P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Ball Valve Features and Benefits B2...VS/VSS, B3...L, B6...VS
● 2-way and 3-way configuration
● NPT and flanged connections
● Bronze with stainless steel trim (2-way)
● Wide Cv range
● Nickel plated brass body (3-way)
● Air gap for use with hot water and steam systems
● Reduced and full port capacities
● Live load low maintenance stem packing
● Two piece construction
● 2 year warranty
● Electronic actuation
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
1
Flow Pattern, Operation and Installation Ball Valves FLOW PATTERN
Open CCW
Flow Direction
B to A Open CW
Closed CW
B to AB Open CCW
NOTE: B3…L are piped differently than B3 CCV Valves.
VS SERIES BALL VALVE PIPING DIAGRAMS 2-way Valve Piping Diagram
3-way Diverting Valve Piping Diagram
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
NOTE: To avoid torque increase during off season shut down, or other periods of inactivity longer than 1 month - the valve should be exercised (actuator or manually driven full open-closed cycle) at least once per month. This is necessary to avoid any application problems after an off season shut down.
PIPING/MOUNTING ORIENTATION Assembly can be mounted horizontally or vertically for water applications. For steam applications the valve can be mounted vertically but if mounted horizontally the valve must be 90° off center of the pipe. Do not install with actuator below pipe.
(Water application only)
(Steam or water application)
800-543-9038 USA
2
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Piping Sizing Geometry Ball Valves
Cv
TYPE
MODEL #
¾” Fp Cv
1 2 4 15 30 51 43 68 48 84 177 108 389 503 370 6.4 12.8 11 34 57 87 330 420 600 1200 3300 9000 12400
2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 2W NPT 3W NPT 3W NPT 3W NPT 3W NPT 3W NPT 3W NPT 2W FLG 2W FLG 2W FLG 2W FLG 2W FLG 2W FLG 2W FLG
B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B219VS/VSS B220VS B224VS/VSS B225VS B232VS/VSS B239VS/VSS B240VS B249VS/VSS B250VS B265VS/VSS B280VS/VSS B315L B320L B325L B332L B340L B350L B650VS B665VS B680VS B6100VS B6150VS B6200VS B6250VS
1.0 2.0 3.8 8.9 30.0 51.0 — — — — — — — — — 5.5 12.8 — — — — — — — — — — —
1” Fp Cv
1¼” Fp Cv
1½” Fp Cv
2” Fp Cv
LINE SIZE 2½” 3” Fp Cv Fp Cv
1.0 1.9 3.6 7.2 21.6 26.5 43.0 68.0 — — — — — — — 5.0 11.8 11.0 — — — — — — — — — —
— — — — 17.4 19.9 36.1 48.3 48.0 — — — — — — 4.8 11.0 10.9 34.0 — — — — — — — — —
— — — — 15.6 17.3 30.5 36.7 44.6 84.0 177.0 — — — — — 10.5 10.7 32.8 57.0 — — — — — — — —
— — — — — — 25.8 29.2 37.9 69.7 102.7 108.0 389.0 — — — — 10.4 29.9 51.9 87.0 330.0 — — — — — —
— — — — — — — — 35.0 59.6 77.9 100.4 221.7 503.0 — — — — 28.2 47.4 82.8 207.9 420.0 — — — — —
— — — — — — — — — 55.4 67.3 91.8 159.5 352.1 370.0 — — — — 44.9 77.9 155.1 319.2 600.0 — — — —
4” Fp Cv
5” Fp Cv
6” Fp Cv
— — — — — — — — — — — 83.2 124.5 221.3 296.0 — — — — — 72.3 122.1 214.2 384.0 1200.0 — — —
— — — — — — — — — — — — — 186.1 251.6 — — — — — — — 184.8 300.0 804.0 — — —
— — — — — — — — — — — — — — 229.4 — — — — — — — — 264.0 600.0 3300.0 — —
8” Fp Cv
10” Fp Cv
— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 480.0 — 1716.0 1254.0 9000.0 3870.0 — 12400.0
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
VALVE SIZE ½” ½” ½” ½” ¾” ¾” 1” 1” 1¼” 1½” 1½” 2” 2” 2½” 3” ½” ¾” 1” 1¼” 1½” 2” 2” 2½” 3” 4” 6” 8” 10”
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
3
Wiring Instructions Ball Valves GENERAL WIRING INSTRUCTIONS
Always read the controller manufacturer’s installation literature carefully before making any connections. Follow all instructions in this literature. If you have any questions, contact the controller manufacturer and/or Belimo. Transformer(s) Typically actuators require a 24 VAC class 2 transformer and draw a maximum of 10 VA per actuator. The actuator enclosure cannot be opened in the field, there are no parts or components to be replaced or repaired. – EMC directive: 89/336/EEC – Software class A: Mode of operation type 1 – Low voltage directive: 73/23/EEC Typical transformer sizing Actuator Series Voltage AF 24 LF 24 AR 24 NR 24 LR 24
Max. VA Per Actuator 10 6 6 4 3
CAUTION It is good practice to power electronic or digital controllers from a separate power transformer than that used for actuators or other end devices. The power supply design in our actuators and other end devices use half wave rectification. Some controllers use full wave rectification. When these two different types of power supplies are connected to the same power transformer and the DC commons are connected together, a short circuit is created across one of the diodes in the full wave power supply, damaging the controller. Only use a single power transformer to power the controller and actuator if you know the controller power supply uses half wave rectification. Multiple actuators, one transformer Multiple actuators may be powered from one transformer provided the following rules are followed: 1. The TOTAL current draw of the actuators (VA rating) is less than or equal to the rating of the transformer. 2. Polarity on the secondary of the transformer is strictly followed. This means that all No. 1 wires from all actuators are connected to the common leg on the transformer and all No. 2 wires from all actuators are connected to the hotleg. Mixing wire No. 1 & 2 on one leg of the transformer will result in erratic operation or failure of the actuator and/or controls. Multiple actuators, multiple transformers Multiple actuators positioned by the same control signal may be powered from multiple transformers provided the following rules are followed: 1. The transformers are properly sized. 2. All No. 1 wires from all actuators are tied together and tied to the negative leg of the control signal. See wiring diagram. Wire type and wire installation tips For most installations, 18 or 16 Ga. cable works well with Belimo actuators. Use code-approved wire nuts, terminal strips or solderless connectors where wires are joined. It is good practice to run control wires unspliced from the actuator to the controller. If splices are unavoidable, make sure the splice can be reached for possible maintenance. Tape and/or wire-tie the splice to reduce the possibility of the splice being inadvertently pulled apart. Wire length for actuator installation Keep power wire runs below the lengths listed in the following tables. If more than one actuator is powered from the same wire run, divide the allowable wire length by the number of actuators to determine the maximum run to any single actuator. See section 1 for specific transformer sizing information for the actuator selected. Example: 3 actuators, 16 Ga wire 350 Ft ÷ 3 Actuators = 117 Ft. Maximum wire run
800-543-9038 USA
4
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
WARNING The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment to the actuator must be made with flexible conduit.
Nomenclature Ball Valves B2
24
VS
AMX
Valve
Valve Size
B2 = 2-way B3 = 3-way B6 = 2-way Flanged
15-80 = ½” to 3” Construction/ 1-370 50-250 = 2” to Material 10” VS = Bronze Body, (Flanged) Stainless Steel Ball and Stem VSS = Stainless Steel Body, Ball and Stem L = Nickel Plated Brass Body, Chrome Plated Brass Ball and Stem
Industrial
24
-MFT-X1
Actuator Type Power Supply Control
Cv
Non-Spring Return 24 = 24 VAC/DC LM… 120 = 120 VAC NM… 230 = 230 VAC AM… GM… SY… SY…P Spring Return LF… NF… AF… Electronic Fail-Safe GK...
-3-X1 = On/Off, Floating Point -MFT-X1 = Multi-Function Technology -MFT95-X1 = 0-135 Ω
-S = Built-in Auxiliary Switch
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Ordering Example 3 1
For MFT orders only - select programming code
Choose the valve actuator combination.
B224VS+AMX24-MFT-X1
+NO
+Tagging (if needed) 4
2
Specify preference or configuration.
Does order require tagging?
Set-Up
P-10001 (A01)
Non-Spring Models NO = Normally Open NC = Normally Closed
P-100xx (Axx) P-200xx (Wxx)
Spring Return Models NO/FO = Normally Open/Fail Open NO/FC = Normally Open/Fail Closed NC/FO = Normally Closed/Fail Open NC/FC = Normally Closed/Fail Closed Refers to valve ports A to AB.
5
Complete Ordering Example:
800-543-9038 USA
P-300xx (Fxx) P-400xx (Jxx) X-XXXXX X-XXXXX
Control voltage applications Pulse width modulation applications Floating point applications On/off applications Create custom MFT configuration code Create custom MFT configuration in the field with MFT actuator PC software
Tagging: Valves may be tagged per customer specification. ($10.00 per tag) Example: AHU-1 FCU-2 Part number for tagging: 99981-00101
B224VS+AMX24-MFT-X1+NO+A01 866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
5
B2...VS Series, 2-way, Ball Valve Bronze Body, Stainless Steel Ball and Stem • Live-load packing set • Stainless steel ball & stem • Blow-out proof stem design
Application This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV Box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionality which facilitates the use of various control input.
½ ½ ½ ½ ¾ ¾ 1 1 1¼ 1½ 1½ 2 2 2½ 3
15 15 15 15 20 20 25 25 32 40 40 50 50 65 80
B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B219VS B220VS B224VS B225VS B232VS B239VS B240VS B249VS B250VS B265VS B280VS
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
1 2 4 15 30 51 43 68 48 84 177 108 389 503 370
LM Series
2-way NPT
NM
DN [mm]
AM Series
Inches
LF Series
Cv
Suitable Actuators Spring Non-Spring Return Return
10
Pressure rating Media temp. range Close-off pressure Maximum differential pressure (ΔP)
600 psig WOG -22°F to +280°F (-30°C to +138°C) 600 psig @ 100°F <600 psig
Flow Patterns
800-543-9038 USA
6
SY Series
Gland Stem Jam nut Body seal Body
Type
GM Series
6 7 8 9 10
reinforced PTFE reinforced PTFE 316 stainless steel reinforced PTFE w/ Durafill B16 (¾” - 1”) stainless steel B584 (1¼” - 3”) stainless steel B16 brass 316 stainless steel stainless steel PTFE (1-1/4” to 3”) B584-C84400 bronze
Valve Nominal Size
NF
Sizes Type of end fitting Materials: 1 Stem packing 2 Stem bearing 3 Ball 4 Seat (x2) 5 Retainer
chilled or hot water, glycol, 35# steam modified equal percentage 90° rotation valve open CW, valve closed CCW ½”, ¾”, 1”, 1¼”, 1½”, 2”, 2½”, 3” SAE NPT (female connections)
AF Series
Technical Data Media Flow characteristic Action
• Up to 35 psi steam • ½” - 600 PSIG WOG, Cold Non-Shock. • Federal Specification: WW-V-35C,Type II Composition: BZ Style: 3
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
B2...VSS Series, 2-way, Ball Valve Stainless Steel Body, Ball and Stem • Live-load packing set • Stainless steel ball & stem • Blow-out proof stem design
Application These threaded valves are designed to provide modulating or two position control of hot or chilled water and saturated steam systems under 50 psi. Typical applications include reheat coils, vav terminal control, unit ventilators, and air handlers, especially in areas which have minimum profile requirements. • Up to 50 psi steam • ½” - 2000 PSIG WOG, Cold Non-Shock. • Federal Specification: WW-V-35C,Type II, Composition: SS Style: 3
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
6 7 8 9 10
Gland Stem Jam nut Body seal Body
20
B219VSS
1
25
B224VSS
48
1¼
32
B232VSS
84
1½
40
B239VSS
108
2
50
B249VSS
503
2½
65
B265VSS
SY Series
¾
43
AM NM Series Series
30
Suitable Actuators Spring Non- Spring Return Return
GM Series
reinforced PTFE reinforced PTFE 316 stainless steel reinforced PTFE w/ Durafill B16 (¾” - 1”) stainless steel B584 (1¼” - 3”) stainless steel A276-316 316 stainless steel stainless steel PTFE (1¼” to 3”) A351-CF8M 316 stainless steel
Cv 15
Valve Nominal Size Type DN Inches 2-way NPT [mm] ½ 15 B2050VSS-15
LF Series
Sizes Type of end fitting Materials: 1 Stem packing 2 Stem bearing 3 Ball 4 Seat (x2) 5 Retainer
chilled or hot water, glycol, 50# steam modified equal percentage 90° rotation valve open CW, valve closed CCW ½”, ¾”, 1”, 1¼”, 1½”, 2”, 2½” SAE NPT (female connections)
AF Series
Technical Data Media Flow characteristic Action
10
Pressure rating Media temp. range Close-off pressure Maximum differential pressure (ΔP)
2000 psig WOG (½” - 1”) -22°F to +298°F (-30°C to +148°C) 600 psig @ 100°F <600 psig
Flow Patterns
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
7
B3...L Series, 3-way, Ball Valve Chrome Plated Brass Ball and Nickel Plated Stem
Application This valve is typically used in air handling and fan coil units on heating or cooling coils, unit ventilators, VAV box re-heat coils, and bypass loops. This valve is suitable for use as a diverting valve only.
