4°F to +122°F [-20°C to +50°C] <60 sec. @-22°F [-30°C] -22° F to +122° F [-30° C to +50° C] NEMA 2 UL 873, CSA C22.2 No. 24 certified, CE max. 62 dB(A) ISO 9001

COP 50 50 50 50 1000

Valve Nominal Size Inches DN [mm] ½ 15 ½ 15 ½ 15 ½ 15 ½ 15

A 6.75 6.75 6.75 6.70 6.70

Dimensions (Inches) B C D F 2.00 6.75 2.25 4.00 2.00 6.75 2.25 4.00 2.00 6.75 2.25 4.00 2.00 8.00 2.25 6.25 2.00 8.00 2.25 6.25

Dimensions with 3-Way Valve

Valve Body

COP

B315L B320L B325L

50 50 50

Valve Nominal Size DN Inches [mm] ½ 15 ¾ 20 1 25

Dimensions (mm) A

B

C

2.63” [67] 1.73” [44] 1.42” [36] 3.01” [78] 1.81” [46] 1.63” [42] 3.42” [87] 1.81” [46] 1.77” [45]

1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed, adjustable 0° to 95° (double insulated)

800-543-9038 USA

14

Valve Body B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B2050VSS-15

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

LF24-MFT US LF24-MFT-S US

Wiring Diagrams

24 VAC/DC Transformer Line Volts

CAUTION Equipment damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. Actuators may also be powered by 24 VDC.

4

IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).

5

Triac A and B can also be contact closures.

7

Common

(2)

Hot

(3)

Y Input

(5)

U Output

a

(–)

Feedback VDC (+)

CCW CW

3

6

Position

(1)

…MFT

On/Off control W041

2

W043

LF24-MFT US Actuators, Multi-Function Technology

24 VAC Transformer (AC only)

Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. Position feedback cannot be used with Triac sink controller. The actuators internal common reference is not compatible.

(1)

Line Volts 7

6

Position

(–)

Feedback VDC (+)

The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel.

Common

(2)

+ Hot

(3)

Y Input

(5)

U Output

CCW CW

…MFT

PWM, triac source and sink

WARNING Live Electrical Components!

W302

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

...MFT

Floating Point control

Propotional 2 to 10 or 4 to 20 mA control signal

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

15

NF Actuators, On/Off Dimensions with 2-Way Valve

C

F

A

B

D

Models w/built-in Aux. Switch

Technical Data Control Power consumption NFB24-X1 NFBUP-X1 Transformer sizing

Electrical connection (-S model has 2 cables) Electrical protection Overload protection Angle of rotation Position indication Running time Ambient temperature Housing Agency listings Noise level

COP 400 200 1000

Valve Nominal Size Dimensions (Inches) Inches DN [mm] A B C D F ¾ 20 7.00 2.00 8.00 3.37 6.25 ¾ 20 7.00 2.00 8.00 3.37 6.25 ¾ 20 7.00 2.00 8.00 3.37 6.25

on/off running holding running holding NFB24-X1 NFBUP(-S)-X1

6W 2.5 W 6W 2.5 W 8.5 VA (class 2 power source) 6 VA @ 24 VAC (class 2 powe source) 6.5 VA @ 120 VAC 9.5 VA @ 240 VAC ½” conduit connector 3 ft. [1m], 18 GA appliance cables 120V actuators double insulated electronic throughout 0° to 95° rotation 95° visual indicator control <75 seconds spring <20 seconds -22° F to +122° F [-30° C to +50° C] NEMA 2 / IP54 UL 873, CSA C22.2 No. 24 certified, CE max. 45 dB(A)

NFBUP-S-X1 Auxiliary switch

2 x SPDT, 3A (0.5A inductive) @ 250 V

800-543-9038 USA

16

Valve Body B219VS B220VS B219VSS

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

NFB24-X1 NFBUP-X1 NFBUP-S-X1

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

NF Actuators, On/Off

1

2

Provide overload protection and disconnect as required.

24 VAC Transformer 1 Common

Line Volts

CAUTION Equipment damage!

2 + Hot

3

Actuators may be connected in parallel. Power consumption must be observed.

3

Actuators may also be powered by 24 VDC.

4

For end position indication, interlock control, fan startup, etc., NF24-S US incorporates a built-in auxiliary switch: 1 x SPDT, 7A (2.5A) @ 250 VAC, UL listed, adjustable 5° to 85°.

NFB24-X1

2

On/Off wiring for NFB24-X1 W066_NFB(X)UP

1

W063_NFB(X)

Wiring Diagrams

Meets cULus or UL and CSA requirements without the need of an electrical ground connection.

WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

NFBUP-X1 NFBUP-S-X1

W067_NFB(X)UP-S

On/Off wiring for NFBUP-X1, NFBUP-S-X1

Wht

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Blk

NFBUP-S-X1 Auxiliary Switch

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

17

NF Actuators, Multi-Function Technology Dimensions with 2-Way Valve

C

F

A

B

D

NFX24-MFT-X1 NFX24-MFT-S-X1 Technical Data Control Control signal Power supply Power consumption

running holding

Transformer sizing Electrical connection Overload protection Input impedance

Feedback output Angle of rotation Direction of rotation Position indication Running time

spring motor motor spring

Ambient temperature Housing Agency listings

Noise level

NFX24-MFT-S-X1 Auxiliary switch

MFT 2 to 10 VDC, (4 to 20 mA with 500 Ω resistor) 24 VAC ± 20% 50/60 Hz 24 VDC ± 20% / -10% 6.5 W 3W 9 VA, (class 2 power source) ½” conduit connector 3 ft. [1m], 18 GA appliance cable electronic throughout 0 to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max 95° reversible with CW/CCW mounting reversible with built-in visual indicator, 0° to 95° 150 seconds (default), variable (40 to 220 seconds) <20 sec @ -4°F to +122°F [-20°C to +50°C]; <60 sec @ -22°F [-30°F] -22°F to +122°F [-30°C to +50°C] NEMA 2 / IP54, Enclosure Type 2 cULus acc. to UL60730-1A/ -2-14, CAN/ CSA E60730-1:02, CE acc. to 2004/108/EC & 2006/95/EC <40 dB(A) motor @ 150 seconds, run time dependent <62 dB(A) spring return

COP 400 200 1000

Valve Nominal Size Dimensions (Inches) Inches DN [mm] A B C D F 7.00 2.00 8.00 3.37 6.25 ¾ 20 ¾ 20 7.00 2.00 8.00 3.37 6.25 ¾ 20 7.00 2.00 8.00 3.37 6.25

2 x SPDT, 3A (0.5A) @ 250 VAC, UL Approved one set at +10°, one adjustable 10° to 90°

800-543-9038 USA

18

Valve Body B219VS B220VS B219VSS

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Models

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

NF Actuators, Multi-Function Technology 4

24 VAC Transformer

4

IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).

5

Triac A and B can also be contact closures.

7

Wht (3) Y1 Input, 2 to 10V 7

Pnk (4) Y2 Input Grn (5) U Output, 2 to 10V CCW CW

VDC/4-20 mA 10

24 VAC Transformer

Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. Position feedback cannot be used with Triac sink controller. The actuators internal common reference is not compatible.

W400_A_11

Actuators may also be powered by 24 VDC.

Red (2) + Hot 500 Ω Ω 1/4 watt

(–) Control Signal (+) 4 to 20 mA or 2 to 10 VDC

Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.

3

6

Volts

CAUTION Equipment damage!

5

Blk (1) Common

Line

2

3

W400_A_11

Wiring Diagrams

5

4

Blk (1) Common –

Line Volts

Red (2) Hot +

A 8 (–) 2 to 10 VDC Feedback Signal (+)

The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel. Meets cULus or UL and CSA requirements without the need of an electrical ground connection.

Wht (3) Y1 Input

B Pnk (4) Y2 Input

9

Org (5) U Output 2 to 10V

Direction of rotation switch CCW

CCW

CW

CW

B 5

A

A

B 5

Floating Point During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

24 VAC Transformer (AC only)

W400_A_11

WARNING Live Electrical Components! 5

4

Blk (1) Common

Line 8

Volts

Red (2) + Hot Wht (3) Y Input Pnk (4) Y2 Input Org (5) U Output

Position (–) Feedback VDC (+)

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

24 VAC/DC Transformer

4

W400_A_11

PWM 5

3

Blk (1) Common

Line Volts

Red (2) Hot a

Position Feedback VDC

Wht (3) Y Input Pnk (4) Y2 Input Org (5) U Output

(–) (+)

W400_A_11

Two Position 5

24 VAC Transformer (AC Only)

Blk (1) Common

Line Volts Ω (–) Control Signal 2-10 VDC or 4 to 20 mA (+)

7

Red (2) + Hot

A B C

Wht (3) Y1 Input, 2 to 10V Pnk (4) Y2 Input Org (5)

500 Ω 1/4 watt

Functions Min* Mid* Max* Normal**

a

b

c

0% 50% 100% Control mode acc. to Y

* Default selectable 0-100%. See Configuration Data Sheet. ** Customizable. See Configuration Data Sheet.

Override Control to Min, Mid, Max, Positions

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

19

NF Actuators, Multi-Function Technology Dimensions with 2-Way Valve

C

F

A

B

D

NFX24-MFT95-X1 Technical Data Control Control signal Power supply Power consumption

running holding

Transformer sizing Electrical connection Overload protection Input impedance

Feedback output Angle of rotation Direction of rotation Position indication Running time

spring motor control spring

Ambient temperature Housing Agency listings

Noise level

MFT 0-135  24 VAC ± 20% 50/60 Hz 24 VDC ± 20% / -10% 6.5 W 3W 9 VA (class 2 power source) ½” conduit connector 3 ft. [1m], 18 GA appliance cable electronic throughout 0 to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max 95° (adjustable with mechanical end stop, 35° to 95°) reversible with CW/CCW mounting reversible with built-in visual indicator, 0° to 95° 150 seconds (default), variable (40 to 220 seconds) <20 sec @ -4°F to +122°F [-20°C to +50°C]; <60 sec @ -22°F [-30°F] -22°F to +122°F [-30°C to +50°C] NEMA 2 / IP54, Enclosure Type 2 cULus acc. to UL60730-1A/ -2-14, CAN/ CSA E60730-1:02, CE acc. to 2004/108/EC & 2006/95/EC <40 dB(A) motor @ 150 seconds, run time dependent, <62 dB(A) spring return

800-543-9038 USA

20

Valve Body B219VS B220VS B219VSS

866-805-7089 CANADA

COP 400 200 1000

Valve Nominal Size Dimensions (Inches) Inches DN [mm] A B C D F 7.00 2.00 8.00 3.37 6.25 ¾ 20 ¾ 20 7.00 2.00 8.00 3.37 6.25 ¾ 20 7.00 2.00 8.00 2.25 6.25

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Models

203-791-8396 LATIN AMERICA / CARIBBEAN

NF Actuators, Multi-Function Technology

Provide overload protection and disconnect as required.