15
B315L
12.8
¾
20
B320L
11
1
25
B325L
34
1¼
32
B332L
57
1½
40
B340L
87
2
50
B350L
Sizes Type of end fitting Materials: Body Ball Stem Stem seal Valve seat Leakage Pressure rating
Media temp. range Close-off pressure Maximum differential pressure (ΔP)
chilled or hot water, 60% glycol modified linear 90° rotation B to A open CW, B to AB open CCW ½”, ¾”, 1”, 1¼”, 1½”, 2” NPT female ends nickel plated brass chrome plated brass nickel plated brass o-ring EPDM PTFE ANSI VI 600 psig WOG 600 psi DN 15-25 (B3...L) 400 psi DN 32-50 (B3...L) 0°F to 250°F [-18°C to +120°C] 200 psi 50 psi
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data Media Flow characteristic Action
NR
w
½
LR Series
6.4
Suitable Actuators Non-Spring Electronic Return Fail-Safe
AR Series
Inches DN [mm]
Spring Return LF Series
Cv
Type 3-way NPT
AF Series
Valve Nominal Size
Flow Patterns
B to A Open CW
800-543-9038 USA
8
B to AB Open CCW
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
B6...VS Series, 2-way, Ball Valve Cast Iron Body, Stainless Steel Ball and Stem • • • • •
Same end to end dimension as conventional flanged iron gate valve Fast quarter turn open or closed operation Stainless steel ball and stem Positive shut-off Two-piece body construction
Application • Ideal for water service where a non-corrosive, clean cosmetic appearance is required. • Optional FDA approval, suitable for potable water and food contact. • Sizes: 2”-10” (50-250mm) • 200 psi CWP (cold water pressure) (non-shock) Approved valves shall comply with the American Standard for face-to-face dimensions (ANSI B16.10) for Class 125 cast iron flanged gate valves.
Sizes Type of end fittings Materials: 1 Body 2 End cap 3 Ball 4 Seats 5 Stem 6 Packing 7 Gland 8 Gasket 9 Nut
Pressure rating Media temp. range Close-off pressure Maximum differential pressure (ΔP)
chilled or hot water, glycol, 50# steam modified equal percentage 90% rotation valve open CW, valve closed CCW 2”, 2½”, 3”, 4”, 6”, 8”, 10” flanged 125# ANSI bolt pattern cast iron - ASTM A126 Class B cast iron - ASTM A126 Class B 304 stainless steel - ASTM A351 PTFE 304 stainless steel - AISI 304 PTFE cast iron - ASTM A126 Class B PTFE steel - ASTM A6
Cv 330
Valve Nominal Size Inches DN [mm] 2 50
Type 2-way NPT B650VS
420
2½
65
600
3
80
B680VS
1200
4
100
B6100VS
3300
6
150
B6150VS
9000
8
203
B6200VS
12400
10
254
B6250VS
Suitable Actuators Non-Spring Return
B665VS SY Series
Technical Data Media Flow characteristic Action
The dimensions and drilling of end flanges conform to the American cast iron flange standard, Class 125 (ANSI B16.1).
200 psig WOG -22°F to +298°F (-30°C to +148°C) 200 psig @ 140°F <200 psi
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
9
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
This Page Intentionally Left Blank
800-543-9038 USA
10
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Ball Valve Product Range Overview VS/VSS Ball Valve Product Range B2...VS/VSS, B3...L, B6...VS
Type
½
15
B2050VS-15
30
¾
20
B219VS
51
¾
20
B220VS
43
1
25
B224VS
68
1
25
B225VS
48
1¼
32
B232VS
1½
40
B239VS
1½
40
B240VS
108
2
50
B249VS
389
2
50
B250VS
190
2½
65
B265VS
370
3
80
B280VS
15
½
15
B2050VSS-15
30
¾
20
B219VSS
43
1
25
B224VSS
48
1¼
32
B232VSS
84
1½
40
B239VSS
108
2
50
B249VSS
190
2½
65
B265VSS
370
3
80
B280VSS
6.4
½
15
B315L
12.8
¾
20
B320L
11
1
25
B325L
34
1¼
32
B332L
57
1½
40
B340L
87
2
50
B350L
330
2
50
B650VS
420
2½
65
B665VS
600
3
80
B680VS
1200
4
100
B6100VS
3300
6
150
B6150VS
9000
8
200
B6200VS
12400
10
250
B6250VS
Product Features Modified equal percentage of flow for B2, B3 and B6. Modified linear flow for B3.
AR Series
NR
LR Series
GM Series
AM Series
NM Series
GK
GM Series
84 177
Mode of Operation The control valve is operated by an electronic actuator that responds to a standard voltage for on/off control, by a proportional VDC/4…20 mA, or 3-point control system. The actuator will then move the ball of the valve to the position dictated by the contol signal thus changing the flow.
GK
15
Actuator Specifications Control type on/off, floating point, proportional, 2-10 VDC multi-function technology (MFT) Manual override LM, NM, GM, AM, SY, AF, NF, GK Electrical connection 3 ft [1m] cable with ½” conduit fitting Valve Specifications Service Flow characteristic
GK
B2050VS-04
LF Series
B2050VS-02
15
NF Series
15
½
AF Series
½
4
LF
2
Electronic Fail-Safe
NF
B2050VS-01
Spring Return
AF Series
15
Non-Spring Return
LFR Series
½
2-Way Flanged
Sizes End fitting Materials Body
Ball
AFR Series
1
3-way NPT
SY Series
2-way NPT
LM Series
DN [mm]
NM Series
Inches
AM Series
Cv
Suitable Actuators
SY Series
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Valve Nominal Size
Stem Seats 2-way 3-way Packing 2-way NPT 2-way flanged Media temp range B2..VS, B6..VS B2..VSS B3...L Body pressure rating 3-way Maximum inlet pressure Steam Water Leakage
800-543-9038 USA
866-805-7089 CANADA
chilled or hot water, (60% glycol), steam modified equal percentage (2-way), modified linear (3-way)
½” to 10” NPT (B2...VS & B3.. L) flanged (B6...VS) bronze (B2..VS), stainless steel (B2..VSS), nickel plated brass (B3...L), cast iron (B6..VS) stainless steel, bronze (½”) chrome plated brass (B3...L) stainless steel, bronze (½”) nickel plated brass (B3...L) MPTFE LPTFE RPTFE PTFE -22°F to +280°F [-30°C to +138°C] -22°F to +298°F [-30°C to +148°C] 0°F to 250°F [-18°C to +120°C] up to 2000 psig WOG 600 psi DN 15-25 (B3...L) 400 psi DN 32-50 (B3...L) 35 psi B2..VS 50 psi B2..VSS, B6..VS 50 psi B3...L ANSI class VI
203-791-8396 LATIN AMERICA / CARIBBEAN
11
LF Actuators, On/Off Dimensions with 2-Way Valve
Models w/built-in Aux. Switch
on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 120 VAC ± 10% 50/60 Hz
Dimensions with 3-Way Valve
w/built-in Aux. Switch
Technical Data Control Power supply LF24(-S) US LF120(-S) US Power consumption LF24(-S) US
A 6.75 6.75 6.75 6.70 6.70
Dimensions (Inches) B C D F 2.00 6.75 2.25 4.00 2.00 6.75 2.25 4.00 2.00 6.75 2.25 4.00 2.00 8.00 2.25 6.25 2.00 8.00 2.25 6.25
running holding running holding
5W 2.5 W LF120(-S) US 5.5 W 3.5 W Transformer sizing 7 VA, class 2 power source Electrical connection ½” conduit connector (-S models have 2 cables) 3 ft. [1m], 18 GA appliance cable Electrical protection 120V actuators double insulated Overload protection electronic throughout rotation Angle of rotation 95° Spring return direction reversible with CW/CCW mounting Position indication visual indicator 0° to 90° Running time <40 to 75 sec. (on/off) spring <25 sec. @ -4°F to +122°F [-20°C to +50°C] <60 sec. @ -22°F [-30°C] Ambient temperature -22° F to +122° F [-30° C to +50° C] Housing NEMA 2 Agency listings† UL 873, CSA C22.2 No. 24 certified, CE Quality standard ISO 9001 Noise level max. 62 dB(A) LF...-S US Auxiliary switch
COP 50 50 50 50 1000
Valve Nominal Size Inches DN [mm] ½ 15 ½ 15 ½ 15 ½ 15 ½ 15
Valve Body B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B2050VSS-15
Valve Body
COP
B315L B320L B325L
50 50 50
Valve Nominal Size DN Inches [mm] ½ 15 ¾ 20 1 25
Dimensions (mm) A
B
C
2.63” [67] 1.73” [44] 1.42” [36] 3.01” [78] 1.81” [46] 1.63” [42] 3.42” [87] 1.81” [46] 1.77” [45]
1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed, adjustable 0° to 95° (double insulated)
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3, Type of action 1.AA (1.AA.B for -S models)
800-543-9038 USA
12
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LF24 US LF24-S US LF120 US LF120-S US
LF Actuators, On/Off W047
Wiring Diagrams 24 VAC Transformer
2
Provide overload protection and disconnect as required.
2 + Hot
CAUTION Equipment damage!
LF24 US
Actuators may be connected in parallel. Power consumption must be observed.
3
2
On/Off wiring for 24 VAC/DC
3
Actuator may also be powered by 24 VDC.
4
For end position indication, interlock control, fan startup, etc., LF24-S US and LF120-S US incorporates a built-in auxiliary switch: 1 x SPDT, 6A (1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.
W049-LF-08
1
1 Common
Line Volts
Meets cULus or UL and CSA requirements without the need of an electrical ground connection.
WARNING Live Electrical Components! On/Off wiring for 120 VAC W048-AUX
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary Switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
13
LF24-MFT US Actuators, Multi-Function Technology Dimensions with 2-Way Valve
Models w/built-in Aux. Switch
Technical Data Control Control signal Power consumption
running holding
Transformer sizing Electrical connection (-S models have 2 cables) Overload protection Input impedance
Feedback Angle of rotation Direction of rotation
spring motor
Position indication Running time spring Ambient temperature Housing Agency listings Noise level Quality standard LF24-MFT-S US Auxiliary switch
MFT 2 to 10 VDC (4-20mA with 500 Ω resistor) 2.5 W 1W 5 VA (class 2 power source) ½” conduit connector 3 ft. [1m], 18 GA appliance cable electronic throughout 0° to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20mA 750 Ω for PWM 500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max 95° reversible with CW/CCW mounting reversible with built-in visual indicator <40 to 75 sec. (on/off) 150 sec. independent of load (proportional) <25 sec. @ -4°F to +122°F [-20°C to +50°C] <60 sec. @-22°F [-30°C] -22° F to +122° F [-30° C to +50° C] NEMA 2 UL 873, CSA C22.2 No. 24 certified, CE max. 62 dB(A) ISO 9001
COP 50 50 50 50 1000
Valve Nominal Size Inches DN [mm] ½ 15 ½ 15 ½ 15 ½ 15 ½ 15
A 6.75 6.75 6.75 6.70 6.70
Dimensions (Inches) B C D F 2.00 6.75 2.25 4.00 2.00 6.75 2.25 4.00 2.00 6.75 2.25 4.00 2.00 8.00 2.25 6.25 2.00 8.00 2.25 6.25
Dimensions with 3-Way Valve
Valve Body
COP
B315L B320L B325L
50 50 50
Valve Nominal Size DN Inches [mm] ½ 15 ¾ 20 1 25
Dimensions (mm) A
B
C
2.63” [67] 1.73” [44] 1.42” [36] 3.01” [78] 1.81” [46] 1.63” [42] 3.42” [87] 1.81” [46] 1.77” [45]
1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed, adjustable 0° to 95° (double insulated)
800-543-9038 USA
14
Valve Body B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B2050VSS-15
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LF24-MFT US LF24-MFT-S US
Wiring Diagrams
24 VAC/DC Transformer Line Volts
CAUTION Equipment damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. Actuators may also be powered by 24 VDC.
4
IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).
5
Triac A and B can also be contact closures.
7
Common
(2)
Hot
(3)
Y Input
(5)
U Output
a
(–)
Feedback VDC (+)
CCW CW
3
6
Position
(1)
…MFT
On/Off control W041
2
W043
LF24-MFT US Actuators, Multi-Function Technology
24 VAC Transformer (AC only)
Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. Position feedback cannot be used with Triac sink controller. The actuators internal common reference is not compatible.
(1)
Line Volts 7
6
Position
(–)
Feedback VDC (+)
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel.
Common
(2)
+ Hot
(3)
Y Input
(5)
U Output
CCW CW
…MFT
PWM, triac source and sink
WARNING Live Electrical Components!
W302
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
...MFT
Floating Point control
Propotional 2 to 10 or 4 to 20 mA control signal
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
15
NF Actuators, On/Off Dimensions with 2-Way Valve
C
F
A
B
D
Models w/built-in Aux. Switch
Technical Data Control Power consumption NFB24-X1 NFBUP-X1 Transformer sizing
Electrical connection (-S model has 2 cables) Electrical protection Overload protection Angle of rotation Position indication Running time Ambient temperature Housing Agency listings Noise level
COP 400 200 1000
Valve Nominal Size Dimensions (Inches) Inches DN [mm] A B C D F ¾ 20 7.00 2.00 8.00 3.37 6.25 ¾ 20 7.00 2.00 8.00 3.37 6.25 ¾ 20 7.00 2.00 8.00 3.37 6.25
on/off running holding running holding NFB24-X1 NFBUP(-S)-X1
6W 2.5 W 6W 2.5 W 8.5 VA (class 2 power source) 6 VA @ 24 VAC (class 2 powe source) 6.5 VA @ 120 VAC 9.5 VA @ 240 VAC ½” conduit connector 3 ft. [1m], 18 GA appliance cables 120V actuators double insulated electronic throughout 0° to 95° rotation 95° visual indicator control <75 seconds spring <20 seconds -22° F to +122° F [-30° C to +50° C] NEMA 2 / IP54 UL 873, CSA C22.2 No. 24 certified, CE max. 45 dB(A)
NFBUP-S-X1 Auxiliary switch
2 x SPDT, 3A (0.5A inductive) @ 250 V
800-543-9038 USA
16
Valve Body B219VS B220VS B219VSS
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
NFB24-X1 NFBUP-X1 NFBUP-S-X1
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
NF Actuators, On/Off
1
2
Provide overload protection and disconnect as required.
24 VAC Transformer 1 Common
Line Volts
CAUTION Equipment damage!
2 + Hot
3
Actuators may be connected in parallel. Power consumption must be observed.
3
Actuators may also be powered by 24 VDC.
4
For end position indication, interlock control, fan startup, etc., NF24-S US incorporates a built-in auxiliary switch: 1 x SPDT, 7A (2.5A) @ 250 VAC, UL listed, adjustable 5° to 85°.
NFB24-X1
2
On/Off wiring for NFB24-X1 W066_NFB(X)UP
1
W063_NFB(X)
Wiring Diagrams
Meets cULus or UL and CSA requirements without the need of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
NFBUP-X1 NFBUP-S-X1
W067_NFB(X)UP-S
On/Off wiring for NFBUP-X1, NFBUP-S-X1
Wht
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Blk
NFBUP-S-X1 Auxiliary Switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
17
NF Actuators, Multi-Function Technology Dimensions with 2-Way Valve
C
F
A
B
D
NFX24-MFT-X1 NFX24-MFT-S-X1 Technical Data Control Control signal Power supply Power consumption
running holding
Transformer sizing Electrical connection Overload protection Input impedance
Feedback output Angle of rotation Direction of rotation Position indication Running time
spring motor motor spring
Ambient temperature Housing Agency listings
Noise level
NFX24-MFT-S-X1 Auxiliary switch
MFT 2 to 10 VDC, (4 to 20 mA with 500 Ω resistor) 24 VAC ± 20% 50/60 Hz 24 VDC ± 20% / -10% 6.5 W 3W 9 VA, (class 2 power source) ½” conduit connector 3 ft. [1m], 18 GA appliance cable electronic throughout 0 to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max 95° reversible with CW/CCW mounting reversible with built-in visual indicator, 0° to 95° 150 seconds (default), variable (40 to 220 seconds) <20 sec @ -4°F to +122°F [-20°C to +50°C]; <60 sec @ -22°F [-30°F] -22°F to +122°F [-30°C to +50°C] NEMA 2 / IP54, Enclosure Type 2 cULus acc. to UL60730-1A/ -2-14, CAN/ CSA E60730-1:02, CE acc. to 2004/108/EC & 2006/95/EC <40 dB(A) motor @ 150 seconds, run time dependent <62 dB(A) spring return
COP 400 200 1000
Valve Nominal Size Dimensions (Inches) Inches DN [mm] A B C D F 7.00 2.00 8.00 3.37 6.25 ¾ 20 ¾ 20 7.00 2.00 8.00 3.37 6.25 ¾ 20 7.00 2.00 8.00 3.37 6.25
2 x SPDT, 3A (0.5A) @ 250 VAC, UL Approved one set at +10°, one adjustable 10° to 90°
800-543-9038 USA
18
Valve Body B219VS B220VS B219VSS
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
NF Actuators, Multi-Function Technology 4
24 VAC Transformer
4
IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).
5
Triac A and B can also be contact closures.
7
Wht (3) Y1 Input, 2 to 10V 7
Pnk (4) Y2 Input Grn (5) U Output, 2 to 10V CCW CW
VDC/4-20 mA 10
24 VAC Transformer
Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. Position feedback cannot be used with Triac sink controller. The actuators internal common reference is not compatible.
W400_A_11
Actuators may also be powered by 24 VDC.
Red (2) + Hot 500 Ω Ω 1/4 watt
(–) Control Signal (+) 4 to 20 mA or 2 to 10 VDC
Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.
3
6
Volts
CAUTION Equipment damage!
5
Blk (1) Common
Line
2
3
W400_A_11
Wiring Diagrams
5
4
Blk (1) Common –
Line Volts
Red (2) Hot +
A 8 (–) 2 to 10 VDC Feedback Signal (+)
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel. Meets cULus or UL and CSA requirements without the need of an electrical ground connection.
Wht (3) Y1 Input
B Pnk (4) Y2 Input
9
Org (5) U Output 2 to 10V
Direction of rotation switch CCW
CCW
CW
CW
B 5
A
A
B 5
Floating Point During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
24 VAC Transformer (AC only)
W400_A_11
WARNING Live Electrical Components! 5
4
Blk (1) Common
Line 8
Volts
Red (2) + Hot Wht (3) Y Input Pnk (4) Y2 Input Org (5) U Output
Position (–) Feedback VDC (+)
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
24 VAC/DC Transformer
4
W400_A_11
PWM 5
3
Blk (1) Common
Line Volts
Red (2) Hot a
Position Feedback VDC
Wht (3) Y Input Pnk (4) Y2 Input Org (5) U Output
(–) (+)
W400_A_11
Two Position 5
24 VAC Transformer (AC Only)
Blk (1) Common
Line Volts Ω (–) Control Signal 2-10 VDC or 4 to 20 mA (+)
7
Red (2) + Hot
A B C
Wht (3) Y1 Input, 2 to 10V Pnk (4) Y2 Input Org (5)
500 Ω 1/4 watt
Functions Min* Mid* Max* Normal**
a
b
c
0% 50% 100% Control mode acc. to Y
* Default selectable 0-100%. See Configuration Data Sheet. ** Customizable. See Configuration Data Sheet.
Override Control to Min, Mid, Max, Positions
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
19
NF Actuators, Multi-Function Technology Dimensions with 2-Way Valve
C
F
A
B
D
NFX24-MFT95-X1 Technical Data Control Control signal Power supply Power consumption
running holding
Transformer sizing Electrical connection Overload protection Input impedance
Feedback output Angle of rotation Direction of rotation Position indication Running time
spring motor control spring
Ambient temperature Housing Agency listings
Noise level
MFT 0-135 24 VAC ± 20% 50/60 Hz 24 VDC ± 20% / -10% 6.5 W 3W 9 VA (class 2 power source) ½” conduit connector 3 ft. [1m], 18 GA appliance cable electronic throughout 0 to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max 95° (adjustable with mechanical end stop, 35° to 95°) reversible with CW/CCW mounting reversible with built-in visual indicator, 0° to 95° 150 seconds (default), variable (40 to 220 seconds) <20 sec @ -4°F to +122°F [-20°C to +50°C]; <60 sec @ -22°F [-30°F] -22°F to +122°F [-30°C to +50°C] NEMA 2 / IP54, Enclosure Type 2 cULus acc. to UL60730-1A/ -2-14, CAN/ CSA E60730-1:02, CE acc. to 2004/108/EC & 2006/95/EC <40 dB(A) motor @ 150 seconds, run time dependent, <62 dB(A) spring return
800-543-9038 USA
20
Valve Body B219VS B220VS B219VSS
866-805-7089 CANADA
COP 400 200 1000
Valve Nominal Size Dimensions (Inches) Inches DN [mm] A B C D F 7.00 2.00 8.00 3.37 6.25 ¾ 20 ¾ 20 7.00 2.00 8.00 3.37 6.25 ¾ 20 7.00 2.00 8.00 2.25 6.25
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models
203-791-8396 LATIN AMERICA / CARIBBEAN
NF Actuators, Multi-Function Technology
Provide overload protection and disconnect as required.
Line
22
R
Series 90 high limit control - 280 Ω
Line
Red (2) + Hot Wht (3) Wht (4) Wht (5) Wht (6)
R B
24
Damper Position
Series 90 Controller
W R B
Blk (1) Common
Volts
Red (2) + Hot
23
A Wht (3) W Wht (4) R
B
-MFT95-X1
21 Line
No. of actuators Resistance 2 140 Ω 3 71.5 Ω 4 47.5 Ω 5 37.5 Ω 6 28 Ω Resistor Kit No. ZG-R03
Wht (3) Wht (4) Wht (5) Wht (6) To other actuators
Red (2) + Hot Wht (3) W
Line
R
Volts
B
24
B
B
22
Wht (6) ‘U5’ Output 2 to 10 VDC
Controller
Line Volts
Red (2) + Hot
‘U5’ Output 2 to 10 VDC
25
Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC To other actuators
-MFT95-X1
Used with the W973 and W7100 controllers
-MFT95-X1
Wht (3) Wht (4) Wht (5) Wht (6)
22
Wht (3) W
21 24 VAC Transformer
Honeywell Q209A Minimum Position Potentiometer
Line
Blk (1) Common
Volts
25
W R B
Shunting Resistor
‘U5’ Output 2 to 10 VDC
Red (2) + Hot
22
23
W
R
R
R
B
W
Wht (3) W
W
Wht (4) R Wht (5) B
B
W973, W7100 T775
23 25
Wht (6) ‘U5’ Output 2 to 10 VDC
Honeywell T675A Morning Warmup
-MFT95-X1
-MFT95-X1
23
Line Volts
24
22
Red (2) + Hot
Series 90 Controller
25
R
W
R
B
Wht (3) W
R
Wht (4) R
B
Wht (5) B
Series 90 low limit control 135 Ω for 0 to 50% control 280 Ω for 0 to 100% control
21
21
Blk (1) Common
W
W R B
24
W
23 B
24 VAC Transformer
W
Blk (1) Common
H205 Change- Occupied over Controller Contact
Low Limit Control
22
B
W
24
-MFT95-X1
21
R
R Shunting Resistor
Honeywell T675A Morning Warmup
W
No. of actuators Resistance 2 1300 Ω 3 910 Ω 4 768 Ω Resistor Kit No. ZG-R06
23
Red (2) + Hot
23
Wht (5) B
R
Volts
Blk (1) Common
Series 90 Controller
Wht (4) R
Occupied Contact
Line
S963A Minimum Position Potentiometer
Line Volts
A W
24 VAC Transformer
21
Blk (1) Common
Volts
B
21
‘U5’ Output 2 to 10 VDC
Red (2) + Hot
Wht (6) ‘U5’ Output 2 to 10 VDC 24 VAC Transformer
W
W973, W7100 Controller
Wiring Multiple Actuators to a Series 90 Controller using a Minimum Position Potentiometer
Wht (5) B
-MFT95-X1
22 Shunting Resistor
W016
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
135 Ω
24
Wht (5) B
24
25
W019
Line
25
Wht (4) R
Blk (1) Common
Volts
W015
21 24 VAC Transformer
Wht (3) W
23
Line
The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.
B
R
23
21 Damper Closed
W
R
Y
-MFT95-X1
Damper Open
R
23
Wht (6) ‘U5’ Output 2 to 10 VDC
Blk (1) Common
W
B W
-MFT95-X1
24 VAC Transformer
Volts
Override Switch B
H205 Changeover Controller
Wiring Multiple Actuators to a Series 90 Controller 21
Red (2) + Hot
22
Wht (6) ‘U5’ Output 2 to 10 VDC
Shunting Resistor
Switch A
24
Wht (5) B
B
W
Blk (1) Common
Volts
Wht (4) R
R B
To reverse control rotation, use the reversing switch.
25
Wht (3) W
W
Series 90 Controller
Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell® resistor kits may also be used.
24
Line
Red (2) + Hot
23
Consult controller instruction data for more detailed information.
23
Q209A Minimum Position Potentiometer
Blk (1) Common
Volts
Actuators and controller must have separate transformers.
22
21 24 VAC Transformer
W018
21
W017
24 VAC Transformer
21
Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers W020
High Limit Control
INSTALLATION NOTES
Blk (1) Common Red (2) + Hot Wht (3) Wht (4) Wht (5) Wht (6)
Wht (6) ‘U5’ Output 2 to 10 VDC
800-543-9038 USA
-MFT95-X1
Line
To other actuators
W R B
23
Red (2) + Hot
22
Wht (3) W
25
23 25
Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC
‘U5’ Output 2 to 10 VDC
-MFT95-X1
866-805-7089 CANADA
Blk (1) Common
Volts
To other actuators
-MFT95-X1
203-791-8396 LATIN AMERICA / CARIBBEAN
21
AF Actuators, On/Off Dimensions with 2-Way Valve
F
C
A
B
D
Models
AFBUP-S-X1 Transformer sizing
on/off running holding running holding AFB24-X1 AFBUP(-S)-X1
Electrical connection (-S model has 2 cables) Electrical protection Overload protection Angle of rotation Position indication Manual override Running time Ambient temperature Housing Agency listings Noise level
5W 2.5 W 7W 3.5 W 7.5 VA (class 2 power source) 7 VA @ 24 VAC (class 2 power source) 8.5 VA @ 120 VAC 18 VA @ 240 VAC ½” conduit connector 3 ft. [1m], 18 GA appliance cables 120V actuators double insulated electronic throughout 0° to 95° rotation 95° visual indicator hex crank control 150 seconds independent of load spring <20 seconds -22°F to +122°F [-30°C to +50°C] NEMA 2 / IP54 UL 873, CSA C22.2 No. 24 certified, CE max. 45 dB(A)
AFBUP-S-X1 Auxiliary switches
* Dual Mounted Actuators
800-543-9038 USA
22
2 x SPDT, 7A (2.5A) @ 250 VAC, UL listed, one switch is fixed at +5°, one is adjustable 25° to 85° (double insulated)
Valve Nominal Size Inches DN [mm] 1 25 1 25 1¼ 32 1½ 40 1½ 40 2 50 1 25 1¼ 32 1½ 40 2 50
A 7.00 7.00 7.25 15.00 15.00 15.00 7.00 7.25 15.00 15.00
Dimensions (Inches) B C D 2.00 8.00 3.37 2.00 8.00 3.62 2.00 8.00 3.97 3.00 8.00 4.37 3.00 8.00 4.75 3.00 8.00 4.68 2.00 8.00 3.37 2.00 8.00 3.97 3.00 8.00 4.37 3.00 8.00 4.68
F 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25
Dimensions with 3-Way Valve 9.77” [248.2]
4.04” [102.7]
Valve Body
COP
B332L B340L B350L
50 50 50
866-805-7089 CANADA
Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56] 1½ 40 4.80” [122] 2.44” [62] 2.61” [67] 2 50 5.60” [142] 2.67” [68] 3.11” [79]
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data Control Power consumption AFBUP-X1
COP 400 200 200 600 600 600 1000 1000 1000 600
2.50” [63.5]
w/built-in Aux. Switches
Valve Body B224VS B225VS B232VS *B239VS *B240VS *B249VS B224VSS B232VSS *B239VSS *B249VSS
3.93” [99.9]
AFB24-X1 AFBUP-X1 AFBUP-S-X1
AF Actuators, On/Off j y
W194_AFB24-X1
p
Wiring Diagrams
24 VAC Transformer
2
Provide overload protection and disconnect as required.
2 + Hot
CAUTION Equipment damage!