Line

22

R

Series 90 high limit control - 280 Ω

Line

Red (2) + Hot Wht (3) Wht (4) Wht (5) Wht (6)

R B

24

Damper Position

Series 90 Controller

W R B

Blk (1) Common

Volts

Red (2) + Hot

23

A Wht (3) W Wht (4) R

B

-MFT95-X1

21 Line

No. of actuators Resistance 2 140 Ω 3 71.5 Ω 4 47.5 Ω 5 37.5 Ω 6 28 Ω Resistor Kit No. ZG-R03

Wht (3) Wht (4) Wht (5) Wht (6) To other actuators

Red (2) + Hot Wht (3) W

Line

R

Volts

B

24

B

B

22

Wht (6) ‘U5’ Output 2 to 10 VDC

Controller

Line Volts

Red (2) + Hot

‘U5’ Output 2 to 10 VDC

25

Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC To other actuators

-MFT95-X1

Used with the W973 and W7100 controllers

-MFT95-X1

Wht (3) Wht (4) Wht (5) Wht (6)

22

Wht (3) W

21 24 VAC Transformer

Honeywell Q209A Minimum Position Potentiometer

Line

Blk (1) Common

Volts

25

W R B

Shunting Resistor

‘U5’ Output 2 to 10 VDC

Red (2) + Hot

22

23

W

R

R

R

B

W

Wht (3) W

W

Wht (4) R Wht (5) B

B

W973, W7100 T775

23 25

Wht (6) ‘U5’ Output 2 to 10 VDC

Honeywell T675A Morning Warmup

-MFT95-X1

-MFT95-X1

23

Line Volts

24

22

Red (2) + Hot

Series 90 Controller

25

R

W

R

B

Wht (3) W

R

Wht (4) R

B

Wht (5) B

Series 90 low limit control 135 Ω for 0 to 50% control 280 Ω for 0 to 100% control

21

21

Blk (1) Common

W

W R B

24

W

23 B

24 VAC Transformer

W

Blk (1) Common

H205 Change- Occupied over Controller Contact

Low Limit Control

22

B

W

24

-MFT95-X1

21

R

R Shunting Resistor

Honeywell T675A Morning Warmup

W

No. of actuators Resistance 2 1300 Ω 3 910 Ω 4 768 Ω Resistor Kit No. ZG-R06

23

Red (2) + Hot

23

Wht (5) B

R

Volts

Blk (1) Common

Series 90 Controller

Wht (4) R

Occupied Contact

Line

S963A Minimum Position Potentiometer

Line Volts

A W

24 VAC Transformer

21

Blk (1) Common

Volts

B

21

‘U5’ Output 2 to 10 VDC

Red (2) + Hot

Wht (6) ‘U5’ Output 2 to 10 VDC 24 VAC Transformer

W

W973, W7100 Controller

Wiring Multiple Actuators to a Series 90 Controller using a Minimum Position Potentiometer

Wht (5) B

-MFT95-X1

22 Shunting Resistor

W016

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

135 Ω

24

Wht (5) B

24

25

W019

Line

25

Wht (4) R

Blk (1) Common

Volts

W015

21 24 VAC Transformer

Wht (3) W

23

Line

The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.

B

R

23

21 Damper Closed

W

R

Y

-MFT95-X1

Damper Open

R

23

Wht (6) ‘U5’ Output 2 to 10 VDC

Blk (1) Common

W

B W

-MFT95-X1

24 VAC Transformer

Volts

Override Switch B

H205 Changeover Controller

Wiring Multiple Actuators to a Series 90 Controller 21

Red (2) + Hot

22

Wht (6) ‘U5’ Output 2 to 10 VDC

Shunting Resistor

Switch A

24

Wht (5) B

B

W

Blk (1) Common

Volts

Wht (4) R

R B

To reverse control rotation, use the reversing switch.

25

Wht (3) W

W

Series 90 Controller

Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell® resistor kits may also be used.

24

Line

Red (2) + Hot

23

Consult controller instruction data for more detailed information.

23

Q209A Minimum Position Potentiometer

Blk (1) Common

Volts

Actuators and controller must have separate transformers.

22

21 24 VAC Transformer

W018

21

W017

24 VAC Transformer

21

Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers W020

High Limit Control

INSTALLATION NOTES

Blk (1) Common Red (2) + Hot Wht (3) Wht (4) Wht (5) Wht (6)

Wht (6) ‘U5’ Output 2 to 10 VDC

800-543-9038 USA

-MFT95-X1

Line

To other actuators

W R B

23

Red (2) + Hot

22

Wht (3) W

25

23 25

Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC

‘U5’ Output 2 to 10 VDC

-MFT95-X1

866-805-7089 CANADA

Blk (1) Common

Volts

To other actuators

-MFT95-X1

203-791-8396 LATIN AMERICA / CARIBBEAN

21

AF Actuators, On/Off Dimensions with 2-Way Valve

F

C

A

B

D

Models

AFBUP-S-X1 Transformer sizing

on/off running holding running holding AFB24-X1 AFBUP(-S)-X1

Electrical connection (-S model has 2 cables) Electrical protection Overload protection Angle of rotation Position indication Manual override Running time Ambient temperature Housing Agency listings Noise level

5W 2.5 W 7W 3.5 W 7.5 VA (class 2 power source) 7 VA @ 24 VAC (class 2 power source) 8.5 VA @ 120 VAC 18 VA @ 240 VAC ½” conduit connector 3 ft. [1m], 18 GA appliance cables 120V actuators double insulated electronic throughout 0° to 95° rotation 95° visual indicator hex crank control 150 seconds independent of load spring <20 seconds -22°F to +122°F [-30°C to +50°C] NEMA 2 / IP54 UL 873, CSA C22.2 No. 24 certified, CE max. 45 dB(A)

AFBUP-S-X1 Auxiliary switches

* Dual Mounted Actuators

800-543-9038 USA

22

2 x SPDT, 7A (2.5A) @ 250 VAC, UL listed, one switch is fixed at +5°, one is adjustable 25° to 85° (double insulated)

Valve Nominal Size Inches DN [mm] 1 25 1 25 1¼ 32 1½ 40 1½ 40 2 50 1 25 1¼ 32 1½ 40 2 50

A 7.00 7.00 7.25 15.00 15.00 15.00 7.00 7.25 15.00 15.00

Dimensions (Inches) B C D 2.00 8.00 3.37 2.00 8.00 3.62 2.00 8.00 3.97 3.00 8.00 4.37 3.00 8.00 4.75 3.00 8.00 4.68 2.00 8.00 3.37 2.00 8.00 3.97 3.00 8.00 4.37 3.00 8.00 4.68

F 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25

Dimensions with 3-Way Valve 9.77” [248.2]

4.04” [102.7]

Valve Body

COP

B332L B340L B350L

50 50 50

866-805-7089 CANADA

Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56] 1½ 40 4.80” [122] 2.44” [62] 2.61” [67] 2 50 5.60” [142] 2.67” [68] 3.11” [79]

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Technical Data Control Power consumption AFBUP-X1

COP 400 200 200 600 600 600 1000 1000 1000 600

2.50” [63.5]

w/built-in Aux. Switches

Valve Body B224VS B225VS B232VS *B239VS *B240VS *B249VS B224VSS B232VSS *B239VSS *B249VSS

3.93” [99.9]

AFB24-X1 AFBUP-X1 AFBUP-S-X1

AF Actuators, On/Off j y

W194_AFB24-X1

p

Wiring Diagrams

24 VAC Transformer

2

Provide overload protection and disconnect as required.

2 + Hot

CAUTION Equipment damage!

AFB24-X1

Actuators may be connected in parallel. Power consumption must be observed.

3

2

On/Off Wiring for AFB24-X1

3

Actuators may also be powered by 24 VDC.

4

For end position indication, interlock control, fan startup, etc., AF24-S US incorporates two built-in auxiliary switches: 2 x SPDT, 7A (2.5A) @ 250 VAC, UL listed, one switch is fixed at +5°, one is adjustable 25° to 85°.

W003_AFB24-X1

1

1 Common

Line Volts

Meets cULus or UL and CSA requirements without the need of an electrical ground connection.

AFBUP-X1 AFBUP-S-X1

WARNING Live Electrical Components!

On/Off Wiring for AFBUP-X1, AFBUP-S-X1 W195_AFBUP-S-X1

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

AFBUP-S-X1

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Auxiliary Switches

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

23

AF Actuators, Multi-Function Technology Dimensions with 2-Way Valve

F

C

A

B

D

Models

Power supply Power consumption

running holding

Transformer sizing Electrical connection (-S model has 2 cables) Overload protection Input impedance

Feedback output Angle of rotation Direction of rotation Position indication Manual override Running time Ambient temperature Housing Agency listings Noise level AFX24-MFT-S-X1 Auxiliary switches

spring motor

control spring

MFT 2 to 10 VDC, (4 to 20 mA with 500 Ω resistor) 0-135 Ω (MFT95) 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 7.5 W 3W 10 VA (class 2 power source) ½” conduit connector 3 ft. [1m], 18 GA appliance cable electronic throughout rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max 95° reversible with CW/CCW mounting reversible with built-in visual indicator hex crank 150 seconds independent of load <20 seconds -22°F to +122°F [-30°C to +50°C] NEMA 2 / IP54 UL 873, CSA C22.2 No. 24 certified, CE max. 45 dB(A)

2 x SPDT, 7A (2.5A) @ 250 VAC, UL listed, one switch is fixed at +5°, one is adjustable 25° to 85° (double insulated)

COP 400 50 200 400 50 200 1000 1000 1000 1000 400

Valve Nominal Size Inches DN [mm] 1 25 1 25 1¼ 32 1½ 40 1½ 40 2 50 1 25 1¼ 32 1¼ 32 1½ 40 2 50

A 7.00 7.00 7.25 7.50 7.50 8.00 7.00 7.25 7.25 6.70 8.00

Dimensions (Inches) B C D F 2.00 8.00 3.37 6.25 2.00 8.00 3.62 6.25 2.00 8.00 3.97 6.25 2.00 8.00 4.37 6.25 2.00 8.00 4.75 6.25 2.00 8.00 4.68 6.25 2.00 8.00 3.37 6.25 2.00 8.00 3.97 6.25 2.00 8.00 3.97 6.25 2.00 8.00 4.37 6.25 2.00 8.00 4.68 6.25

Dimensions with 3-Way Valve 9.77” [248.2]

4.04” [102.7]

Valve Body

COP

B332L B340L B350L

50 50 50

Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56] 1½ 40 4.80” [122] 2.44” [62] 2.61” [67] 2 50 5.60” [142] 2.67” [68] 3.11” [79]

* Dual Mounted Actuators

800-543-9038 USA

24

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Technical Data Control Control signal

Valve Body B224VS B225VS B232VS *B239VS *B240VS *B249VS B224VSS B232VSS *B232VSS *B239VSS *B249VSS

2.50” [63.5]

w/built-in Aux. Switches

3.93” [99.9]

AFX24-MFT-X1 AFX24-MFT-S-X1 AFX24-MFT95-X1

AF Actuators, Multi-Function Technology W043

Wiring Diagrams 24 VAC/DC Transformer

Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.

3

Actuators may also be powered by 24 VDC.

4

IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).

5

Triac A and B can also be contact closures.

6 7

Position

(1)

Common

(2)

Hot

(3)

Y Input

(5)

U Output

a

(–)

Feedback VDC (+)

CCW CW

…MFT

On/Off control W041

2

Line Volts

CAUTION Equipment damage!

24 VAC Transformer (AC only)

Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. Position feedback cannot be used with Triac sink controller. The actuators internal common reference is not compatible.

(1)

Line Volts 7

6

Position

(–)

Feedback VDC (+)

+ Hot

(3)

Y Input

(5)

U Output

CCW CW

…MFT

PWM, triac source and sink W302_AFBX24-MFT

The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel. Meets cULus or UL and CSA requirements without the need of an electrical ground connection.

Common

(2)

WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

...MFT

Floating Point control

Propotional 2 to 10 or 4 to 20 mA control signal

AFX24-MFT-S-X1

Auxiliary Switches

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

25

AF Actuators, Multi-Function Technology

Line

22

R

Series 90 high limit control - 280 Ω

Red (2) + Hot Wht (3) Wht (4) Wht (5) Wht (6)

R B

24

Damper Position

Series 90 Controller

W R B

Blk (1) Common

Volts

Red (2) + Hot

23

A Wht (3) W 135 Ω

24

Wht (4) R

B

-MFT95-X1

21 Line

No. of actuators Resistance 2 140 Ω 3 71.5 Ω 4 47.5 Ω 5 37.5 Ω 6 28 Ω Resistor Kit No. ZG-R03

Wht (3) Wht (4) Wht (5) Wht (6) To other actuators

Red (2) + Hot Wht (3) W

Line

R

Volts

B

24

B

B

22

Wht (6) ‘U5’ Output 2 to 10 VDC

Controller

Volts

‘U5’ Output 2 to 10 VDC

25

Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC To other actuators

-MFT95-X1

Used with the W973 and W7100 controllers

-MFT95-X1

Wht (3) Wht (4) Wht (5) Wht (6)

22

Wht (3) W

21 24 VAC Transformer

Honeywell Q209A Minimum Position Potentiometer

Line

Blk (1) Common

Volts

25

W R B

Shunting Resistor

‘U5’ Output 2 to 10 VDC

Red (2) + Hot

22

23

W

R

R

R

B

W

Wht (3) W

W

Wht (4) R Wht (5) B

B

W973, W7100 T775

23 25

Wht (6) ‘U5’ Output 2 to 10 VDC

Honeywell T675A Morning Warmup

-MFT95-X1

-MFT95-X1

23

Line Volts

24

22

Red (2) + Hot R

B

Wht (3) W

R

Wht (4) R

B

Wht (5) B

Series 90 low limit control 135 Ω for 0 to 50% control 280 Ω for 0 to 100% control

R

W

21

-MFT95-X1

Line

Blk (1) Common Red (2) + Hot Wht (3) Wht (4) Wht (5) Wht (6)

Wht (6) ‘U5’ Output 2 to 10 VDC

800-543-9038 USA

26

25

21

Blk (1) Common

Series 90 Controller

Red (2) + Hot

W016

Line

W

W R B

24

W

23 B

24 VAC Transformer

W

Blk (1) Common

H205 Change- Occupied over Controller Contact

Low Limit Control

22

B

W

24

-MFT95-X1

21

R

R Shunting Resistor

Honeywell T675A Morning Warmup

W

No. of actuators Resistance 2 1300 Ω 3 910 Ω 4 768 Ω Resistor Kit No. ZG-R06

23

Red (2) + Hot

23

Wht (5) B

R

Volts

Blk (1) Common

Series 90 Controller

Wht (4) R

Occupied Contact

Line

S963A Minimum Position Potentiometer

Line Volts

A W

24 VAC Transformer

21

Blk (1) Common

Volts

B

21

‘U5’ Output 2 to 10 VDC

Red (2) + Hot

Wht (6) ‘U5’ Output 2 to 10 VDC 24 VAC Transformer

W

W973, W7100 Controller

Wiring Multiple Actuators to a Series 90 Controller using a Minimum Position Potentiometer

Wht (5) B

-MFT95-X1

22

24

25

W019

Line

Wht (5) B

Blk (1) Common

Volts

W015

21 24 VAC Transformer

25

23

Line

The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.

Wht (3) W Wht (4) R

R

23

21 Damper Closed

B

Y

-MFT95-X1

Damper Open

W

R

Shunting Resistor

Blk (1) Common

W

R

23

Wht (6) ‘U5’ Output 2 to 10 VDC

W018

Line

B W

-MFT95-X1

24 VAC Transformer

Volts

Override Switch B

H205 Changeover Controller

Wiring Multiple Actuators to a Series 90 Controller 21

Red (2) + Hot

22

Wht (6) ‘U5’ Output 2 to 10 VDC

Shunting Resistor

Switch A

24

Wht (5) B

B

W

Blk (1) Common

Volts

Wht (4) R

R B

To reverse control rotation, use the reversing switch.

25

Wht (3) W

W

Series 90 Controller

Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell® resistor kits may also be used.

24

Line

Red (2) + Hot

23

Consult controller instruction data for more detailed information.

23

Q209A Minimum Position Potentiometer

Blk (1) Common

Volts

Actuators and controller must have separate transformers.

22

21 24 VAC Transformer

To other actuators

W R B

23

Red (2) + Hot

22

Wht (3) W

25

23 25

Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC

‘U5’ Output 2 to 10 VDC

-MFT95-X1

866-805-7089 CANADA

Blk (1) Common

Volts

To other actuators

-MFT95-X1

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Provide overload protection and disconnect as required.

21

W017

24 VAC Transformer

21

Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers W020

High Limit Control

INSTALLATION NOTES

LM(B)X24-3-X1, LRX24-3 Actuators, On/Off, Floating Point

PAGE7

Dimensions with 2-Way Valve

H2

H1

F

C

B

A

Models D

LMB24-3-X1 LMX24-3-X1 LRX24-3 Technical Data Control Power supply Power consumption

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Transformer sizing Electrical connection LMB24-3-X1 Overload protection Input impedance Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings

Noise level Servicing Quality standard

Valve Body COP B2050VS-01 50 B2050VS-02 50 B2050VS-04 50 B2050VS-15 50

on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 1.5 W holding 0.2 W 3 VA (class 2 power source) ½” conduit connector 3 ft., 18 GA plenum rated cables

A 6.75 6.75 6.75 6.75

Dimensions (Inches) B C D F H1 2.00 6.75 2.25 4.00 9.75 2.00 6.75 2.25 4.00 9.75 2.00 6.75 2.25 4.00 9.75 2.00 6.75 2.25 4.00 9.75

H2 8.50 8.50 8.50 8.50

Dimensions with 3-Way Valve

electronic throughout 0° to 95° rotation 600 Ω 95° 45 in-lbs [5 Nm] reversible with reflective visual indicator (snap-on) external push button 95 seconds, constant independent of load 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA C22.2 No. 24 certified, CE acc. to 73/23/EEC <35 db(A) maintenance free ISO 9001

800-543-9038 USA

Valve Nominal Size Inches DN [mm] ½ 15 15 ½ ½ 15 ½ 15

Valve Body

COP

B315L B320L B325L

50 50 50

866-805-7089 CANADA

Valve Nominal Size DN Inches [mm] ½ 15 ¾ 20 1 25

Dimensions (mm) A

B

C

2.63” [67] 1.73” [44] 1.42” [36] 3.01” [78] 1.81” [46] 1.63” [42] 3.42” [87] 1.81” [46] 1.77” [45]

203-791-8396 LATIN AMERICA / CARIBBEAN

27

LM(B)X24-3-X1, LRX24-3 Actuators, On/Off, Floating Point W266-08

Wiring Diagrams

1

Provide overload protection and disconnect as required.

3

Actuators may also be powered by 24 VDC.

Meets cULus or UL and CSA requirements without the need of an electrical ground connection. On/Off control

WARNING Live Electrical Components!

W267-08

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

Floating Point or On/Off control

Piping

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. Allow 6” for cover removal and 12” for complete actuator removal. The assembly can be mounted with the actuator vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction.

800-543-9038 USA

28

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

LMX24-MFT-X1, LRX24-MFT Actuators, Multi-Function Technology

PAGE7

Dimensions with 2-Way Valve

H2

H1

F

C

B

A

Models LMX24-MFT-X1 LRX24-MFT

D

Technical Data Power supply Power consumption Transformer sizing Electrical connection

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Overload protection Input impedance

Feedback Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings

Noise level Servicing Quality standard

24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 2W 3.5 VA (class 2 power source) 3 ft. [1m], 10 ft. [3m], 16 ft. [5m] 18 GA plenum rated cable ½” conduit connector electronic throughout 0° to 95° rotation 100k Ω for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max VDC variable 95° 45 in-lbs [5 Nm] reversible with reflective visual indicator (snap-on) external push button 150 seconds (default) variable (35 to 150 seconds) 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <35 db(A) maintenance free ISO 9001

800-543-9038 USA

Valve Nominal Size DN Valve Body COP Inches [mm] B2050VS-01 50 ½ 15 B2050VS-02 50 15 ½ B2050VS-04 50 ½ 15 B2050VS-15 50 ½ 15

Dimensions (Inches) A

B

C

D

F

H1

H2

6.75 6.75 6.75 6.75

2.00 2.00 2.00 2.00

6.75 6.75 6.75 6.75

2.25 2.25 2.25 2.25

4.00 4.00 4.00 4.00

9.75 9.75 9.75 9.75

8.50 8.50 8.50 8.50

Dimensions with 3-Way Valve

Valve Body

COP

B315L B320L B325L

50 50 50

866-805-7089 CANADA

Valve Nominal Size DN Inches [mm] ½ 15 ¾ 20 1 25

Dimensions (mm) A

B

C

2.63” [67] 1.73” [44] 1.42” [36] 3.01” [78] 1.81” [46] 1.63” [42] 3.42” [87] 1.81” [46] 1.77” [45]

203-791-8396 LATIN AMERICA / CARIBBEAN

29

LMX24-MFT-X1, LRX24-MFTT Actuators, Multi-Function Technology

Provide overload protection and disconnect as required.

3

Actuators may also be powered by 24 VDC.

5

Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line.

6

ZG-R01 may be used.

4

7 8

24 VAC/DC Transformer

1

2 Blk (1) Common

Line Volts

Red (2) Hot

3 a

(–)

Position

Wht (3) Y Input

Feedback VDC (+)

Org (5) U Output …MFT

Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.