AFB24-X1
Actuators may be connected in parallel. Power consumption must be observed.
3
2
On/Off Wiring for AFB24-X1
3
Actuators may also be powered by 24 VDC.
4
For end position indication, interlock control, fan startup, etc., AF24-S US incorporates two built-in auxiliary switches: 2 x SPDT, 7A (2.5A) @ 250 VAC, UL listed, one switch is fixed at +5°, one is adjustable 25° to 85°.
W003_AFB24-X1
1
1 Common
Line Volts
Meets cULus or UL and CSA requirements without the need of an electrical ground connection.
AFBUP-X1 AFBUP-S-X1
WARNING Live Electrical Components!
On/Off Wiring for AFBUP-X1, AFBUP-S-X1 W195_AFBUP-S-X1
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
AFBUP-S-X1
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary Switches
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
23
AF Actuators, Multi-Function Technology Dimensions with 2-Way Valve
F
C
A
B
D
Models
Power supply Power consumption
running holding
Transformer sizing Electrical connection (-S model has 2 cables) Overload protection Input impedance
Feedback output Angle of rotation Direction of rotation Position indication Manual override Running time Ambient temperature Housing Agency listings Noise level AFX24-MFT-S-X1 Auxiliary switches
spring motor
control spring
MFT 2 to 10 VDC, (4 to 20 mA with 500 Ω resistor) 0-135 Ω (MFT95) 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 7.5 W 3W 10 VA (class 2 power source) ½” conduit connector 3 ft. [1m], 18 GA appliance cable electronic throughout rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max 95° reversible with CW/CCW mounting reversible with built-in visual indicator hex crank 150 seconds independent of load <20 seconds -22°F to +122°F [-30°C to +50°C] NEMA 2 / IP54 UL 873, CSA C22.2 No. 24 certified, CE max. 45 dB(A)
2 x SPDT, 7A (2.5A) @ 250 VAC, UL listed, one switch is fixed at +5°, one is adjustable 25° to 85° (double insulated)
COP 400 50 200 400 50 200 1000 1000 1000 1000 400
Valve Nominal Size Inches DN [mm] 1 25 1 25 1¼ 32 1½ 40 1½ 40 2 50 1 25 1¼ 32 1¼ 32 1½ 40 2 50
A 7.00 7.00 7.25 7.50 7.50 8.00 7.00 7.25 7.25 6.70 8.00
Dimensions (Inches) B C D F 2.00 8.00 3.37 6.25 2.00 8.00 3.62 6.25 2.00 8.00 3.97 6.25 2.00 8.00 4.37 6.25 2.00 8.00 4.75 6.25 2.00 8.00 4.68 6.25 2.00 8.00 3.37 6.25 2.00 8.00 3.97 6.25 2.00 8.00 3.97 6.25 2.00 8.00 4.37 6.25 2.00 8.00 4.68 6.25
Dimensions with 3-Way Valve 9.77” [248.2]
4.04” [102.7]
Valve Body
COP
B332L B340L B350L
50 50 50
Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56] 1½ 40 4.80” [122] 2.44” [62] 2.61” [67] 2 50 5.60” [142] 2.67” [68] 3.11” [79]
* Dual Mounted Actuators
800-543-9038 USA
24
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data Control Control signal
Valve Body B224VS B225VS B232VS *B239VS *B240VS *B249VS B224VSS B232VSS *B232VSS *B239VSS *B249VSS
2.50” [63.5]
w/built-in Aux. Switches
3.93” [99.9]
AFX24-MFT-X1 AFX24-MFT-S-X1 AFX24-MFT95-X1
AF Actuators, Multi-Function Technology W043
Wiring Diagrams 24 VAC/DC Transformer
Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
4
IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).
5
Triac A and B can also be contact closures.
6 7
Position
(1)
Common
(2)
Hot
(3)
Y Input
(5)
U Output
a
(–)
Feedback VDC (+)
CCW CW
…MFT
On/Off control W041
2
Line Volts
CAUTION Equipment damage!
24 VAC Transformer (AC only)
Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. Position feedback cannot be used with Triac sink controller. The actuators internal common reference is not compatible.
(1)
Line Volts 7
6
Position
(–)
Feedback VDC (+)
+ Hot
(3)
Y Input
(5)
U Output
CCW CW
…MFT
PWM, triac source and sink W302_AFBX24-MFT
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel. Meets cULus or UL and CSA requirements without the need of an electrical ground connection.
Common
(2)
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
...MFT
Floating Point control
Propotional 2 to 10 or 4 to 20 mA control signal
AFX24-MFT-S-X1
Auxiliary Switches
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
25
AF Actuators, Multi-Function Technology
Line
22
R
Series 90 high limit control - 280 Ω
Red (2) + Hot Wht (3) Wht (4) Wht (5) Wht (6)
R B
24
Damper Position
Series 90 Controller
W R B
Blk (1) Common
Volts
Red (2) + Hot
23
A Wht (3) W 135 Ω
24
Wht (4) R
B
-MFT95-X1
21 Line
No. of actuators Resistance 2 140 Ω 3 71.5 Ω 4 47.5 Ω 5 37.5 Ω 6 28 Ω Resistor Kit No. ZG-R03
Wht (3) Wht (4) Wht (5) Wht (6) To other actuators
Red (2) + Hot Wht (3) W
Line
R
Volts
B
24
B
B
22
Wht (6) ‘U5’ Output 2 to 10 VDC
Controller
Volts
‘U5’ Output 2 to 10 VDC
25
Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC To other actuators
-MFT95-X1
Used with the W973 and W7100 controllers
-MFT95-X1
Wht (3) Wht (4) Wht (5) Wht (6)
22
Wht (3) W
21 24 VAC Transformer
Honeywell Q209A Minimum Position Potentiometer
Line
Blk (1) Common
Volts
25
W R B
Shunting Resistor
‘U5’ Output 2 to 10 VDC
Red (2) + Hot
22
23
W
R
R
R
B
W
Wht (3) W
W
Wht (4) R Wht (5) B
B
W973, W7100 T775
23 25
Wht (6) ‘U5’ Output 2 to 10 VDC
Honeywell T675A Morning Warmup
-MFT95-X1
-MFT95-X1
23
Line Volts
24
22
Red (2) + Hot R
B
Wht (3) W
R
Wht (4) R
B
Wht (5) B
Series 90 low limit control 135 Ω for 0 to 50% control 280 Ω for 0 to 100% control
R
W
21
-MFT95-X1
Line
Blk (1) Common Red (2) + Hot Wht (3) Wht (4) Wht (5) Wht (6)
Wht (6) ‘U5’ Output 2 to 10 VDC
800-543-9038 USA
26
25
21
Blk (1) Common
Series 90 Controller
Red (2) + Hot
W016
Line
W
W R B
24
W
23 B
24 VAC Transformer
W
Blk (1) Common
H205 Change- Occupied over Controller Contact
Low Limit Control
22
B
W
24
-MFT95-X1
21
R
R Shunting Resistor
Honeywell T675A Morning Warmup
W
No. of actuators Resistance 2 1300 Ω 3 910 Ω 4 768 Ω Resistor Kit No. ZG-R06
23
Red (2) + Hot
23
Wht (5) B
R
Volts
Blk (1) Common
Series 90 Controller
Wht (4) R
Occupied Contact
Line
S963A Minimum Position Potentiometer
Line Volts
A W
24 VAC Transformer
21
Blk (1) Common
Volts
B
21
‘U5’ Output 2 to 10 VDC
Red (2) + Hot
Wht (6) ‘U5’ Output 2 to 10 VDC 24 VAC Transformer
W
W973, W7100 Controller
Wiring Multiple Actuators to a Series 90 Controller using a Minimum Position Potentiometer
Wht (5) B
-MFT95-X1
22
24
25
W019
Line
Wht (5) B
Blk (1) Common
Volts
W015
21 24 VAC Transformer
25
23
Line
The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.
Wht (3) W Wht (4) R
R
23
21 Damper Closed
B
Y
-MFT95-X1
Damper Open
W
R
Shunting Resistor
Blk (1) Common
W
R
23
Wht (6) ‘U5’ Output 2 to 10 VDC
W018
Line
B W
-MFT95-X1
24 VAC Transformer
Volts
Override Switch B
H205 Changeover Controller
Wiring Multiple Actuators to a Series 90 Controller 21
Red (2) + Hot
22
Wht (6) ‘U5’ Output 2 to 10 VDC
Shunting Resistor
Switch A
24
Wht (5) B
B
W
Blk (1) Common
Volts
Wht (4) R
R B
To reverse control rotation, use the reversing switch.
25
Wht (3) W
W
Series 90 Controller
Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell® resistor kits may also be used.
24
Line
Red (2) + Hot
23
Consult controller instruction data for more detailed information.
23
Q209A Minimum Position Potentiometer
Blk (1) Common
Volts
Actuators and controller must have separate transformers.
22
21 24 VAC Transformer
To other actuators
W R B
23
Red (2) + Hot
22
Wht (3) W
25
23 25
Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC
‘U5’ Output 2 to 10 VDC
-MFT95-X1
866-805-7089 CANADA
Blk (1) Common
Volts
To other actuators
-MFT95-X1
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Provide overload protection and disconnect as required.
21
W017
24 VAC Transformer
21
Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers W020
High Limit Control
INSTALLATION NOTES
LM(B)X24-3-X1, LRX24-3 Actuators, On/Off, Floating Point
PAGE7
Dimensions with 2-Way Valve
H2
H1
F
C
B
A
Models D
LMB24-3-X1 LMX24-3-X1 LRX24-3 Technical Data Control Power supply Power consumption
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Transformer sizing Electrical connection LMB24-3-X1 Overload protection Input impedance Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings
Noise level Servicing Quality standard
Valve Body COP B2050VS-01 50 B2050VS-02 50 B2050VS-04 50 B2050VS-15 50
on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 1.5 W holding 0.2 W 3 VA (class 2 power source) ½” conduit connector 3 ft., 18 GA plenum rated cables
A 6.75 6.75 6.75 6.75
Dimensions (Inches) B C D F H1 2.00 6.75 2.25 4.00 9.75 2.00 6.75 2.25 4.00 9.75 2.00 6.75 2.25 4.00 9.75 2.00 6.75 2.25 4.00 9.75
H2 8.50 8.50 8.50 8.50
Dimensions with 3-Way Valve
electronic throughout 0° to 95° rotation 600 Ω 95° 45 in-lbs [5 Nm] reversible with reflective visual indicator (snap-on) external push button 95 seconds, constant independent of load 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA C22.2 No. 24 certified, CE acc. to 73/23/EEC <35 db(A) maintenance free ISO 9001
800-543-9038 USA
Valve Nominal Size Inches DN [mm] ½ 15 15 ½ ½ 15 ½ 15
Valve Body
COP
B315L B320L B325L
50 50 50
866-805-7089 CANADA
Valve Nominal Size DN Inches [mm] ½ 15 ¾ 20 1 25
Dimensions (mm) A
B
C
2.63” [67] 1.73” [44] 1.42” [36] 3.01” [78] 1.81” [46] 1.63” [42] 3.42” [87] 1.81” [46] 1.77” [45]
203-791-8396 LATIN AMERICA / CARIBBEAN
27
LM(B)X24-3-X1, LRX24-3 Actuators, On/Off, Floating Point W266-08
Wiring Diagrams
1
Provide overload protection and disconnect as required.
3
Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without the need of an electrical ground connection. On/Off control
WARNING Live Electrical Components!
W267-08
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Floating Point or On/Off control
Piping
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. Allow 6” for cover removal and 12” for complete actuator removal. The assembly can be mounted with the actuator vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction.
800-543-9038 USA
28
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
LMX24-MFT-X1, LRX24-MFT Actuators, Multi-Function Technology
PAGE7
Dimensions with 2-Way Valve
H2
H1
F
C
B
A
Models LMX24-MFT-X1 LRX24-MFT
D
Technical Data Power supply Power consumption Transformer sizing Electrical connection
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Overload protection Input impedance
Feedback Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings
Noise level Servicing Quality standard
24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 2W 3.5 VA (class 2 power source) 3 ft. [1m], 10 ft. [3m], 16 ft. [5m] 18 GA plenum rated cable ½” conduit connector electronic throughout 0° to 95° rotation 100k Ω for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max VDC variable 95° 45 in-lbs [5 Nm] reversible with reflective visual indicator (snap-on) external push button 150 seconds (default) variable (35 to 150 seconds) 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <35 db(A) maintenance free ISO 9001
800-543-9038 USA
Valve Nominal Size DN Valve Body COP Inches [mm] B2050VS-01 50 ½ 15 B2050VS-02 50 15 ½ B2050VS-04 50 ½ 15 B2050VS-15 50 ½ 15
Dimensions (Inches) A
B
C
D
F
H1
H2
6.75 6.75 6.75 6.75
2.00 2.00 2.00 2.00
6.75 6.75 6.75 6.75
2.25 2.25 2.25 2.25
4.00 4.00 4.00 4.00
9.75 9.75 9.75 9.75
8.50 8.50 8.50 8.50
Dimensions with 3-Way Valve
Valve Body
COP
B315L B320L B325L
50 50 50
866-805-7089 CANADA
Valve Nominal Size DN Inches [mm] ½ 15 ¾ 20 1 25
Dimensions (mm) A
B
C
2.63” [67] 1.73” [44] 1.42” [36] 3.01” [78] 1.81” [46] 1.63” [42] 3.42” [87] 1.81” [46] 1.77” [45]
203-791-8396 LATIN AMERICA / CARIBBEAN
29
LMX24-MFT-X1, LRX24-MFTT Actuators, Multi-Function Technology
Provide overload protection and disconnect as required.
3
Actuators may also be powered by 24 VDC.
5
Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line.
6
ZG-R01 may be used.
4
7 8
24 VAC/DC Transformer
1
2 Blk (1) Common
Line Volts
Red (2) Hot
3 a
(–)
Position
Wht (3) Y Input
Feedback VDC (+)
Org (5) U Output …MFT
Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.