On/Off control 24 VAC Transformer

W399

1

W399

Wiring Diagrams

2

1

Blk (1) Common –

Line Volts

Red (2) Hot +

A

3 5

Wht (3) Y1 Input

B

8

Pnk (4) Y2 Input 7

2 to 10 VDC Feedback Signal

Org (5) U Output 2 to 10V

4 …MFT

W399

Floating Point 24 VAC Transformer 1 Line Volts

2 Blk (1) Common Red (2) + Hot

3

Ω

Control Signal 4 to 20 mA or 2 to 10 VDC

500Ω 1/4 watt

(–) (+)

Wht (3) Y1 Input, 2 to 10V 6 Org (5) U Output, 2 to 10V

…MFT

24 VAC Transformer (AC only) 1

Blk (1) Common

Line Volts

5

(–) 2 Position Feedback VDC (+)

Red (2) + Hot Wht (3) Y Input Org (5) U Output

…MFT

PWM

800-543-9038 USA

30

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

W399

VDC/4-20 mA

NM(B)X24-3-X1, NRB24-3 Actuators, On/Off, Floating Point

PAGE7

Dimensions with 2-Way Valve

H2

H1

F

C

B

A

Models NMB24-3-X1 NMX24-3-X1 NRB24-3

D

Technical Data Control Power supply

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Power consumption Transformer sizing Electrical connection NMB24-3-X1 Overload protection Input impedance Angle of rotation Torque Direction of rotation

Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings

Noise level Servicing Quality standard

on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 2.0 W holding 0.2 W 4 VA (class 2 power source) 3 ft., 18 GA plenum rated cable ½” conduit connector electronic throughout 0° to 95° rotation 600 Ω max 95°, adjustable with mechanical stop 90 in-lbs [10 Nm] reversible with =CCW with decreasing control signal (10-2V) =CW with decreasing control signal (10-2V) reflective visual indicator (snap-on) external push button 95 seconds, constant independent of load 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA C22.2 No. 24 certified, CE acc. to 73/23/EEC <45 db(A) maintenance free ISO 9001

800-543-9038 USA

Valve Nominal Size DN Valve Body COP Inches [mm] B219VS 400 ¾ 20 B220VS 20 400 ¾ B2050VSS-15 1000 ½ 15 B219VSS 1000 ¾ 20

Dimensions (Inches) A

B

C

D

F

H1

H2

6.70 6.70 6.70 6.70

2.00 2.00 2.00 2.00

8.00 8.00 8.00 8.00

3.00 3.12 2.25 3.00

6.25 6.25 6.25 6.25

9.75 9.75 9.75 9.75

8.50 8.50 8.50 8.50

Dimensions with 3-Way Valve

Valve Body

COP

B332L

50

866-805-7089 CANADA

Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56]

203-791-8396 LATIN AMERICA / CARIBBEAN

31

NM(B)X24-3-X1, NRB24-3 Actuators, On/Off, Floating Point W266-08

Wiring Diagrams

1

Provide overload protection and disconnect as required.

3

Actuators may also be powered by 24 VDC.

Meets cULus or UL and CSA requirements without the need of an electrical ground connection. During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

On/Off control W267-08

WARNING Live Electrical Components!

Floating Point or On/Off control

Piping

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. Allow 6” for cover removal and 12” for complete actuator removal. The assembly can be mounted with the actuator vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction.

800-543-9038 USA

32

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

NMX24-MFT-X1, NRX24-MFT Actuators, Multi-Function Technology

PAGE7

Dimensions with 2-Way Valve

H2

H1

F

C

B

A

Models NMX24-MFT-X1 NRX24-MFT

D

Technical Data Power supply Power consumption Transformer sizing Electrical connection

Overload protection Input impedance

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Feedback Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings

Noise level Servicing Quality standard

24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 3.5 W (1.25 W) 5.5 VA (class 2 power source) 3 ft. [1m], 10 ft. [3m], 16 ft. [5m] 18 GA plenum rated cable ½” conduit connector electronic throughout 0° to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max VDC variable max 95°, adjust. with mechanical stop electronically variable 90 in-lbs [10 Nm] reversible with reflective visual indicator (snap-on) external push button 150 seconds (default) Variable (45 to 170 secondss) 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <45 db(A) maintenance free ISO 9001

800-543-9038 USA

Valve Nominal Size DN Valve Body COP Inches [mm] B219VS 400 ¾ 20 B220VS 20 400 ¾ B2050VSS-15 1000 ½ 15 B219VSS 1000 ¾ 20

Dimensions (Inches) A

B

C

D

F

H1

H2

6.70 6.70 6.70 6.70

2.00 2.00 2.00 2.00

8.00 8.00 8.00 8.00

3.00 3.12 2.25 3.00

6.25 6.25 6.25 6.25

9.75 9.75 9.75 9.75

8.50 8.50 8.50 8.50

Dimensions with 3-Way Valve

Valve Body

COP

B332L

50

866-805-7089 CANADA

Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56]

203-791-8396 LATIN AMERICA / CARIBBEAN

33

NMX24-MFT-X1, NRX24-MFT Actuators, Multi-Function Technology

Provide overload protection and disconnect as required.

3

Actuators may also be powered by 24 VDC.

5

Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line.

6

ZG-R01 may be used.

4

7 8

24 VAC/DC Transformer

1

2 Blk (1) Common

Line Volts

Red (2) Hot

3 a

(–)

Position

Wht (3) Y Input

Feedback VDC (+)

Org (5) U Output …MFT

Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.

On/Off control 24 VAC Transformer

W399

1

W399

Wiring Diagrams

2

1

Blk (1) Common –

Line Volts

Red (2) Hot +

A

3 5

Wht (3) Y1 Input

B

8

Pnk (4) Y2 Input 7

2 to 10 VDC Feedback Signal

Org (5) U Output 2 to 10V

4 …MFT

W399

Floating Point 24 VAC Transformer 1 Line Volts

2 Blk (1) Common Red (2) + Hot

3

Ω

Control Signal 4 to 20 mA or 2 to 10 VDC

500Ω 1/4 watt

(–) (+)

Wht (3) Y1 Input, 2 to 10V 6 Org (5) U Output, 2 to 10V

…MFT

24 VAC Transformer (AC only) 1

Blk (1) Common

Line Volts

5

(–) 2 Position Feedback VDC (+)

Red (2) + Hot Wht (3) Y Input Org (5) U Output

…MFT

PWM

800-543-9038 USA

34

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

W399

VDC/4-20 mA

AM(B)X24-3-X1, ARX24-3 Actuators, On/Off, Floating Point

PAGE7

Dimensions with 2-Way Valve

H2

H1

F

C

B

A

Models AMB24-3-X1 AMX24-3-X1 ARX24-3

D

Technical Data Control Power supply

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Power consumption Transformer sizing Electrical connection AMB24-3-X1 Overload protection Input impedance Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings

Noise level Servicing Quality standard

on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 2.5 W holding 0.2 W 5.5 VA (class 2 power source) ½” conduit connector 3 ft., 18 GA plenum rated cable electronic throughout 0° to 95° rotation 600 Ω max 95°, adjustable with mechanical stop 180 in-lbs [20 Nm] reversible with reflective visual indicator (snap-on) external push button 95 seconds, constant independent of load 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA C22.2 No. 24 certified, CE acc. to 73/23/EEC <45 db(A) maintenance free ISO 9001

800-543-9038 USA

Valve Body COP B224VS B225VS B232VS B224VSS B232VSS

400 200 400 1000 1000

Valve Nominal Size DN Inches [mm] 1 25 25 1 32 1¼ 1 25 1¼ 32

Dimensions (Inches) A

B

C

D

F

H1

H2

7.00 7.00 7.25 7.00 7.25

2.00 2.00 2.00 2.00 2.00

8.00 8.00 8.00 8.00 8.00

3.37 3.62 3.97 3.37 3.97

6.25 6.25 6.25 6.25 6.25

9.75 9.75 9.75 9.75 9.75

8.50 8.50 8.50 8.50 8.50

Dimensions with 3-Way Valve

Valve Body

COP

B340L B350L

50 50

866-805-7089 CANADA

Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1½ 40 4.80” [122] 2.44” [62] 2.61” [65] 2 50 5.60” [142] 2.67” [68] 3.11” [79]

203-791-8396 LATIN AMERICA / CARIBBEAN

35

AM(B)X24-3-X1, ARX24-3 Actuators, On/Off, Floating Point

1 2

W259-08

Wiring Diagrams

Provide overload protection and disconnect as required.

CAUTION Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed.

3

Actuators may also be powered by 24 VDC.

5

Only connect common to neg. (–) leg of control circuits.

W260-08

On/Off control Meets cULus or UL and CSA requirements without the need of an electrical ground connection.

WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

Floating Point or On/Off control

Piping

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. Allow 6” for cover removal and 12” for complete actuator removal. The assembly can be mounted with the actuator vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction.

800-543-9038 USA

36

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

AMX24-MFT-X1, ARX24-MFT Actuators, Multi-Function Technology

PAGE7

Dimensions with 2-Way Valve

H2

H1

F

C

B

A

Models AMX24-MFT-X1 AMX24-MFT95-X1 ARX24-MFT Technical Data Power supply Power consumption Transformer sizing Electrical connection

Overload protection Input impedance

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Feedback Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings

Noise level Servicing Quality standard

D

24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 4 W (1.25 W) 6 VA (class 2 power source) 3 ft. [1m], 10 ft. [3m], 16 ft. [5m] 18 GA plenum rated cable ½” conduit connector electronic throughout 0° to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max VDC variable max 95°, adjust. with mechanical stop electronically variable 180 in-lbs [20 Nm] reversible with reflective visual indicator (snap-on) external push button 150 seconds (default) variable (90 to 350 seconds) 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <45 db(A) maintenance free ISO 9001

800-543-9038 USA

Valve Nominal Size DN Valve Body COP Inches [mm] B224VS 400 1 25 B225VS 25 200 1 32 B232VS 400 1¼ B224VSS 1000 1 25 B232VSS 1000 1¼ 32

Dimensions (Inches) A

B

C

D

F

H1

H2

7.00 7.00 7.25 7.00 7.25

2.00 2.00 2.00 2.00 2.00

8.00 8.00 8.00 8.00 8.00

3.37 3.62 3.97 3.37 3.97

6.25 6.25 6.25 6.25 6.25

9.75 9.75 9.75 9.75 9.75

8.50 8.50 8.50 8.50 8.50

Dimensions with 3-Way Valve

Valve Body

COP

B340L B350L

50 50

866-805-7089 CANADA

Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1½ 40 4.80” [122] 2.44” [62] 2.61” [65] 2 50 5.60” [142] 2.67” [68] 3.11” [79]

203-791-8396 LATIN AMERICA / CARIBBEAN

37

AMX24-MFT-X1, ARX24-MFTT Actuators, Multi-Function Technology

Provide overload protection and disconnect as required.

3

Actuators may also be powered by 24 VDC.

5

Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line.

6

ZG-R01 may be used.

4

7 8

24 VAC/DC Transformer

1

2 Blk (1) Common

Line Volts

Red (2) Hot

3 a

(–)

Position

Wht (3) Y Input

Feedback VDC (+)

Org (5) U Output …MFT

Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.

On/Off control 24 VAC Transformer

W399

1

W399

Wiring Diagrams

2

1

Blk (1) Common –

Line Volts

Red (2) Hot +

A

3 5

Wht (3) Y1 Input

B

8

Pnk (4) Y2 Input 7

2 to 10 VDC Feedback Signal

Org (5) U Output 2 to 10V

4 …MFT

W399

Floating Point 24 VAC Transformer 1 Line Volts

2 Blk (1) Common Red (2) + Hot

3

Ω

Control Signal 4 to 20 mA or 2 to 10 VDC

500Ω 1/4 watt

(–) (+)

Wht (3) Y1 Input, 2 to 10V 6 Org (5) U Output, 2 to 10V

…MFT

24 VAC Transformer (AC only) 1

Blk (1) Common

Line Volts

5

(–) 2 Position Feedback VDC (+)

Red (2) + Hot Wht (3) Y Input Org (5) U Output

…MFT

PWM

800-543-9038 USA

38

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

W399

VDC/4-20 mA

AMX24-MFT-X1 Actuators, Multi-Function Technology

Provide overload protection and disconnect as required.

Line

22 Series 90 Controller

Wht (3) W

R

Wht (4) R R

Series 90 high limit control - 280 Ω

Line

Red (2) + Hot Wht (3) W Wht (4) R Wht (5) B

W R B

24

Damper Position

Blk (1) Common

Volts

Red (2) + Hot

23

A Wht (3) W 135 Ω

24

Wht (4) R

B

Red (2) + Hot

No. of actuators Resistance 2 140 Ω 3 71.5 Ω 4 47.5 Ω 5 37.5 Ω 6 28 Ω Resistor Kit No. ZG-R03

Wht (3) Wht (4) Wht (5) Wht (6) To other actuators

Wht (6) ‘U5’ Output 2 to 10 VDC -MFT95-X1

21 24 VAC Transformer

Red (2) + Hot

Line Volts

Wht (3) W

R

Wht (4) R

B

B

22

24

B

R

R

22

Wht (6) ‘U5’ Output 2 to 10 VDC

Controller

Line Volts

Red (2) + Hot

23 Series 90 Controller

25

Blk (1) Common Red (2) + Hot

‘U5’ Output 2 to 10 VDC

Wht (3) W

25

Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC To other actuators

-MFT95-X1

Used with the W973 and W7100 controllers

-MFT95-X1

21 24 VAC Transformer

Wht (3) Wht (4) Wht (5) Wht (6)

Honeywell Q209A Minimum Position Potentiometer

Line

Blk (1) Common

Volts

25

W R B

Shunting Resistor

‘U5’ Output 2 to 10 VDC

Red (2) + Hot

22

23

W

R

R

R

B

W

Wht (3) W

W

Wht (4) R Wht (5) B

B

W973, W7100 T775

23 25

Wht (6) ‘U5’ Output 2 to 10 VDC

Honeywell T675A Morning Warmup

-MFT95-X1

-MFT95-X1 R

W

R

B

Wht (3) W

R

Wht (4) R

B

Wht (5) B

Series 90 low limit control 135 Ω for 0 to 50% control 280 Ω for 0 to 100% control

21

21

Blk (1) Common

W

Honeywell T675A Morning Warmup

W

No. of actuators Resistance 2 1300 Ω 3 910 Ω 4 768 Ω Resistor Kit No. ZG-R06

24

W

23 B

24 VAC Transformer

W

R

H205 Change- Occupied over Controller Contact

Low Limit Control

22

B

W

24

-MFT95-X1

21

W R B

Red (2) + Hot

23

Wht (5) B

Occupied Contact

21

23

Blk (1) Common

Series 90 Controller

Shunting Resistor

B

Volts

S963A Minimum Position Potentiometer

Line Volts

A W

24 VAC Transformer

21

Blk (1) Common

W

W016

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Line Volts

-MFT95-X1

22 Shunting Resistor

Line

Wiring Multiple Actuators to a Series 90 Controller using a Minimum Position Potentiometer

Wht (5) B

Wht (5) B

W973, W7100 Controller

W019

Line

Wht (4) R

Blk (1) Common

Volts

W015

21 24 VAC Transformer

B

23 25

23

Line

The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.

R

Wht (3) W

24

25

21 Damper Closed

W

R

23

-MFT95-X1

Damper Open

W

Y

Wht (6) ‘U5’ Output 2 to 10 VDC

Series 90 Controller

R

Wht (6) ‘U5’ Output 2 to 10 VDC

Blk (1) Common

Volts

Override Switch B

H205 Changeover Controller

B

-MFT95-X1

24 VAC Transformer

21

Red (2) + Hot

22

Wiring Multiple Actuators to a Series 90 Controller

Shunting Resistor

Switch A

24

Wht (5) B

B

W

Blk (1) Common

Volts

Wht (6) ‘U5’ Output 2 to 10 VDC

To reverse control rotation, use the reversing switch.

25

W

B

Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell® resistor kits may also be used.

24

Line

Red (2) + Hot

23

Consult controller instruction data for more detailed information.

23

Q209A Minimum Position Potentiometer

Blk (1) Common

Volts

Actuators and controller must have separate transformers.

22

21 24 VAC Transformer

W018

21

W017

24 VAC Transformer

21

Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers W020

High Limit Control

INSTALLATION NOTES

24

Line Volts

Red (2) + Hot

22

Wht (3) Wht (4) Wht (5) Wht (6)

Wht (6) ‘U5’ Output 2 to 10 VDC

800-543-9038 USA

-MFT95-X1

Line

Blk (1) Common

To other actuators

W R B

23

Red (2) + Hot

22

Wht (3) W

25

23 25

Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC

‘U5’ Output 2 to 10 VDC

-MFT95-X1

866-805-7089 CANADA

Blk (1) Common

Volts

To other actuators

-MFT95-X1

203-791-8396 LATIN AMERICA / CARIBBEAN

39

GMB24-3-X1 Actuators, On/Off, Floating Point

PAGE7

Dimensions with 2-Way Valve

H2

H1

F

C

B

A

D

Models

Power consumption Transformer sizing Electrical connection

Overload protection Angle of rotation Direction of rotation Position indication Running time Humidity Ambient temperature Housing Housing material Agency listings

Noise level Quality standard

on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 4 W holding 2 W 6 VA (class 2 power source) 3 ft. [1m] 18 GA plenum rated cable ½” conduit connector electronic throughout stroke 95° reversible with reflective visual indicator (snap-on) 150 seconds, constant independent of load 5 to 95% RH non-condensing -22°F to +122°F [-30°C to +50°C] NEMA 2/IP54 with cable entry down UL94-5V (flammability rating) cULus acc. to UL 60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <45 dB(A) ISO 9001

Dimensions (Inches) A

B

C

D

F

H1

H2

7.50 7.50 7.50 7.50

3.00 3.00 3.00 3.00

8.00 8.00 8.00 8.00

4.37 4.68 4.37 4.68

6.25 6.25 6.25 6.25

9.75 9.75 9.75 9.75

8.50 8.50 8.50 8.50

Dimensions with 2*GM... and 2-Way Valve

H2

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Technical Data Control Power supply

Valve Nominal Size DN Valve Body COP Inches [mm] B239VS 400 1½ 40 B249VS 50 200 2 40 B239VSS 1000 1½ B249VSS 400 2 50

PAGE7

GMB24-3-X1 2*GMB24-3-X1

H1

F

C

B

A

D

Valve Nominal Size DN Valve Body COP Inches [mm] 40 B240VS 400 1½ B250VS 50 200 2 B265VS 65 100 2½ B280VS 80 50 3 B249VSS 1000 2 50 B265VSS 200 2½ 65

Dimensions (Inches) A

B

C

D

F

7.50 15.00 15.00 15.00 7.50 15.00

3.00 3.00 3.00 3.00 3.00 3.00

8.00 8.00 8.00 8.00 8.00 8.00

4.75 5.37 6.25 6.75 4.68 6.25

6.25 6.25 6.25 6.25 6.25 6.25

H1* H2* 9.75 9.75 9.75 9.75 9.75 9.75

*Handles not available on spring return series or dual mounted actuators

800-543-9038 USA

40

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

8.50 8.50 8.50 8.50 8.50 8.50

GMB24-3-X1 Actuators, On/Off, Floating Point Wiring Diagrams

1

Provide overload protection and disconnect as required.

2

Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.

3

Actuators may also be powered by 24 VDC.

4 5 7 8

Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line. Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.

GMB24-3-X1

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

On/Off control

GMB24-3-X1

Floating Point or On/Off control

Piping The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. Allow 6” for cover removal and 12” for complete actuator removal. The assembly can be mounted with the actuator vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction.

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

41

GMX24-MFT-X1 Actuators, Multi-Function Technology

PAGE7

Dimensions with 2-Way Valve

H2

H1

F

C

B

A

D

Models

Power consumption Transformer sizing Electrical connection

Overload protection Input impedance

Feedback Angle of rotation Direction of rotation Position indication Running time Humidity Ambient temperature Housing Housing material Agency listings

Noise level Quality standard

on/off, floating point, 2 to 10 VDC 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 4.5 W holding 3 W 7 VA (class 2 power source) 3 ft. [1m] 18 GA plenum rated cable ½” conduit connector electronic throughout stroke 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max VDC variable 95° reversible with reflective visual indicator (snap-on) 150 seconds, constant independent of load 5 to 95% RH non-condensing -22°F to +122°F [-30°C to +50°C] NEMA 2/IP54 with cable entry down UL94-5V (flammability rating) cULus acc. to UL 60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <45 dB(A) ISO 9001

B239VS B249VS B239VSS B249VSS

400 200 1000 400

Dimensions (Inches) A

B

C

D

F

H1

H2

7.50 7.50 7.50 7.50

3.00 3.00 3.00 3.00

8.00 8.00 8.00 8.00

4.37 4.68 4.37 4.68

6.25 6.25 6.25 6.25

9.75 9.75 9.75 9.75

8.50 8.50 8.50 8.50

Dimensions with 2xGM... and 2-Way Valve PAGE7

Technical Data Control Power supply

Valve Body COP

Valve Nominal Size DN Inches [mm] 1½ 40 50 2 40 1½ 2 50

H2

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

GMX24-MFT-X1 *2xGMX24-MFT-X1 GMX24-MFT95-X1

H1

F

C

B

A

D

Valve Body COP B240VS B250VS B265VS B280VS B265VSS B280VSS

400 200 100 50 200 100

Valve Nominal Size DN Inches [mm] 40 1½ 50 2 65 2½ 80 3 65 2½ 80 3

Dimensions (Inches) A

B

C

D

F

7.50 15.00 15.00 15.00 15.00 15.00

3.00 3.00 3.00 3.00 3.00 3.00

8.00 8.00 8.00 8.00 8.00 8.00

4.75 5.37 6.25 6.75 6.25 6.75

6.25 6.25 6.25 6.25 6.25 6.25

H1* H2* 9.75 9.75 9.75 9.75 9.75 9.75

8.50 8.50 8.50 8.50 8.50 8.50

*Handles not available on spring return series or dual mounted actuators

800-543-9038 USA

42

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

GMX24-MFT-X1 Actuators, Multi-Function Technology Wiring Diagrams

1

Provide overload protection and disconnect as required.