On/Off control 24 VAC Transformer
W399
1
W399
Wiring Diagrams
2
1
Blk (1) Common –
Line Volts
Red (2) Hot +
A
3 5
Wht (3) Y1 Input
B
8
Pnk (4) Y2 Input 7
2 to 10 VDC Feedback Signal
Org (5) U Output 2 to 10V
4 …MFT
W399
Floating Point 24 VAC Transformer 1 Line Volts
2 Blk (1) Common Red (2) + Hot
3
Ω
Control Signal 4 to 20 mA or 2 to 10 VDC
500Ω 1/4 watt
(–) (+)
Wht (3) Y1 Input, 2 to 10V 6 Org (5) U Output, 2 to 10V
…MFT
24 VAC Transformer (AC only) 1
Blk (1) Common
Line Volts
5
(–) 2 Position Feedback VDC (+)
Red (2) + Hot Wht (3) Y Input Org (5) U Output
…MFT
PWM
800-543-9038 USA
30
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W399
VDC/4-20 mA
NM(B)X24-3-X1, NRB24-3 Actuators, On/Off, Floating Point
PAGE7
Dimensions with 2-Way Valve
H2
H1
F
C
B
A
Models NMB24-3-X1 NMX24-3-X1 NRB24-3
D
Technical Data Control Power supply
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Power consumption Transformer sizing Electrical connection NMB24-3-X1 Overload protection Input impedance Angle of rotation Torque Direction of rotation
Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings
Noise level Servicing Quality standard
on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 2.0 W holding 0.2 W 4 VA (class 2 power source) 3 ft., 18 GA plenum rated cable ½” conduit connector electronic throughout 0° to 95° rotation 600 Ω max 95°, adjustable with mechanical stop 90 in-lbs [10 Nm] reversible with =CCW with decreasing control signal (10-2V) =CW with decreasing control signal (10-2V) reflective visual indicator (snap-on) external push button 95 seconds, constant independent of load 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA C22.2 No. 24 certified, CE acc. to 73/23/EEC <45 db(A) maintenance free ISO 9001
800-543-9038 USA
Valve Nominal Size DN Valve Body COP Inches [mm] B219VS 400 ¾ 20 B220VS 20 400 ¾ B2050VSS-15 1000 ½ 15 B219VSS 1000 ¾ 20
Dimensions (Inches) A
B
C
D
F
H1
H2
6.70 6.70 6.70 6.70
2.00 2.00 2.00 2.00
8.00 8.00 8.00 8.00
3.00 3.12 2.25 3.00
6.25 6.25 6.25 6.25
9.75 9.75 9.75 9.75
8.50 8.50 8.50 8.50
Dimensions with 3-Way Valve
Valve Body
COP
B332L
50
866-805-7089 CANADA
Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56]
203-791-8396 LATIN AMERICA / CARIBBEAN
31
NM(B)X24-3-X1, NRB24-3 Actuators, On/Off, Floating Point W266-08
Wiring Diagrams
1
Provide overload protection and disconnect as required.
3
Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without the need of an electrical ground connection. During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
On/Off control W267-08
WARNING Live Electrical Components!
Floating Point or On/Off control
Piping
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. Allow 6” for cover removal and 12” for complete actuator removal. The assembly can be mounted with the actuator vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction.
800-543-9038 USA
32
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
NMX24-MFT-X1, NRX24-MFT Actuators, Multi-Function Technology
PAGE7
Dimensions with 2-Way Valve
H2
H1
F
C
B
A
Models NMX24-MFT-X1 NRX24-MFT
D
Technical Data Power supply Power consumption Transformer sizing Electrical connection
Overload protection Input impedance
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Feedback Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings
Noise level Servicing Quality standard
24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 3.5 W (1.25 W) 5.5 VA (class 2 power source) 3 ft. [1m], 10 ft. [3m], 16 ft. [5m] 18 GA plenum rated cable ½” conduit connector electronic throughout 0° to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max VDC variable max 95°, adjust. with mechanical stop electronically variable 90 in-lbs [10 Nm] reversible with reflective visual indicator (snap-on) external push button 150 seconds (default) Variable (45 to 170 secondss) 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <45 db(A) maintenance free ISO 9001
800-543-9038 USA
Valve Nominal Size DN Valve Body COP Inches [mm] B219VS 400 ¾ 20 B220VS 20 400 ¾ B2050VSS-15 1000 ½ 15 B219VSS 1000 ¾ 20
Dimensions (Inches) A
B
C
D
F
H1
H2
6.70 6.70 6.70 6.70
2.00 2.00 2.00 2.00
8.00 8.00 8.00 8.00
3.00 3.12 2.25 3.00
6.25 6.25 6.25 6.25
9.75 9.75 9.75 9.75
8.50 8.50 8.50 8.50
Dimensions with 3-Way Valve
Valve Body
COP
B332L
50
866-805-7089 CANADA
Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56]
203-791-8396 LATIN AMERICA / CARIBBEAN
33
NMX24-MFT-X1, NRX24-MFT Actuators, Multi-Function Technology
Provide overload protection and disconnect as required.
3
Actuators may also be powered by 24 VDC.
5
Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line.
6
ZG-R01 may be used.
4
7 8
24 VAC/DC Transformer
1
2 Blk (1) Common
Line Volts
Red (2) Hot
3 a
(–)
Position
Wht (3) Y Input
Feedback VDC (+)
Org (5) U Output …MFT
Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.
On/Off control 24 VAC Transformer
W399
1
W399
Wiring Diagrams
2
1
Blk (1) Common –
Line Volts
Red (2) Hot +
A
3 5
Wht (3) Y1 Input
B
8
Pnk (4) Y2 Input 7
2 to 10 VDC Feedback Signal
Org (5) U Output 2 to 10V
4 …MFT
W399
Floating Point 24 VAC Transformer 1 Line Volts
2 Blk (1) Common Red (2) + Hot
3
Ω
Control Signal 4 to 20 mA or 2 to 10 VDC
500Ω 1/4 watt
(–) (+)
Wht (3) Y1 Input, 2 to 10V 6 Org (5) U Output, 2 to 10V
…MFT
24 VAC Transformer (AC only) 1
Blk (1) Common
Line Volts
5
(–) 2 Position Feedback VDC (+)
Red (2) + Hot Wht (3) Y Input Org (5) U Output
…MFT
PWM
800-543-9038 USA
34
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W399
VDC/4-20 mA
AM(B)X24-3-X1, ARX24-3 Actuators, On/Off, Floating Point
PAGE7
Dimensions with 2-Way Valve
H2
H1
F
C
B
A
Models AMB24-3-X1 AMX24-3-X1 ARX24-3
D
Technical Data Control Power supply
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Power consumption Transformer sizing Electrical connection AMB24-3-X1 Overload protection Input impedance Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings
Noise level Servicing Quality standard
on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 2.5 W holding 0.2 W 5.5 VA (class 2 power source) ½” conduit connector 3 ft., 18 GA plenum rated cable electronic throughout 0° to 95° rotation 600 Ω max 95°, adjustable with mechanical stop 180 in-lbs [20 Nm] reversible with reflective visual indicator (snap-on) external push button 95 seconds, constant independent of load 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA C22.2 No. 24 certified, CE acc. to 73/23/EEC <45 db(A) maintenance free ISO 9001
800-543-9038 USA
Valve Body COP B224VS B225VS B232VS B224VSS B232VSS
400 200 400 1000 1000
Valve Nominal Size DN Inches [mm] 1 25 25 1 32 1¼ 1 25 1¼ 32
Dimensions (Inches) A
B
C
D
F
H1
H2
7.00 7.00 7.25 7.00 7.25
2.00 2.00 2.00 2.00 2.00
8.00 8.00 8.00 8.00 8.00
3.37 3.62 3.97 3.37 3.97
6.25 6.25 6.25 6.25 6.25
9.75 9.75 9.75 9.75 9.75
8.50 8.50 8.50 8.50 8.50
Dimensions with 3-Way Valve
Valve Body
COP
B340L B350L
50 50
866-805-7089 CANADA
Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1½ 40 4.80” [122] 2.44” [62] 2.61” [65] 2 50 5.60” [142] 2.67” [68] 3.11” [79]
203-791-8396 LATIN AMERICA / CARIBBEAN
35
AM(B)X24-3-X1, ARX24-3 Actuators, On/Off, Floating Point
1 2
W259-08
Wiring Diagrams
Provide overload protection and disconnect as required.
CAUTION Equipment damage! Actuators may be connected in parallel. Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (–) leg of control circuits.
W260-08
On/Off control Meets cULus or UL and CSA requirements without the need of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Floating Point or On/Off control
Piping
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. Allow 6” for cover removal and 12” for complete actuator removal. The assembly can be mounted with the actuator vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction.
800-543-9038 USA
36
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
AMX24-MFT-X1, ARX24-MFT Actuators, Multi-Function Technology
PAGE7
Dimensions with 2-Way Valve
H2
H1
F
C
B
A
Models AMX24-MFT-X1 AMX24-MFT95-X1 ARX24-MFT Technical Data Power supply Power consumption Transformer sizing Electrical connection
Overload protection Input impedance
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Feedback Angle of rotation Torque Direction of rotation Position indication Manual override Running time Humidity Ambient temperature Storage temperature Housing Housing material Agency listings
Noise level Servicing Quality standard
D
24 VAC ± 20% 50/60 Hz 24 VDC ± 10% 4 W (1.25 W) 6 VA (class 2 power source) 3 ft. [1m], 10 ft. [3m], 16 ft. [5m] 18 GA plenum rated cable ½” conduit connector electronic throughout 0° to 95° rotation 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max VDC variable max 95°, adjust. with mechanical stop electronically variable 180 in-lbs [20 Nm] reversible with reflective visual indicator (snap-on) external push button 150 seconds (default) variable (90 to 350 seconds) 5 to 95% RH non-condensing (EN 60730-1) -22°F to +122°F [-30°C to +50°C] -40°F to +176°F [-40°C to +80°C] NEMA type 2/IP54 UL94-5VA cULus acc. to UL 60730-1/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <45 db(A) maintenance free ISO 9001
800-543-9038 USA
Valve Nominal Size DN Valve Body COP Inches [mm] B224VS 400 1 25 B225VS 25 200 1 32 B232VS 400 1¼ B224VSS 1000 1 25 B232VSS 1000 1¼ 32
Dimensions (Inches) A
B
C
D
F
H1
H2
7.00 7.00 7.25 7.00 7.25
2.00 2.00 2.00 2.00 2.00
8.00 8.00 8.00 8.00 8.00
3.37 3.62 3.97 3.37 3.97
6.25 6.25 6.25 6.25 6.25
9.75 9.75 9.75 9.75 9.75
8.50 8.50 8.50 8.50 8.50
Dimensions with 3-Way Valve
Valve Body
COP
B340L B350L
50 50
866-805-7089 CANADA
Valve Nominal Dimensions (mm) Size DN Inches A B C [mm] 1½ 40 4.80” [122] 2.44” [62] 2.61” [65] 2 50 5.60” [142] 2.67” [68] 3.11” [79]
203-791-8396 LATIN AMERICA / CARIBBEAN
37
AMX24-MFT-X1, ARX24-MFTT Actuators, Multi-Function Technology
Provide overload protection and disconnect as required.
3
Actuators may also be powered by 24 VDC.
5
Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line.
6
ZG-R01 may be used.
4
7 8
24 VAC/DC Transformer
1
2 Blk (1) Common
Line Volts
Red (2) Hot
3 a
(–)
Position
Wht (3) Y Input
Feedback VDC (+)
Org (5) U Output …MFT
Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.
On/Off control 24 VAC Transformer
W399
1
W399
Wiring Diagrams
2
1
Blk (1) Common –
Line Volts
Red (2) Hot +
A
3 5
Wht (3) Y1 Input
B
8
Pnk (4) Y2 Input 7
2 to 10 VDC Feedback Signal
Org (5) U Output 2 to 10V
4 …MFT
W399
Floating Point 24 VAC Transformer 1 Line Volts
2 Blk (1) Common Red (2) + Hot
3
Ω
Control Signal 4 to 20 mA or 2 to 10 VDC
500Ω 1/4 watt
(–) (+)
Wht (3) Y1 Input, 2 to 10V 6 Org (5) U Output, 2 to 10V
…MFT
24 VAC Transformer (AC only) 1
Blk (1) Common
Line Volts
5
(–) 2 Position Feedback VDC (+)
Red (2) + Hot Wht (3) Y Input Org (5) U Output
…MFT
PWM
800-543-9038 USA
38
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W399
VDC/4-20 mA
AMX24-MFT-X1 Actuators, Multi-Function Technology
Provide overload protection and disconnect as required.