2

Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.

3

Actuators may also be powered by 24 VDC.

5

Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line.

6

ZG-R01 may be used.

7 8

Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.

24 VAC/DC Transformer

1

W399

4

2 Blk (1) Common

Line Volts

Red (2) Hot

3 a

(–)

Position

Wht (3) Y Input

Feedback VDC (+)

Org (5) U Output …MFT

24 VAC Transformer

2

1

Blk (1) Common –

Line Volts

Red (2) Hot +

A

3 5

Wht (3) Y1 Input

B

8

Pnk (4) Y2 Input 7

2 to 10 VDC Feedback Signal

Org (5) U Output 2 to 10V

4 …MFT

W399

Floating Point 24 VAC Transformer 1 Line Volts

2 Blk (1) Common Red (2) + Hot

3

Ω

Control Signal 4 to 20 mA or 2 to 10 VDC

500Ω 1/4 watt

(–) (+)

Wht (3) Y1 Input, 2 to 10V 6 Org (5) U Output, 2 to 10V

…MFT

VDC/4-20 mA W399

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

W399

On/Off control

24 VAC Transformer (AC only) 1

Line Volts (–) 2 Position Feedback VDC (+)

Blk (1) Common 5

Red (2) + Hot Wht (3) Y Input Org (5) U Output

…MFT

PWM

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

43

GMX24-MFT-X1 Actuators, Multi-Function Technology

Line

22 Series 90 Controller

Wht (3) W

R

Wht (4) R R

Series 90 high limit control - 280 Ω

Red (2) + Hot Wht (3) W Wht (4) R Wht (5) B

W R B

24

Damper Position

Blk (1) Common

Volts

Red (2) + Hot

23

A Wht (3) W 135 Ω

24

Wht (4) R

B

Red (2) + Hot

No. of actuators Resistance 2 140 Ω 3 71.5 Ω 4 47.5 Ω 5 37.5 Ω 6 28 Ω Resistor Kit No. ZG-R03

Wht (3) Wht (4) Wht (5) Wht (6) To other actuators

Wht (6) ‘U5’ Output 2 to 10 VDC -MFT95-X1

21 24 VAC Transformer Line

Red (2) + Hot

Line Volts

Wht (3) W

R

Wht (4) R

B

B

22

24

B

R

R

22

Wht (6) ‘U5’ Output 2 to 10 VDC

Controller

Volts

Red (2) + Hot

23 R

B

Wht (3) W

R

Wht (4) R

B

Wht (5) B

Series 90 low limit control 135 Ω for 0 to 50% control 280 Ω for 0 to 100% control

Red (2) + Hot Wht (3) W

‘U5’ Output 2 to 10 VDC

25

Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC To other actuators

-MFT95-X1

Used with the W973 and W7100 controllers

-MFT95-X1

Wht (3) Wht (4) Wht (5) Wht (6)

21 24 VAC Transformer

Honeywell Q209A Minimum Position Potentiometer

Line

Blk (1) Common

Volts

25

W R B

Shunting Resistor

‘U5’ Output 2 to 10 VDC

Red (2) + Hot

22

23

W

R

R

R

B

W

Wht (3) W

W

Wht (4) R Wht (5) B

B

W973, W7100 T775

23 25

Wht (6) ‘U5’ Output 2 to 10 VDC

Honeywell T675A Morning Warmup

-MFT95-X1

-MFT95-X1 R

W

21

24

Line Volts

-MFT95-X1

Line

Blk (1) Common Red (2) + Hot

22

Wht (3) Wht (4) Wht (5) Wht (6)

Wht (6) ‘U5’ Output 2 to 10 VDC

800-543-9038 USA

44

25

21

Blk (1) Common

Series 90 Controller

Blk (1) Common

W016

Line

W

Honeywell T675A Morning Warmup

W

No. of actuators Resistance 2 1300 Ω 3 910 Ω 4 768 Ω Resistor Kit No. ZG-R06

24

W

23 B

24 VAC Transformer

W

R

H205 Change- Occupied over Controller Contact

Low Limit Control

22

B

W

24

-MFT95-X1

21

W R B

Red (2) + Hot

23

Wht (5) B

Occupied Contact

21

23

Blk (1) Common

Series 90 Controller

Shunting Resistor

B

Volts

S963A Minimum Position Potentiometer

Line Volts

A W

24 VAC Transformer

21

Blk (1) Common

Volts

W

Line

Wiring Multiple Actuators to a Series 90 Controller using a Minimum Position Potentiometer

Wht (5) B

-MFT95-X1

22

W973, W7100 Controller

W019

Line

Wht (5) B

Blk (1) Common

Volts

W015

21 24 VAC Transformer

Wht (4) R

23

Line

The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.

B

23 25

24

25

21 Damper Closed

R

R

23

-MFT95-X1

Damper Open

W

Wht (3) W

Y

Wht (6) ‘U5’ Output 2 to 10 VDC

Series 90 Controller

W

Shunting Resistor

Blk (1) Common

Volts

R

Wht (6) ‘U5’ Output 2 to 10 VDC

W018

Line

Override Switch B

H205 Changeover Controller

B

-MFT95-X1

24 VAC Transformer

21

Red (2) + Hot

22

Wiring Multiple Actuators to a Series 90 Controller

Shunting Resistor

Switch A

24

Wht (5) B

B

W

Blk (1) Common

Volts

Wht (6) ‘U5’ Output 2 to 10 VDC

To reverse control rotation, use the reversing switch.

25

W

B

Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell® resistor kits may also be used.

24

Line

Red (2) + Hot

23

Consult controller instruction data for more detailed information.

23

Q209A Minimum Position Potentiometer

Blk (1) Common

Volts

Actuators and controller must have separate transformers.

22

21 24 VAC Transformer

To other actuators

W R B

23

Red (2) + Hot

22

Wht (3) W

25

23 25

Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC

‘U5’ Output 2 to 10 VDC

-MFT95-X1

866-805-7089 CANADA

Blk (1) Common

Volts

To other actuators

-MFT95-X1

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Provide overload protection and disconnect as required.

21

W017

24 VAC Transformer

21

Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers W020

High Limit Control

INSTALLATION NOTES

SY...24 NEMA 4X Industrial Style Actuators, 24VAC Attention SY Series actuators are fractional horsepower devices, and utilize full-wave power supplies. Observe wire sizing and transformer sizing requirements. Proportional models CANNOT be connected to Belimo direct coupled (AF, AM, GM…etc) actuator power supplies or any type of half-wave device. You MUST use a separate, dedicated transformer or power supply to power the SY actuator. Please do not connect other automation equipment to the dedicated SY supply source. You MUST use four wires (plus a ground) to control a proportional control SY actuator (See SY Wiring Section).

Models SY1-24(P) SY2-24MFT SY3-24MFT SY4-24MFT SY5-24MFT

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Technical Data Power supply Electrical connection Overload protection Motor protection

SY1 SY2... - SY5...

Geartrain Operating range Sensitivity Feedback Angle of rotation Direction of rotation Position indication Internal humidity control Auxiliary switches

SY...-24 SY...-24MFT SY...-24MFT SY...-24MFT

Ambient temperature Humidity range Housing type Housing material Agency listings

800-543-9038 USA

24 VAC 50/60Hz, single phase ½” conduit connector, screw terminals thermally protected 135°C cut-out H class insulation F class insulation high alloy steel gear sets, self locking on/off 2-10 VDC, 4-20mA, 1-5 VDC 0.2mA / 100mV 2-10 VDC, 4-20mA mechanically limited to 95° reversible top mounted domed indicator resistive heating element (2) SPDT, 10A 250VAC factory set for 3° and 87° change of state -22°F to +150°F [-30°C to +65°C] up to 95% IP67, NEMA 4X die cast aluminum alloy ISO, CE, cCSAus

Technical Data - continued Power Consumption SY1-24(P) SY2-24MFT SY3-24MFT SY4-24MFT SY5-24MFT Torque SY1-24(P) SY2-24MFT SY3-24MFT SY4-24MFT SY5-24MFT Manual Override SY1-24(P) SY2-24 – SY5-24 Running Time SY1-24(P) SY2-24MFT SY3-24MFT SY4-24MFT SY5-24MFT

866-805-7089 CANADA

1.8A 3.0A 3.0A 6.0A 6.5A 35 Nm / 310 in-lbs 90 Nm / 801 in-lbs 150 Nm / 1335 in-lbs 400 Nm / 3560 in-lbs 500 Nm / 4450 in-lbs 8mm wrench hand wheel 15 seconds 15 seconds 22 seconds 16 seconds 22 seconds

203-791-8396 LATIN AMERICA / CARIBBEAN

45

SY...24 NEMA 4X Industrial Style Actuators, 24VAC Wiring Diagrams

T 1 2

Transformer sizing = SY actuator draw X 1.25 (safety margin) EXAMPLE: SY2-24 requires 3.0A x 1.25 = 3.75A, 3.75A X 24 VAC = 90VA Transformer. There can be no connection (internal to automation controller, external wiring, or otherwise) between actuator supply neutral & control signal reference. These actuators are full wave devices. Any connection to half wave equipment will result in equipment damage. Do not change sensitivity or dip switch settings with power applied.

3

Terminals 6 & 11 can be common when control and feedback signals are both set for 2-10VDC operation.

4

Use of feedback is optional.

WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

On/Off control for SY(2-5)-24

2 to 10 vdc or 4 to 20 mA control signal for SY1-24P

800-543-9038 USA

46

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

SY...120 NEMA 4X Industrial Style Actuators, 120VAC Application: The SY actuators are NEMA 4X rated and designed to meet the needs of HVAC and Commercial applications. Offered on the HSU and HS butterfly valve series, these actuators are available for on/off and modulating applications. Depending on the application, they are available in 24 VAC, 120 VAC and 230 VAC. Technical Data - continued

Models SY1-110(P) SY2-120MFT SY3-120MFT SY4-120MFT SY5-120MFT SY6-120MFT SY7-120MFT SY8-120MFT

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Technical Data Power supply Electrical connection Overload protection Motor protection Geartrain Operating range

SY1 SY2... - SY8... SY...-110 SY...-120MFT

Sensitivity SY...-120MFT Feedback SY...120MFT Angle of rotation Direction of rotation Position indication Internal humidity control Auxiliary switches Ambient temperature Humidity range Housing type Housing material Agency listings

800-543-9038 USA

120 VAC 50/60Hz, single phase ½” conduit connector, screw terminals thermally protected 135°C cut-out H class insulation F class insulation high alloy steel gear sets, self locking on/off, floating point 2-10 VDC 4-20mA, 1-5 VDC

SY1-110(P) SY2-120MFT SY3-120MFT SY4-120MFT SY5-120MFT SY6-120MFT SY7-120MFT SY8-120MFT Torque SY1-110(P) SY2-120MFT SY3-120MFT SY4-120MFT SY5-120MFT SY6-120MFT SY7-120MFT SY8-120MFT Manual Override SY1-110(P) SY2-120MFT – SY8-120MFT Running Time SY1-110(P) SY2-120MFT SY3-120MFT SY4-120MFT SY5-120MFT SY6-120MFT SY7-120MFT SY8-120MFT

0.5A 1.0A 1.0A 1.3A 1.5A 1.8A 3.2A 4.0A 35 Nm / 310 in-lbs 90 Nm / 801 in-lbs 150 Nm / 1335 in-lbs 400 Nm / 3560 in-lbs 500 Nm / 4450 in-lbs 650 Nm / 5785 in-lbs 1000 Nm / 8900 in-lbs 1500 Nm / 13350 in-lbs 8mm wrench hand wheel 50hz 13 seconds 17 seconds 26 seconds 18 seconds 25 seconds 31 seconds 55 seconds 55 seconds

60hz 12 seconds 15 seconds 22 seconds 16 seconds 22 seconds 28 seconds 46 seconds 46 seconds

0.2mA / 100mV 2-10 VDC, 4-20mA mechanically limited to 95° reversible top mounted domed indicator resistive heating element (2) SPDT, 5A 250 VAC factory set for 5° and 85° change of state -22°F to +150°F [-30°C to +65°C] up to 95% IP67, NEMA 4X die cast aluminum alloy ISO, CE, cCSAus

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

47

SY...120 NEMA 4X Industrial Style Actuators, 120VAC Wiring Diagrams

Hazard Identification

NOTES SY1-110P

Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.

G

sCaution: Power supply voltage.

Ground

N L1

4

Power Supply Com

H L2

5

Power Supply Hot

6

Control Signal (-)

s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGS with power applied.

CAUTION

35

Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.

Actuator B

G

120 VAC

NOTES SY2...8-120MFT

7

Control Signal (+)

8

Internal Use Only

9

Internal Use Only

10 Internal Use Only

sCaution: Power supply voltage.

11 Feedback (-)

Feedback (B)

Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. Equipment damage! Power consumption and input impedance must be observed.

12 Feedback (+)

36

A

LS3

B C

A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max.

E F

LS4

A-E (Closed Indication)

SY1 -110P

INSTALLATION NOTES G

Observe class 1 and class 2 wiring restrictions.

APPLICATION NOTES 35

36

Control Signal 35

Recommended twisted shielded pair for control wiring. Ground shielded wire at control panel chassis. Tape back ground at actuator.

Actuator A

G

Ground

4

Power Supply Com

5

Power Supply Hot

6

Control Signal (-)

7

Control Signal (+)

8

Internal Use Only

9

Internal Use Only

10 Internal Use Only

Use of feedback is optional.

Feedback (A) Power Supply Com – 120v (N)

11 Feedback (-) 12 Feedback (+)

36

Power Supply Hot – 120v (H)

A

LS3

B A

Internal Use Only

B

Internal Use Only

C

L

Control Signal (+)

Y

1

Internal Use Only

Control Signal (-)

┴1

2

Internal Use Only

Feedback Signal (+)

U5

3

Internal Use Only

Feedback Signal (-)

┴2

Not Used -

C1

Not Used -

C2

8

Internal Use Only

9

Internal Use Only

10

Internal Use Only

E F

35

Adaption

Address

Y1

PE

G

LS4

A-E (Closed Indication)

SY1 -110P

Feedback 36

A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max.

Y2

SYx-120SR/MFT Actuator A

Power Supply Com – 120v (N) Power Supply Hot – 120v (H)

N

A

Internal Use Only

B

Internal Use Only

1

Internal Use Only

L

PC Tool Service Jack

Control Signal (+)

Y

Control Signal (-)

┴1

2

Internal Use Only

Feedback Signal (+)

U5

3

Internal Use Only

Feedback Signal (-)

┴2

Not Used -

C1

Not Used -

C2

Control Signal

A

A-C (Open Indication)

C

Feedback 36

D LS4

35

Adaption

800-543-9038 USA

48

PE

Actuator B

SYx-120MFT

E

Address

Y1

G

LS3

B

8

Internal Use Only

9

Internal Use Only

10

Internal Use Only

F

D-F (Closed Indication) Contact Rating: 5A 250 VAC Max.

Y2

866-805-7089 CANADA

SY2...8-120MFT

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

N

PC Tool Service Jack

SY...230 NEMA 4X Industrial Style Actuators, 230VAC Attention SY Series actuators are fractional horsepower devices, and utilize full-wave power supplies. Observe wire sizing and transformer sizing requirements. Proportional models CANNOT be connected to Belimo direct coupled (AF, AM, GM…etc) actuator power supplies or any type of half-wave device. You MUST use a separate, dedicated transformer or power supply to power the SY actuator. Please do not connect other automation equipment to the dedicated SY supply source. You MUST use four wires (plus a ground) to control a proportional control SY actuator (See SY Wiring Section).

Models SY1-220(P) SY2-230MFT SY3-230MFT SY4-230MFT SY5-230MFT SY6-230MFT

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Technical Data Power supply Electrical connection Overload protection Motor protection Geartrain Operating range

SY1 SY2... - SY6... SY...-220 SY...-230MFT SY...-230MFT SY...-230MFT

Sensitivity Feedback Angle of rotation Direction of rotation Position indication Internal humidity control Auxiliary switches Ambient temperature Humidity range Housing type Housing material Agency listings

230 VAC 50/60Hz, single phase ½” conduit connector, screw terminals thermally protected 135°C cut-out H class insulation F class insulation high alloy steel gear sets, self locking on/off, floating point 2-10 VDC, 4-20mA, 1-5 VDC 0.2mA / 200mV 2-10 VDC, 4-20mA mechanically limited to 95° reversible top mounted domed indicator resistive heating element (2) SPDT, 5A 250VAC factory set for 5° and 85° change of state -22°F to +150°F [-30°C to +65°C] up to 95% IP67, NEMA 4X die cast aluminum alloy ISO, CE, cCSAus

800-543-9038 USA

Technical Data - Continued Power consumption SY1-220(P) SY2-230MFT SY3-230MFT SY4-230MFT SY5-230MFT SY6-230MFT Torque SY1-220(P) SY2-230MFT SY3-230MFT SY4-230MFT SY5-230MFT SY6-230MFT Manual Override SY1-220(P) SY2-230MFT – SY6-230MFT Running Time SY1-220(P) SY2-230MFT SY3-230MFT SY4-230MFT SY5-230MFT SY6-230MFT

866-805-7089 CANADA

0.3A 0.5A 0.5A 0.6A 0.7A 0.8A 35 Nm / 310 in-lbs 90 Nm / 801 in-lbs 150 Nm / 1335 in-lbs 400 Nm / 3560 in-lbs 500 Nm / 4450 in-lbs 650 Nm / 5785 in-lbs 8mm wrench hand wheel 50hz 13 seconds 17 seconds 26 seconds 18 seconds 25 seconds 31 seconds

60hz 12 seconds 15 seconds 22 seconds 16 seconds 22 seconds 28 seconds

203-791-8396 LATIN AMERICA / CARIBBEAN

49

SY...230 NEMA 4X Industrial Style Actuators, 230VAC Wiring Diagrams

Hazard Identification

NOTES SY1-220P

Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.

G

sCaution: Power supply voltage.

Ground

N L1

4

Power Supply Com

H L2

5

Power Supply Hot

6

Control Signal (-)

s$ONOTCHANGESENSITIVITYORDIPSWITCHSETTINGS with power applied.

CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.

Actuator B

G

230 VAC

35

NOTES SY2...6-230MFT

7

Control Signal (+)

8

Internal Use Only

9

Internal Use Only

10 Internal Use Only

sCaution: Power supply voltage.

11 Feedback (-)

Feedback (B)

Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. Equipment damage! Power consumption and input impedance must be observed.

12 Feedback (+)

36

A

LS3

B C

A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max.

E F

LS4

A-E (Closed Indication)

SY1 -220P

INSTALLATION NOTES G

Observe class 1 and class 2 wiring restrictions.

APPLICATION NOTES 35

36

Control Signal 35

Recommended twisted shielded pair for control wiring. Ground shielded wire at control panel chassis. Tape back ground at actuator.

Actuator A

G

Ground

4

Power Supply Com

5

Power Supply Hot

6

Control Signal (-)

7

Control Signal (+)

8

Internal Use Only

9

Internal Use Only

10 Internal Use Only

Use of feedback is optional.

Feedback (A) Power Supply Com – 230v (L1)

11 Feedback (-) 12 Feedback (+)

36

Power Supply Hot – 230v (L2)

A

LS3

B A

Internal Use Only

B

Internal Use Only

C

L

Control Signal (+)

Y

1

Internal Use Only

Control Signal (-)

┴1

2

Internal Use Only

Feedback Signal (+)

U5

3

Internal Use Only

Feedback Signal (-)

┴2

Not Used -

C1

Not Used -

C2

8

Internal Use Only

9

Internal Use Only

10

Internal Use Only

E F

35

Adaption

Address

Y1 Y2

PE

G

Actuator A

LS4

A-E (Closed Indication)

SY1 -220P

Feedback 36

A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max.

SYx-230MFT

Power Supply Com – 230v (L1) Power Supply Hot – 230v (L2)

N

A

Internal Use Only

B

Internal Use Only

1

Internal Use Only

L

PC Tool Service Jack

Control Signal (+)

Y

Control Signal (-)

┴1

2

Internal Use Only

Feedback Signal (+)

U5

3

Internal Use Only

Feedback Signal (-)

┴2

Not Used -

C1

Not Used -

C2

Control Signal

Feedback 36

A

LS3

B A-C (Open Indication)

C D LS4

35

Adaption

E

Address

Y1

8

Internal Use Only

9

Internal Use Only

10

Internal Use Only

F

D-F (Closed Indication) Contact Rating: 5A 250 VAC Max.