Line
22 Series 90 Controller
Wht (3) W
R
Wht (4) R R
Series 90 high limit control - 280 Ω
Line
Red (2) + Hot Wht (3) W Wht (4) R Wht (5) B
W R B
24
Damper Position
Blk (1) Common
Volts
Red (2) + Hot
23
A Wht (3) W 135 Ω
24
Wht (4) R
B
Red (2) + Hot
No. of actuators Resistance 2 140 Ω 3 71.5 Ω 4 47.5 Ω 5 37.5 Ω 6 28 Ω Resistor Kit No. ZG-R03
Wht (3) Wht (4) Wht (5) Wht (6) To other actuators
Wht (6) ‘U5’ Output 2 to 10 VDC -MFT95-X1
21 24 VAC Transformer
Red (2) + Hot
Line Volts
Wht (3) W
R
Wht (4) R
B
B
22
24
B
R
R
22
Wht (6) ‘U5’ Output 2 to 10 VDC
Controller
Line Volts
Red (2) + Hot
23 Series 90 Controller
25
Blk (1) Common Red (2) + Hot
‘U5’ Output 2 to 10 VDC
Wht (3) W
25
Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC To other actuators
-MFT95-X1
Used with the W973 and W7100 controllers
-MFT95-X1
21 24 VAC Transformer
Wht (3) Wht (4) Wht (5) Wht (6)
Honeywell Q209A Minimum Position Potentiometer
Line
Blk (1) Common
Volts
25
W R B
Shunting Resistor
‘U5’ Output 2 to 10 VDC
Red (2) + Hot
22
23
W
R
R
R
B
W
Wht (3) W
W
Wht (4) R Wht (5) B
B
W973, W7100 T775
23 25
Wht (6) ‘U5’ Output 2 to 10 VDC
Honeywell T675A Morning Warmup
-MFT95-X1
-MFT95-X1 R
W
R
B
Wht (3) W
R
Wht (4) R
B
Wht (5) B
Series 90 low limit control 135 Ω for 0 to 50% control 280 Ω for 0 to 100% control
21
21
Blk (1) Common
W
Honeywell T675A Morning Warmup
W
No. of actuators Resistance 2 1300 Ω 3 910 Ω 4 768 Ω Resistor Kit No. ZG-R06
24
W
23 B
24 VAC Transformer
W
R
H205 Change- Occupied over Controller Contact
Low Limit Control
22
B
W
24
-MFT95-X1
21
W R B
Red (2) + Hot
23
Wht (5) B
Occupied Contact
21
23
Blk (1) Common
Series 90 Controller
Shunting Resistor
B
Volts
S963A Minimum Position Potentiometer
Line Volts
A W
24 VAC Transformer
21
Blk (1) Common
W
W016
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Line Volts
-MFT95-X1
22 Shunting Resistor
Line
Wiring Multiple Actuators to a Series 90 Controller using a Minimum Position Potentiometer
Wht (5) B
Wht (5) B
W973, W7100 Controller
W019
Line
Wht (4) R
Blk (1) Common
Volts
W015
21 24 VAC Transformer
B
23 25
23
Line
The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.
R
Wht (3) W
24
25
21 Damper Closed
W
R
23
-MFT95-X1
Damper Open
W
Y
Wht (6) ‘U5’ Output 2 to 10 VDC
Series 90 Controller
R
Wht (6) ‘U5’ Output 2 to 10 VDC
Blk (1) Common
Volts
Override Switch B
H205 Changeover Controller
B
-MFT95-X1
24 VAC Transformer
21
Red (2) + Hot
22
Wiring Multiple Actuators to a Series 90 Controller
Shunting Resistor
Switch A
24
Wht (5) B
B
W
Blk (1) Common
Volts
Wht (6) ‘U5’ Output 2 to 10 VDC
To reverse control rotation, use the reversing switch.
25
W
B
Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell® resistor kits may also be used.
24
Line
Red (2) + Hot
23
Consult controller instruction data for more detailed information.
23
Q209A Minimum Position Potentiometer
Blk (1) Common
Volts
Actuators and controller must have separate transformers.
22
21 24 VAC Transformer
W018
21
W017
24 VAC Transformer
21
Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers W020
High Limit Control
INSTALLATION NOTES
24
Line Volts
Red (2) + Hot
22
Wht (3) Wht (4) Wht (5) Wht (6)
Wht (6) ‘U5’ Output 2 to 10 VDC
800-543-9038 USA
-MFT95-X1
Line
Blk (1) Common
To other actuators
W R B
23
Red (2) + Hot
22
Wht (3) W
25
23 25
Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC
‘U5’ Output 2 to 10 VDC
-MFT95-X1
866-805-7089 CANADA
Blk (1) Common
Volts
To other actuators
-MFT95-X1
203-791-8396 LATIN AMERICA / CARIBBEAN
39
GMB24-3-X1 Actuators, On/Off, Floating Point
PAGE7
Dimensions with 2-Way Valve
H2
H1
F
C
B
A
D
Models
Power consumption Transformer sizing Electrical connection
Overload protection Angle of rotation Direction of rotation Position indication Running time Humidity Ambient temperature Housing Housing material Agency listings
Noise level Quality standard
on/off, floating point 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 4 W holding 2 W 6 VA (class 2 power source) 3 ft. [1m] 18 GA plenum rated cable ½” conduit connector electronic throughout stroke 95° reversible with reflective visual indicator (snap-on) 150 seconds, constant independent of load 5 to 95% RH non-condensing -22°F to +122°F [-30°C to +50°C] NEMA 2/IP54 with cable entry down UL94-5V (flammability rating) cULus acc. to UL 60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <45 dB(A) ISO 9001
Dimensions (Inches) A
B
C
D
F
H1
H2
7.50 7.50 7.50 7.50
3.00 3.00 3.00 3.00
8.00 8.00 8.00 8.00
4.37 4.68 4.37 4.68
6.25 6.25 6.25 6.25
9.75 9.75 9.75 9.75
8.50 8.50 8.50 8.50
Dimensions with 2*GM... and 2-Way Valve
H2
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data Control Power supply
Valve Nominal Size DN Valve Body COP Inches [mm] B239VS 400 1½ 40 B249VS 50 200 2 40 B239VSS 1000 1½ B249VSS 400 2 50
PAGE7
GMB24-3-X1 2*GMB24-3-X1
H1
F
C
B
A
D
Valve Nominal Size DN Valve Body COP Inches [mm] 40 B240VS 400 1½ B250VS 50 200 2 B265VS 65 100 2½ B280VS 80 50 3 B249VSS 1000 2 50 B265VSS 200 2½ 65
Dimensions (Inches) A
B
C
D
F
7.50 15.00 15.00 15.00 7.50 15.00
3.00 3.00 3.00 3.00 3.00 3.00
8.00 8.00 8.00 8.00 8.00 8.00
4.75 5.37 6.25 6.75 4.68 6.25
6.25 6.25 6.25 6.25 6.25 6.25
H1* H2* 9.75 9.75 9.75 9.75 9.75 9.75
*Handles not available on spring return series or dual mounted actuators
800-543-9038 USA
40
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
8.50 8.50 8.50 8.50 8.50 8.50
GMB24-3-X1 Actuators, On/Off, Floating Point Wiring Diagrams
1
Provide overload protection and disconnect as required.
2
Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
4 5 7 8
Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line. Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.
GMB24-3-X1
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off control
GMB24-3-X1
Floating Point or On/Off control
Piping The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. Allow 6” for cover removal and 12” for complete actuator removal. The assembly can be mounted with the actuator vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
41
GMX24-MFT-X1 Actuators, Multi-Function Technology
PAGE7
Dimensions with 2-Way Valve
H2
H1
F
C
B
A
D
Models
Power consumption Transformer sizing Electrical connection
Overload protection Input impedance
Feedback Angle of rotation Direction of rotation Position indication Running time Humidity Ambient temperature Housing Housing material Agency listings
Noise level Quality standard
on/off, floating point, 2 to 10 VDC 24 VAC ± 20% 50/60 Hz 24 VDC ± 10% running 4.5 W holding 3 W 7 VA (class 2 power source) 3 ft. [1m] 18 GA plenum rated cable ½” conduit connector electronic throughout stroke 100 kΩ for 2 to 10 VDC (0.1 mA) 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on/off and floating point 2 to 10 VDC, 0.5 mA max VDC variable 95° reversible with reflective visual indicator (snap-on) 150 seconds, constant independent of load 5 to 95% RH non-condensing -22°F to +122°F [-30°C to +50°C] NEMA 2/IP54 with cable entry down UL94-5V (flammability rating) cULus acc. to UL 60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC <45 dB(A) ISO 9001
B239VS B249VS B239VSS B249VSS
400 200 1000 400
Dimensions (Inches) A
B
C
D
F
H1
H2
7.50 7.50 7.50 7.50
3.00 3.00 3.00 3.00
8.00 8.00 8.00 8.00
4.37 4.68 4.37 4.68
6.25 6.25 6.25 6.25
9.75 9.75 9.75 9.75
8.50 8.50 8.50 8.50
Dimensions with 2xGM... and 2-Way Valve PAGE7
Technical Data Control Power supply
Valve Body COP
Valve Nominal Size DN Inches [mm] 1½ 40 50 2 40 1½ 2 50
H2
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
GMX24-MFT-X1 *2xGMX24-MFT-X1 GMX24-MFT95-X1
H1
F
C
B
A
D
Valve Body COP B240VS B250VS B265VS B280VS B265VSS B280VSS
400 200 100 50 200 100
Valve Nominal Size DN Inches [mm] 40 1½ 50 2 65 2½ 80 3 65 2½ 80 3
Dimensions (Inches) A
B
C
D
F
7.50 15.00 15.00 15.00 15.00 15.00
3.00 3.00 3.00 3.00 3.00 3.00
8.00 8.00 8.00 8.00 8.00 8.00
4.75 5.37 6.25 6.75 6.25 6.75
6.25 6.25 6.25 6.25 6.25 6.25
H1* H2* 9.75 9.75 9.75 9.75 9.75 9.75
8.50 8.50 8.50 8.50 8.50 8.50
*Handles not available on spring return series or dual mounted actuators
800-543-9038 USA
42
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
GMX24-MFT-X1 Actuators, Multi-Function Technology Wiring Diagrams
1
Provide overload protection and disconnect as required.
2
Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible. Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line.
6
ZG-R01 may be used.
7 8
Contact closures A & B also can be triacs. A& B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.
24 VAC/DC Transformer
1
W399
4
2 Blk (1) Common
Line Volts
Red (2) Hot
3 a
(–)
Position
Wht (3) Y Input
Feedback VDC (+)
Org (5) U Output …MFT
24 VAC Transformer
2
1
Blk (1) Common –
Line Volts
Red (2) Hot +
A
3 5
Wht (3) Y1 Input
B
8
Pnk (4) Y2 Input 7
2 to 10 VDC Feedback Signal
Org (5) U Output 2 to 10V
4 …MFT
W399
Floating Point 24 VAC Transformer 1 Line Volts
2 Blk (1) Common Red (2) + Hot
3
Ω
Control Signal 4 to 20 mA or 2 to 10 VDC
500Ω 1/4 watt
(–) (+)
Wht (3) Y1 Input, 2 to 10V 6 Org (5) U Output, 2 to 10V
…MFT
VDC/4-20 mA W399
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W399
On/Off control
24 VAC Transformer (AC only) 1
Line Volts (–) 2 Position Feedback VDC (+)
Blk (1) Common 5
Red (2) + Hot Wht (3) Y Input Org (5) U Output
…MFT
PWM
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
43
GMX24-MFT-X1 Actuators, Multi-Function Technology
Line
22 Series 90 Controller
Wht (3) W
R
Wht (4) R R
Series 90 high limit control - 280 Ω
Red (2) + Hot Wht (3) W Wht (4) R Wht (5) B
W R B
24
Damper Position
Blk (1) Common
Volts
Red (2) + Hot
23
A Wht (3) W 135 Ω
24
Wht (4) R
B
Red (2) + Hot
No. of actuators Resistance 2 140 Ω 3 71.5 Ω 4 47.5 Ω 5 37.5 Ω 6 28 Ω Resistor Kit No. ZG-R03
Wht (3) Wht (4) Wht (5) Wht (6) To other actuators
Wht (6) ‘U5’ Output 2 to 10 VDC -MFT95-X1
21 24 VAC Transformer Line
Red (2) + Hot
Line Volts
Wht (3) W
R
Wht (4) R
B
B
22
24
B
R
R
22
Wht (6) ‘U5’ Output 2 to 10 VDC
Controller
Volts
Red (2) + Hot
23 R
B
Wht (3) W
R
Wht (4) R
B
Wht (5) B
Series 90 low limit control 135 Ω for 0 to 50% control 280 Ω for 0 to 100% control
Red (2) + Hot Wht (3) W
‘U5’ Output 2 to 10 VDC
25
Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC To other actuators
-MFT95-X1
Used with the W973 and W7100 controllers
-MFT95-X1
Wht (3) Wht (4) Wht (5) Wht (6)
21 24 VAC Transformer
Honeywell Q209A Minimum Position Potentiometer
Line
Blk (1) Common
Volts
25
W R B
Shunting Resistor
‘U5’ Output 2 to 10 VDC
Red (2) + Hot
22
23
W
R
R
R
B
W
Wht (3) W
W
Wht (4) R Wht (5) B
B
W973, W7100 T775
23 25
Wht (6) ‘U5’ Output 2 to 10 VDC
Honeywell T675A Morning Warmup
-MFT95-X1
-MFT95-X1 R
W
21
24
Line Volts
-MFT95-X1
Line
Blk (1) Common Red (2) + Hot
22
Wht (3) Wht (4) Wht (5) Wht (6)
Wht (6) ‘U5’ Output 2 to 10 VDC
800-543-9038 USA
44
25
21
Blk (1) Common
Series 90 Controller
Blk (1) Common
W016
Line
W
Honeywell T675A Morning Warmup
W
No. of actuators Resistance 2 1300 Ω 3 910 Ω 4 768 Ω Resistor Kit No. ZG-R06
24
W
23 B
24 VAC Transformer
W
R
H205 Change- Occupied over Controller Contact
Low Limit Control
22
B
W
24
-MFT95-X1
21
W R B
Red (2) + Hot
23
Wht (5) B
Occupied Contact
21
23
Blk (1) Common
Series 90 Controller
Shunting Resistor
B
Volts
S963A Minimum Position Potentiometer
Line Volts
A W
24 VAC Transformer
21
Blk (1) Common
Volts
W
Line
Wiring Multiple Actuators to a Series 90 Controller using a Minimum Position Potentiometer
Wht (5) B
-MFT95-X1
22
W973, W7100 Controller
W019
Line
Wht (5) B
Blk (1) Common
Volts
W015
21 24 VAC Transformer
Wht (4) R
23
Line
The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.
B
23 25
24
25
21 Damper Closed
R
R
23
-MFT95-X1
Damper Open
W
Wht (3) W
Y
Wht (6) ‘U5’ Output 2 to 10 VDC
Series 90 Controller
W
Shunting Resistor
Blk (1) Common
Volts
R
Wht (6) ‘U5’ Output 2 to 10 VDC
W018
Line
Override Switch B
H205 Changeover Controller
B
-MFT95-X1
24 VAC Transformer
21
Red (2) + Hot
22
Wiring Multiple Actuators to a Series 90 Controller
Shunting Resistor
Switch A
24
Wht (5) B
B
W
Blk (1) Common
Volts
Wht (6) ‘U5’ Output 2 to 10 VDC
To reverse control rotation, use the reversing switch.
25
W
B
Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell® resistor kits may also be used.
24
Line
Red (2) + Hot
23
Consult controller instruction data for more detailed information.
23
Q209A Minimum Position Potentiometer
Blk (1) Common
Volts
Actuators and controller must have separate transformers.
22
21 24 VAC Transformer
To other actuators
W R B
23
Red (2) + Hot
22
Wht (3) W
25
23 25
Wht (4) R Wht (5) B Wht (6) ‘U5’ Output 2 to 10 VDC
‘U5’ Output 2 to 10 VDC
-MFT95-X1
866-805-7089 CANADA
Blk (1) Common
Volts
To other actuators
-MFT95-X1
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Provide overload protection and disconnect as required.
21
W017
24 VAC Transformer
21
Typical wiring diagrams for multiple actuators used with the W973, W7100 and T775 controllers W020
High Limit Control
INSTALLATION NOTES
SY...24 NEMA 4X Industrial Style Actuators, 24VAC Attention SY Series actuators are fractional horsepower devices, and utilize full-wave power supplies. Observe wire sizing and transformer sizing requirements. Proportional models CANNOT be connected to Belimo direct coupled (AF, AM, GM…etc) actuator power supplies or any type of half-wave device. You MUST use a separate, dedicated transformer or power supply to power the SY actuator. Please do not connect other automation equipment to the dedicated SY supply source. You MUST use four wires (plus a ground) to control a proportional control SY actuator (See SY Wiring Section).
Models SY1-24(P) SY2-24MFT SY3-24MFT SY4-24MFT SY5-24MFT
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data Power supply Electrical connection Overload protection Motor protection
SY1 SY2... - SY5...
Geartrain Operating range Sensitivity Feedback Angle of rotation Direction of rotation Position indication Internal humidity control Auxiliary switches
SY...-24 SY...-24MFT SY...-24MFT SY...-24MFT
Ambient temperature Humidity range Housing type Housing material Agency listings
800-543-9038 USA
24 VAC 50/60Hz, single phase ½” conduit connector, screw terminals thermally protected 135°C cut-out H class insulation F class insulation high alloy steel gear sets, self locking on/off 2-10 VDC, 4-20mA, 1-5 VDC 0.2mA / 100mV 2-10 VDC, 4-20mA mechanically limited to 95° reversible top mounted domed indicator resistive heating element (2) SPDT, 10A 250VAC factory set for 3° and 87° change of state -22°F to +150°F [-30°C to +65°C] up to 95% IP67, NEMA 4X die cast aluminum alloy ISO, CE, cCSAus
Technical Data - continued Power Consumption SY1-24(P) SY2-24MFT SY3-24MFT SY4-24MFT SY5-24MFT Torque SY1-24(P) SY2-24MFT SY3-24MFT SY4-24MFT SY5-24MFT Manual Override SY1-24(P) SY2-24 – SY5-24 Running Time SY1-24(P) SY2-24MFT SY3-24MFT SY4-24MFT SY5-24MFT
866-805-7089 CANADA
1.8A 3.0A 3.0A 6.0A 6.5A 35 Nm / 310 in-lbs 90 Nm / 801 in-lbs 150 Nm / 1335 in-lbs 400 Nm / 3560 in-lbs 500 Nm / 4450 in-lbs 8mm wrench hand wheel 15 seconds 15 seconds 22 seconds 16 seconds 22 seconds
203-791-8396 LATIN AMERICA / CARIBBEAN
45
SY...24 NEMA 4X Industrial Style Actuators, 24VAC Wiring Diagrams
T 1 2
Transformer sizing = SY actuator draw X 1.25 (safety margin) EXAMPLE: SY2-24 requires 3.0A x 1.25 = 3.75A, 3.75A X 24 VAC = 90VA Transformer. There can be no connection (internal to automation controller, external wiring, or otherwise) between actuator supply neutral & control signal reference. These actuators are full wave devices. Any connection to half wave equipment will result in equipment damage. Do not change sensitivity or dip switch settings with power applied.
3
Terminals 6 & 11 can be common when control and feedback signals are both set for 2-10VDC operation.
4
Use of feedback is optional.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off control for SY(2-5)-24
2 to 10 vdc or 4 to 20 mA control signal for SY1-24P
800-543-9038 USA
46
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
SY...120 NEMA 4X Industrial Style Actuators, 120VAC Application: The SY actuators are NEMA 4X rated and designed to meet the needs of HVAC and Commercial applications. Offered on the HSU and HS butterfly valve series, these actuators are available for on/off and modulating applications. Depending on the application, they are available in 24 VAC, 120 VAC and 230 VAC. Technical Data - continued
Models SY1-110(P) SY2-120MFT SY3-120MFT SY4-120MFT SY5-120MFT SY6-120MFT SY7-120MFT SY8-120MFT
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data Power supply Electrical connection Overload protection Motor protection Geartrain Operating range
SY1 SY2... - SY8... SY...-110 SY...-120MFT
Sensitivity SY...-120MFT Feedback SY...120MFT Angle of rotation Direction of rotation Position indication Internal humidity control Auxiliary switches Ambient temperature Humidity range Housing type Housing material Agency listings
800-543-9038 USA
120 VAC 50/60Hz, single phase ½” conduit connector, screw terminals thermally protected 135°C cut-out H class insulation F class insulation high alloy steel gear sets, self locking on/off, floating point 2-10 VDC 4-20mA, 1-5 VDC
SY1-110(P) SY2-120MFT SY3-120MFT SY4-120MFT SY5-120MFT SY6-120MFT SY7-120MFT SY8-120MFT Torque SY1-110(P) SY2-120MFT SY3-120MFT SY4-120MFT SY5-120MFT SY6-120MFT SY7-120MFT SY8-120MFT Manual Override SY1-110(P) SY2-120MFT – SY8-120MFT Running Time SY1-110(P) SY2-120MFT SY3-120MFT SY4-120MFT SY5-120MFT SY6-120MFT SY7-120MFT SY8-120MFT
0.5A 1.0A 1.0A 1.3A 1.5A 1.8A 3.2A 4.0A 35 Nm / 310 in-lbs 90 Nm / 801 in-lbs 150 Nm / 1335 in-lbs 400 Nm / 3560 in-lbs 500 Nm / 4450 in-lbs 650 Nm / 5785 in-lbs 1000 Nm / 8900 in-lbs 1500 Nm / 13350 in-lbs 8mm wrench hand wheel 50hz 13 seconds 17 seconds 26 seconds 18 seconds 25 seconds 31 seconds 55 seconds 55 seconds
60hz 12 seconds 15 seconds 22 seconds 16 seconds 22 seconds 28 seconds 46 seconds 46 seconds
0.2mA / 100mV 2-10 VDC, 4-20mA mechanically limited to 95° reversible top mounted domed indicator resistive heating element (2) SPDT, 5A 250 VAC factory set for 5° and 85° change of state -22°F to +150°F [-30°C to +65°C] up to 95% IP67, NEMA 4X die cast aluminum alloy ISO, CE, cCSAus
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
47
SY...120 NEMA 4X Industrial Style Actuators, 120VAC Wiring Diagrams
Hazard Identification
NOTES SY1-110P
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
G
s Caution: Power supply voltage.
Ground
N L1
4
Power Supply Com
H L2
5
Power Supply Hot
6
Control Signal (-)
s $O NOT CHANGE SENSITIVITY OR DIP SWITCH SETTINGS with power applied.
CAUTION
35
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
Actuator B
G
120 VAC
NOTES SY2...8-120MFT
7
Control Signal (+)
8
Internal Use Only
9
Internal Use Only
10 Internal Use Only
s Caution: Power supply voltage.
11 Feedback (-)
Feedback (B)
Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. Equipment damage! Power consumption and input impedance must be observed.
12 Feedback (+)
36
A
LS3
B C
A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max.
E F
LS4
A-E (Closed Indication)
SY1 -110P
INSTALLATION NOTES G
Observe class 1 and class 2 wiring restrictions.
APPLICATION NOTES 35
36
Control Signal 35
Recommended twisted shielded pair for control wiring. Ground shielded wire at control panel chassis. Tape back ground at actuator.
Actuator A
G
Ground
4
Power Supply Com
5
Power Supply Hot
6
Control Signal (-)
7
Control Signal (+)
8
Internal Use Only
9
Internal Use Only
10 Internal Use Only
Use of feedback is optional.
Feedback (A) Power Supply Com – 120v (N)
11 Feedback (-) 12 Feedback (+)
36
Power Supply Hot – 120v (H)
A
LS3
B A
Internal Use Only
B
Internal Use Only
C
L
Control Signal (+)
Y
1
Internal Use Only
Control Signal (-)
┴1
2
Internal Use Only
Feedback Signal (+)
U5
3
Internal Use Only
Feedback Signal (-)
┴2
Not Used -
C1
Not Used -
C2
8
Internal Use Only
9
Internal Use Only
10
Internal Use Only
E F
35
Adaption
Address
Y1
PE
G
LS4
A-E (Closed Indication)
SY1 -110P
Feedback 36
A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max.
Y2
SYx-120SR/MFT Actuator A
Power Supply Com – 120v (N) Power Supply Hot – 120v (H)
N
A
Internal Use Only
B
Internal Use Only
1
Internal Use Only
L
PC Tool Service Jack
Control Signal (+)
Y
Control Signal (-)
┴1
2
Internal Use Only
Feedback Signal (+)
U5
3
Internal Use Only
Feedback Signal (-)
┴2
Not Used -
C1
Not Used -
C2
Control Signal
A
A-C (Open Indication)
C
Feedback 36
D LS4
35
Adaption
800-543-9038 USA
48
PE
Actuator B
SYx-120MFT
E
Address
Y1
G
LS3
B
8
Internal Use Only
9
Internal Use Only
10
Internal Use Only
F
D-F (Closed Indication) Contact Rating: 5A 250 VAC Max.
Y2
866-805-7089 CANADA
SY2...8-120MFT
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
N
PC Tool Service Jack
SY...230 NEMA 4X Industrial Style Actuators, 230VAC Attention SY Series actuators are fractional horsepower devices, and utilize full-wave power supplies. Observe wire sizing and transformer sizing requirements. Proportional models CANNOT be connected to Belimo direct coupled (AF, AM, GM…etc) actuator power supplies or any type of half-wave device. You MUST use a separate, dedicated transformer or power supply to power the SY actuator. Please do not connect other automation equipment to the dedicated SY supply source. You MUST use four wires (plus a ground) to control a proportional control SY actuator (See SY Wiring Section).
Models SY1-220(P) SY2-230MFT SY3-230MFT SY4-230MFT SY5-230MFT SY6-230MFT
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data Power supply Electrical connection Overload protection Motor protection Geartrain Operating range
SY1 SY2... - SY6... SY...-220 SY...-230MFT SY...-230MFT SY...-230MFT
Sensitivity Feedback Angle of rotation Direction of rotation Position indication Internal humidity control Auxiliary switches Ambient temperature Humidity range Housing type Housing material Agency listings
230 VAC 50/60Hz, single phase ½” conduit connector, screw terminals thermally protected 135°C cut-out H class insulation F class insulation high alloy steel gear sets, self locking on/off, floating point 2-10 VDC, 4-20mA, 1-5 VDC 0.2mA / 200mV 2-10 VDC, 4-20mA mechanically limited to 95° reversible top mounted domed indicator resistive heating element (2) SPDT, 5A 250VAC factory set for 5° and 85° change of state -22°F to +150°F [-30°C to +65°C] up to 95% IP67, NEMA 4X die cast aluminum alloy ISO, CE, cCSAus
800-543-9038 USA
Technical Data - Continued Power consumption SY1-220(P) SY2-230MFT SY3-230MFT SY4-230MFT SY5-230MFT SY6-230MFT Torque SY1-220(P) SY2-230MFT SY3-230MFT SY4-230MFT SY5-230MFT SY6-230MFT Manual Override SY1-220(P) SY2-230MFT – SY6-230MFT Running Time SY1-220(P) SY2-230MFT SY3-230MFT SY4-230MFT SY5-230MFT SY6-230MFT
866-805-7089 CANADA
0.3A 0.5A 0.5A 0.6A 0.7A 0.8A 35 Nm / 310 in-lbs 90 Nm / 801 in-lbs 150 Nm / 1335 in-lbs 400 Nm / 3560 in-lbs 500 Nm / 4450 in-lbs 650 Nm / 5785 in-lbs 8mm wrench hand wheel 50hz 13 seconds 17 seconds 26 seconds 18 seconds 25 seconds 31 seconds
60hz 12 seconds 15 seconds 22 seconds 16 seconds 22 seconds 28 seconds
203-791-8396 LATIN AMERICA / CARIBBEAN
49
SY...230 NEMA 4X Industrial Style Actuators, 230VAC Wiring Diagrams
Hazard Identification
NOTES SY1-220P
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
G
s Caution: Power supply voltage.
Ground
N L1
4
Power Supply Com
H L2
5
Power Supply Hot
6
Control Signal (-)
s $O NOT CHANGE SENSITIVITY OR DIP SWITCH SETTINGS with power applied.
CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
Actuator B
G
230 VAC
35
NOTES SY2...6-230MFT
7
Control Signal (+)
8
Internal Use Only
9
Internal Use Only
10 Internal Use Only
s Caution: Power supply voltage.
11 Feedback (-)
Feedback (B)
Indicates an action or condition that may cause irreversible damage to the actuator(s) or associated equipment. Equipment damage! Power consumption and input impedance must be observed.
12 Feedback (+)
36
A
LS3
B C
A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max.
E F
LS4
A-E (Closed Indication)
SY1 -220P
INSTALLATION NOTES G
Observe class 1 and class 2 wiring restrictions.
APPLICATION NOTES 35
36
Control Signal 35
Recommended twisted shielded pair for control wiring. Ground shielded wire at control panel chassis. Tape back ground at actuator.
Actuator A
G
Ground
4
Power Supply Com
5
Power Supply Hot
6
Control Signal (-)
7
Control Signal (+)
8
Internal Use Only
9
Internal Use Only
10 Internal Use Only
Use of feedback is optional.