Y2 G

800-543-9038 USA

50

PE

Actuator B

SYx-230MFT

866-805-7089 CANADA

SY2...6-230MFT

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

N

PC Tool Service Jack

Ball Valve Dimensions with SY... Series Actuators

B

C

B

B6VS_SYDIM MS

Dimensions with Flanged Valves B2VSS_SYDIMS

Dimensions with 2-Way Valves

C

D

D

Valve Body B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B219VS B220VS B224VS B225VS B232VS B239VS B240VS B249VS B250VS B265VS

COP 600 600 600 600 600 600 600 600 600 600 600 600 600 600

B280VS

600

B2050VSS-15 1000

Valve Nominal Size Inches DN [mm] ½” 15 ½” 15 ½” 15 ½” 15 ¾” 20 ¾” 20 1” 25 1” 25 1¼” 32 1½” 40 1½” 40 2” 50 2” 50 2½” 65 3”

Dimensions (Inches) A 2.25 2.25 2.25 2.25 3.00 3.12 3.37 3.62 3.97 4.37 4.75 4.68 5.37 6.25

B 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 8.00 8.00 8.00 8.00

C 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 13.00 13.00 13.00 13.00

D 8.00 8.00 8.00 8.00 8.00 3.12 16.00 9.00 9.50 17.50 19.00 19.50 20.00 20.00

80

6.75

8.00

13.00

21.00

½”

15

2.25

8.00

13.00

16.00

¾” 1” 1¼” 1½”

20 25 32 40

3.00 3.37 3.97 4.37

8.00 8.00 8.00 8.00

13.00 13.00 13.00 13.00

18.00 17.00 3.97 18.50

1000

2”

50

4.68

8.00

13.00

19.50

1000 600

2½” 3”

65 80

6.25 6.75

8.00 8.00

13.00 13.00

20.00 21.00

B219VSS B224VSS B232VSS B239VSS

1000 1000 1000 1000

B249VSS B265VSS B280VSS

800-543-9038 USA

A

SY8 SY5 SY4 SY3 SY2

SY3 SY2 SY1 & SY2 SY1 SY3

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

SY2

SY1 & SY2

SY1

A

Valve Body COP B650VS 200 B665VS 200 B680VS

Valve Nominal Size Inches DN [mm] 2” 50 2½” 65

A 7.00 7.50

Dimensions (Inches) B C D 8.00 13.00 22.00 8.00 13.00 22.00

200

3”

80

8.00

8.00

13.00

23.00

B6100VS 200

4”

100

9.00

12.00

15.00

27.00

B6150VS 200

6”

150

10.50

12.00

15.00

29.00

B6200VS 200 B6250VS 200

8” 10”

203 254

11.50 13.00

14.00 14.00

21.00 21.00

39.00 43.00

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

51

MFT Standard Configuration Code

P-10001 P-10002 P-10003 P-10004 P-10005 P-10006 P-10007 P-10009 P-10010 P-10013 P-10015 P-10016 P-10017 P-10018 P-10020 P-10028 P-10031 P-10063 P-10064 P-20001 P-20002 P-20003 P-20004 P-20005 P-30001 P-30002 P-30003 P-30004 P-30005 P-30006 P-40001 P-40002 P-40003 P-40004 P-40005

A01 A02 A03 A04 A05 A06 A07 A09 A10 A13 A15 A16 A17 A18 A20 A28 A31 A63 A64 W01 W02 W03 W04 W05 F01 F02 F03 F04 F05 F06 J01 J02 J03 J04 J05

Control

Motion

Input Range

Position Feedback

Running Time†

Torque %

Adaptation

2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 4.0 to 7.0 VDC 6.0 to 9.0 VDC 10.5 to 13.5 VDC 0.0 to 5.0 VDC 5.0 to 10.0 VDC 5.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 5.0 VDC 2.0 to 6.0 VDC 6.0 to 10.0 VDC 14.0 to 17.0 VDC 9.0 to 12.0 VDC 0.0 to 10.0 VDC 0.0 to 4.0 VDC 0.5 to 4.5 VDC 5.5 to 10.0 VDC 0.59 to 2.93 seconds 0.02 to 5.00 seconds 0.10 to 25.50 seconds 0.10 to 25.60 seconds 0.10 to 5.20 seconds Floating Point Floating Point Floating Point Floating Point Floating Point Floating Point On/Off On/Off On/Off On/Off On/Off

2.0 to 10.0 VDC 0.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 0.5 to 4.5 VDC 5.5 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 0.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 0.0 to 10.0 VDC

150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 100 150 150 150 150 150 150 150 150 150 150 100 100 100 150 75 150 75 100 100

100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual

*P-10001 is the default configuration. Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed. Note: V-codes used for NV…Series actuator. All other MFT actuators use P-codes. Note: Most popular configurations available at no additional cost. Note: If the configuration needed is not listed, please fill in pg 54 or call Customer Service. Note: For Non-Spring Return Actuators the 3-digit code can be used in place of the P… pre-set MFT configuration number.

SY MULTI-FUNCTION TECHNOLOGY Description MFT MFT MFT MFT MFT MFT MFT MFT MFT

800-543-9038 USA

52

Code ACE ACF ACH ACJ ACK ACM ACN ACP ACS

Control Input 2-10 VDC 0.5-10 VDC 4-20 mA 2-10 VDC 0.5-10 VDC 4-20 mA 2-10 VDC 0.5-10 VDC 4-20 mA

Built-in Feedback 2-10 VDC 0.5-10 VDC 2-10 VDC 2-10 VDC 0.5-10 VDC 2-10 VDC 2-10 VDC 0.5-10 VDC 2-10 VDC

866-805-7089 CANADA

Loss of Signal stop stop stop open open open close close close

Running Time actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

On/Off

Floating Point

PWM

Voltage

Configuration (Substitute ‘V’ for ‘P’ for NV actuators)

MFT Programming Codes, Flexible Products PRODUCTS MODEL LMX24-3-X1 LMX24-MFT-X1 NMX24-3-X1 NMX24-MFT-X1 AMX24-3-X1 AMX24-MFT-X1 GMX24-3-X1 GMX24-MFT-X1

Base Actuator Codes LX000 LX100 NX000 NX100 AX000 AX100 GX000 GX100

PWM Floating Point On/Off

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

Voltage

Configuration

Torque

Control Input

Feedback

45 in-lbs [5 Nm] 45 in-lbs [5 Nm] 90 in-lbs [10 Nm] 90 in-lbs [10 Nm] 180 in-lbs [20 Nm] 180 in-lbs [20 Nm] 360 in-lbs [40 Nm] 360 in-lbs [40 Nm]

On/Off, Floating Point 2-10 VDC (Default) On/Off, Floating Point 2-10 VDC (Default) On/Off, Floating Point 2-10 VDC (Default) On/Off, Floating Point 2-10 VDC (Default)

— 2-10 VDC — 2-10 VDC — 2-10 VDC — 2-10 VDC

(Substitute ‘V’ for ‘P’ for NV[F] actuators)

Code

P-10001 P-10002 P-10003 P-10004 P-10005 P-10006 P-10007 P-10009 P-10010 P-10013 P-10015 P-10016 P-10017 P-10018 P-10020 P-10028 P-10031 P-10063 P-10064 P-20001 P-20002 P-20003 P-20004 P-20005 P-30001 P-30002 P-30003 P-30004 P-30005 P-30006 P-40001 P-40002 P-40003 P-40004 P-40005

A01 A02 A03 A04 A05 A06 A07 A09 A10 A13 A15 A16 A17 A18 A20 A28 A31 A63 A64 W01 W02 W03 W04 W05 F01 F02 F03 F04 F05 F06 J01 J02 J03 J04 J05

Running Angle of Time Rotation/Stroke 95 (Default) 95 deg 150 (Default) 95 deg 95 (Default) 95 deg 150 (Default) 95 deg 95 (Default) 95 deg 150 (Default) 95 deg 95 (Default) 95 deg 150 (Default) 95 deg

Control

Power Supply 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC

VA Rating 2 5 4 6 5.5 6 6 7

Weight (lbs) 1.10 1.50 1.70 2.10 2.20 2.60 3.40 3.40

Motion

Input Range

Position Feedback

Running Time†

Torque %

Adaptation

2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 4.0 to 7.0 VDC 6.0 to 9.0 VDC 10.5 to 13.5 VDC 0.0 to 5.0 VDC 5.0 to 10.0 VDC 5.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 5.0 VDC 2.0 to 6.0 VDC 6.0 to 10.0 VDC 14.0 to 17.0 VDC 9.0 to 12.0 VDC 0.0 to 10.0 VDC 0.0 to 4.0 VDC 0.5 to 4.5 VDC 5.5 to 10.0 VDC 0.59 to 2.93 seconds 0.02 to 5.00 seconds 0.10 to 25.50 seconds 0.10 to 25.60 seconds 0.10 to 5.20 seconds Floating Point Floating Point Floating Point Floating Point Floating Point Floating Point On/Off On/Off On/Off On/Off On/Off

2.0 to 10.0 VDC 0.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 0.5 to 4.5 VDC 5.5 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 0.0 to 10.0 VDC 0.0 to 5.0 VDC None 2.0 to 10.0 VDC None 0.0 to 5.0 VDC 0.0 to 10.0 VDC

150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 100 150 150 150 150 150 150 150 150 150 150 100 100 100 150 75 150 75 100 100

100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual

*P-10001 is the default configuration.

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

53

Custom MFT Configuration Order Form FAX: USA Toll Free 1-800-228-8283

#1 Select an Actuator (use one sheet for each unique actuator/configuration)

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑

AF24-MFT US AF24-MFT-S US NF24-MFT US LF24-MFT US LF24-MFT-S US AF24-MFT95 US NV24-MFT US NVF24-MFT US NVF24-MFT-E US NVFD24-MFT US NVFD24-MFT-E US GMX24-MFT GMX24-MFTX1

Quantity ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑

AMX24-MFT AMX24-MFTX1 NMX24-MFT NMX24-MFTX1 LMX24-MFT LMX24-MFTX1 LRX24-MFT GMX24-MFT95 AMX24-MFT95 NMX24-MFT95 LMX24-MFT95 LHX24-MFT LUX24-MFT

Name _______________________________________________________________________________

Quantity ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______

Company ____________________________________________________________________________ Address _____________________________________________________________________________ City_______________________________________ State _____________Zip _____________________ Phone_____________________________________ Fax_______________________________________ Email _____________________________________ FIELD LABELING: LBL-MFT



(-S=Auxiliary Switch)

Custom configuration labels required 1-3/8” X 1-¼” orange labels preprinted to your specifications 12 label sets per sheet. Includes configuration code and wiring labels.

#2 Create a Custom Configuration g

1 Angle of rotation setting

Deactivated (Default)

The following settings

Activated

The following settings mechanical angle of rotation.

-

refer to the full angle of rotation of 95º. are automatically adapted to the effective

Manual triggering by pressing the push button twice. Automatic triggering each time the unit is powered up or by pressing the push button twice. VDC

3 Feedback Signals U5

Floating Point

2 – 10

0.2 to 5.0 seconds

0 – 10

0.1 to 25.5 seconds

Variable

On/Off

0.59 to 2.93 seconds

Start

.

Variable

Stop

.

Start

.

Stop

.

Position Feedback U

DC 2...10 V (Default)

Position Feedback U

DC 0...10 V

Position Feedback U

Start

DC

.

V (0...8 V)

Finish DC

.

V (2...10 V)

The finish must be at least 2 V above the start!

150 seconds (Default) Running time

4 Running Time

5 Override control and

Min. (min. position)

=

%

(0...100%)

(beginning of working range) default 0

ZS

=

%

(0...100%)

(0% = Min.; 100% = Max.) default 50

=

%

(0...100%)

(end of working range) default 100

electronic angle of rotation limiting 800-543-9038 USA

54

seconds (75...300 seconds) (in 5 second increments)

Note:

The sound power level [dB(A)] increases when the running time is below 150 seconds.

(intermediate position)

Max. (max. position)

866-805-7089 CANADA

LM NM AM GM Others

35…150 seconds 45…170 seconds 90…300 seconds 90…300 seconds 75…300 seconds

203-791-8396 LATIN AMERICA / CARIBBEAN

P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.

2 Control Types

PWM