Feedback (A) Power Supply Com – 230v (L1)
11 Feedback (-) 12 Feedback (+)
36
Power Supply Hot – 230v (L2)
A
LS3
B A
Internal Use Only
B
Internal Use Only
C
L
Control Signal (+)
Y
1
Internal Use Only
Control Signal (-)
┴1
2
Internal Use Only
Feedback Signal (+)
U5
3
Internal Use Only
Feedback Signal (-)
┴2
Not Used -
C1
Not Used -
C2
8
Internal Use Only
9
Internal Use Only
10
Internal Use Only
E F
35
Adaption
Address
Y1 Y2
PE
G
Actuator A
LS4
A-E (Closed Indication)
SY1 -220P
Feedback 36
A-B (Open Indication) Contact Rating: 5A 125 VAC Max. 3A 250 VAC Max.
SYx-230MFT
Power Supply Com – 230v (L1) Power Supply Hot – 230v (L2)
N
A
Internal Use Only
B
Internal Use Only
1
Internal Use Only
L
PC Tool Service Jack
Control Signal (+)
Y
Control Signal (-)
┴1
2
Internal Use Only
Feedback Signal (+)
U5
3
Internal Use Only
Feedback Signal (-)
┴2
Not Used -
C1
Not Used -
C2
Control Signal
Feedback 36
A
LS3
B A-C (Open Indication)
C D LS4
35
Adaption
E
Address
Y1
8
Internal Use Only
9
Internal Use Only
10
Internal Use Only
F
D-F (Closed Indication) Contact Rating: 5A 250 VAC Max.
Y2 G
800-543-9038 USA
50
PE
Actuator B
SYx-230MFT
866-805-7089 CANADA
SY2...6-230MFT
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
N
PC Tool Service Jack
Ball Valve Dimensions with SY... Series Actuators
B
C
B
B6VS_SYDIM MS
Dimensions with Flanged Valves B2VSS_SYDIMS
Dimensions with 2-Way Valves
C
D
D
Valve Body B2050VS-01 B2050VS-02 B2050VS-04 B2050VS-15 B219VS B220VS B224VS B225VS B232VS B239VS B240VS B249VS B250VS B265VS
COP 600 600 600 600 600 600 600 600 600 600 600 600 600 600
B280VS
600
B2050VSS-15 1000
Valve Nominal Size Inches DN [mm] ½” 15 ½” 15 ½” 15 ½” 15 ¾” 20 ¾” 20 1” 25 1” 25 1¼” 32 1½” 40 1½” 40 2” 50 2” 50 2½” 65 3”
Dimensions (Inches) A 2.25 2.25 2.25 2.25 3.00 3.12 3.37 3.62 3.97 4.37 4.75 4.68 5.37 6.25
B 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 8.00 8.00 8.00 8.00
C 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 6.25 13.00 13.00 13.00 13.00
D 8.00 8.00 8.00 8.00 8.00 3.12 16.00 9.00 9.50 17.50 19.00 19.50 20.00 20.00
80
6.75
8.00
13.00
21.00
½”
15
2.25
8.00
13.00
16.00
¾” 1” 1¼” 1½”
20 25 32 40
3.00 3.37 3.97 4.37
8.00 8.00 8.00 8.00
13.00 13.00 13.00 13.00
18.00 17.00 3.97 18.50
1000
2”
50
4.68
8.00
13.00
19.50
1000 600
2½” 3”
65 80
6.25 6.75
8.00 8.00
13.00 13.00
20.00 21.00
B219VSS B224VSS B232VSS B239VSS
1000 1000 1000 1000
B249VSS B265VSS B280VSS
800-543-9038 USA
A
SY8 SY5 SY4 SY3 SY2
SY3 SY2 SY1 & SY2 SY1 SY3
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
SY2
SY1 & SY2
SY1
A
Valve Body COP B650VS 200 B665VS 200 B680VS
Valve Nominal Size Inches DN [mm] 2” 50 2½” 65
A 7.00 7.50
Dimensions (Inches) B C D 8.00 13.00 22.00 8.00 13.00 22.00
200
3”
80
8.00
8.00
13.00
23.00
B6100VS 200
4”
100
9.00
12.00
15.00
27.00
B6150VS 200
6”
150
10.50
12.00
15.00
29.00
B6200VS 200 B6250VS 200
8” 10”
203 254
11.50 13.00
14.00 14.00
21.00 21.00
39.00 43.00
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
51
MFT Standard Configuration Code
P-10001 P-10002 P-10003 P-10004 P-10005 P-10006 P-10007 P-10009 P-10010 P-10013 P-10015 P-10016 P-10017 P-10018 P-10020 P-10028 P-10031 P-10063 P-10064 P-20001 P-20002 P-20003 P-20004 P-20005 P-30001 P-30002 P-30003 P-30004 P-30005 P-30006 P-40001 P-40002 P-40003 P-40004 P-40005
A01 A02 A03 A04 A05 A06 A07 A09 A10 A13 A15 A16 A17 A18 A20 A28 A31 A63 A64 W01 W02 W03 W04 W05 F01 F02 F03 F04 F05 F06 J01 J02 J03 J04 J05
Control
Motion
Input Range
Position Feedback
Running Time†
Torque %
Adaptation
2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 4.0 to 7.0 VDC 6.0 to 9.0 VDC 10.5 to 13.5 VDC 0.0 to 5.0 VDC 5.0 to 10.0 VDC 5.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 5.0 VDC 2.0 to 6.0 VDC 6.0 to 10.0 VDC 14.0 to 17.0 VDC 9.0 to 12.0 VDC 0.0 to 10.0 VDC 0.0 to 4.0 VDC 0.5 to 4.5 VDC 5.5 to 10.0 VDC 0.59 to 2.93 seconds 0.02 to 5.00 seconds 0.10 to 25.50 seconds 0.10 to 25.60 seconds 0.10 to 5.20 seconds Floating Point Floating Point Floating Point Floating Point Floating Point Floating Point On/Off On/Off On/Off On/Off On/Off
2.0 to 10.0 VDC 0.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 0.5 to 4.5 VDC 5.5 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 0.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 0.0 to 10.0 VDC
150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 100 150 150 150 150 150 150 150 150 150 150 100 100 100 150 75 150 75 100 100
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual
*P-10001 is the default configuration. Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed. Note: V-codes used for NV…Series actuator. All other MFT actuators use P-codes. Note: Most popular configurations available at no additional cost. Note: If the configuration needed is not listed, please fill in pg 54 or call Customer Service. Note: For Non-Spring Return Actuators the 3-digit code can be used in place of the P… pre-set MFT configuration number.
SY MULTI-FUNCTION TECHNOLOGY Description MFT MFT MFT MFT MFT MFT MFT MFT MFT
800-543-9038 USA
52
Code ACE ACF ACH ACJ ACK ACM ACN ACP ACS
Control Input 2-10 VDC 0.5-10 VDC 4-20 mA 2-10 VDC 0.5-10 VDC 4-20 mA 2-10 VDC 0.5-10 VDC 4-20 mA
Built-in Feedback 2-10 VDC 0.5-10 VDC 2-10 VDC 2-10 VDC 0.5-10 VDC 2-10 VDC 2-10 VDC 0.5-10 VDC 2-10 VDC
866-805-7089 CANADA
Loss of Signal stop stop stop open open open close close close
Running Time actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant actuator(s) constant
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off
Floating Point
PWM
Voltage
Configuration (Substitute ‘V’ for ‘P’ for NV actuators)
MFT Programming Codes, Flexible Products PRODUCTS MODEL LMX24-3-X1 LMX24-MFT-X1 NMX24-3-X1 NMX24-MFT-X1 AMX24-3-X1 AMX24-MFT-X1 GMX24-3-X1 GMX24-MFT-X1
Base Actuator Codes LX000 LX100 NX000 NX100 AX000 AX100 GX000 GX100
PWM Floating Point On/Off
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Voltage
Configuration
Torque
Control Input
Feedback
45 in-lbs [5 Nm] 45 in-lbs [5 Nm] 90 in-lbs [10 Nm] 90 in-lbs [10 Nm] 180 in-lbs [20 Nm] 180 in-lbs [20 Nm] 360 in-lbs [40 Nm] 360 in-lbs [40 Nm]
On/Off, Floating Point 2-10 VDC (Default) On/Off, Floating Point 2-10 VDC (Default) On/Off, Floating Point 2-10 VDC (Default) On/Off, Floating Point 2-10 VDC (Default)
— 2-10 VDC — 2-10 VDC — 2-10 VDC — 2-10 VDC
(Substitute ‘V’ for ‘P’ for NV[F] actuators)
Code
P-10001 P-10002 P-10003 P-10004 P-10005 P-10006 P-10007 P-10009 P-10010 P-10013 P-10015 P-10016 P-10017 P-10018 P-10020 P-10028 P-10031 P-10063 P-10064 P-20001 P-20002 P-20003 P-20004 P-20005 P-30001 P-30002 P-30003 P-30004 P-30005 P-30006 P-40001 P-40002 P-40003 P-40004 P-40005
A01 A02 A03 A04 A05 A06 A07 A09 A10 A13 A15 A16 A17 A18 A20 A28 A31 A63 A64 W01 W02 W03 W04 W05 F01 F02 F03 F04 F05 F06 J01 J02 J03 J04 J05
Running Angle of Time Rotation/Stroke 95 (Default) 95 deg 150 (Default) 95 deg 95 (Default) 95 deg 150 (Default) 95 deg 95 (Default) 95 deg 150 (Default) 95 deg 95 (Default) 95 deg 150 (Default) 95 deg
Control
Power Supply 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC 24 VAC/DC
VA Rating 2 5 4 6 5.5 6 6 7
Weight (lbs) 1.10 1.50 1.70 2.10 2.20 2.60 3.40 3.40
Motion
Input Range
Position Feedback
Running Time†
Torque %
Adaptation
2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 4.0 to 7.0 VDC 6.0 to 9.0 VDC 10.5 to 13.5 VDC 0.0 to 5.0 VDC 5.0 to 10.0 VDC 5.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 5.0 VDC 2.0 to 6.0 VDC 6.0 to 10.0 VDC 14.0 to 17.0 VDC 9.0 to 12.0 VDC 0.0 to 10.0 VDC 0.0 to 4.0 VDC 0.5 to 4.5 VDC 5.5 to 10.0 VDC 0.59 to 2.93 seconds 0.02 to 5.00 seconds 0.10 to 25.50 seconds 0.10 to 25.60 seconds 0.10 to 5.20 seconds Floating Point Floating Point Floating Point Floating Point Floating Point Floating Point On/Off On/Off On/Off On/Off On/Off
2.0 to 10.0 VDC 0.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 0.5 to 4.5 VDC 5.5 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 2.0 to 10.0 VDC 0.0 to 10.0 VDC 2.0 to 10.0 VDC 0.0 to 5.0 VDC 0.0 to 10.0 VDC 0.0 to 5.0 VDC None 2.0 to 10.0 VDC None 0.0 to 5.0 VDC 0.0 to 10.0 VDC
150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 100 150 150 150 150 150 150 150 150 150 150 100 100 100 150 75 150 75 100 100
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual
*P-10001 is the default configuration.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
53
Custom MFT Configuration Order Form FAX: USA Toll Free 1-800-228-8283
#1 Select an Actuator (use one sheet for each unique actuator/configuration)
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
AF24-MFT US AF24-MFT-S US NF24-MFT US LF24-MFT US LF24-MFT-S US AF24-MFT95 US NV24-MFT US NVF24-MFT US NVF24-MFT-E US NVFD24-MFT US NVFD24-MFT-E US GMX24-MFT GMX24-MFTX1
Quantity ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
AMX24-MFT AMX24-MFTX1 NMX24-MFT NMX24-MFTX1 LMX24-MFT LMX24-MFTX1 LRX24-MFT GMX24-MFT95 AMX24-MFT95 NMX24-MFT95 LMX24-MFT95 LHX24-MFT LUX24-MFT
Name _______________________________________________________________________________
Quantity ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______
Company ____________________________________________________________________________ Address _____________________________________________________________________________ City_______________________________________ State _____________Zip _____________________ Phone_____________________________________ Fax_______________________________________ Email _____________________________________ FIELD LABELING: LBL-MFT
❑
(-S=Auxiliary Switch)
Custom configuration labels required 1-3/8” X 1-¼” orange labels preprinted to your specifications 12 label sets per sheet. Includes configuration code and wiring labels.
#2 Create a Custom Configuration g
1 Angle of rotation setting
Deactivated (Default)
The following settings
Activated
The following settings mechanical angle of rotation.
-
refer to the full angle of rotation of 95º. are automatically adapted to the effective
Manual triggering by pressing the push button twice. Automatic triggering each time the unit is powered up or by pressing the push button twice. VDC
3 Feedback Signals U5
Floating Point
2 – 10
0.2 to 5.0 seconds
0 – 10
0.1 to 25.5 seconds
Variable
On/Off
0.59 to 2.93 seconds
Start
.
Variable
Stop
.
Start
.
Stop
.
Position Feedback U
DC 2...10 V (Default)
Position Feedback U
DC 0...10 V
Position Feedback U
Start
DC
.
V (0...8 V)
Finish DC
.
V (2...10 V)
The finish must be at least 2 V above the start!
150 seconds (Default) Running time
4 Running Time
5 Override control and
Min. (min. position)
=
%
(0...100%)
(beginning of working range) default 0
ZS
=
%
(0...100%)
(0% = Min.; 100% = Max.) default 50
=
%
(0...100%)
(end of working range) default 100
electronic angle of rotation limiting 800-543-9038 USA
54
seconds (75...300 seconds) (in 5 second increments)
Note:
The sound power level [dB(A)] increases when the running time is below 150 seconds.
(intermediate position)
Max. (max. position)
866-805-7089 CANADA
LM NM AM GM Others
35…150 seconds 45…170 seconds 90…300 seconds 90…300 seconds 75…300 seconds
203-791-8396 LATIN AMERICA / CARIBBEAN
P10415 - 06/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2 Control Types
PWM