COOPER LIGHTING DESCRIPTION The 2HP2-IC is an energy saving solution for a multitude of applica-tions. It uses a high performance T8 system that can s...

17 downloads 694 Views 766KB Size
COOPER LIGHTING - METALUX

®

DESCRIPTION

The 2HP2-IC is an energy saving solution for a multitude of applications. It uses a high performance T8 system that can save up to 40% of energy costs when compared to standard 3-lamp, 18-cell parabolics. The 2HP2-IC incorporates a 2" precision formed louver into a deep prepainted housing. This combination creates a soft, even distribution while delivering a highly efficient T8 luminaire. The luminaire is compatible with all of today’s popular ceiling systems and is Type IC rated for installations when the housing is in direct contact with insulation. The 2HP2-IC series is an excellent choice for commercial office spaces, schools, hospitals or retail merchandising areas.

Type

Catalog # Project

Date

Comments Prepared by

SPECIFICATION FEATURES Construction

E l e c t r i c a l **

Louver

Die formed nominal 4-3/4" deep paracontoured housing made from code gauge, cold rolled steel. Housing features die formed stiffeners for added rigidity along with end plates that securely attach to housing via interlocking tabs. Other housing features include a Grid to T-option (or vice versa) that allows you to do a conversion in the field. End plates also have an integral Grid-Lock feature for safety and convenience. A contoured ballast/wireway cover rests in the center of the housing and can be easily removed without tools, while die formed captive lamp holders encloses lampholder wiring for easy lampholder replacement.

Ballasts are CBM/ETL Class “P” are positively secured by mounting bolts. Pressure lock lampholders. UL/CUL listed for Type IC Recessed Luminaire (Rated for direct contact with insulation) Suitable for damp locations.

Die formed high reflectance white aluminum (standard). Silver with semi-specular finish (optional). Accurate precision parabolic cells are held in place by interlocking feature. True-cut mitered corners. Black reveal with mechanical light seal around entire perimeter of louver. Louver protected by polyethylene cover.

Finish

High reflectance white prepaint (standard). Multistage, iron phosphate pretreatment ensures maximum bonding and rust inhibition. H i n g i n g / L a t ch i n g

Positive cam action spring loaded, self locking, black steel latches with safety lock Thinges allow hinging and latching from either side.

Controls

2HP2-IC 228T8 328T8 232 332

Fifth Light ballast options are offered for both 0-10V continuous dimming and DALI applications. Combine with energysaving products like occupancy sensors, daylighting controls, and lighting relay panels from Cooper Controls (www.coopercontrol.com) to maximize energy savings.

12, 18 Cell 2' X 4' PARABOLIC 2 OR 3 LAMP HIGH PERFORMANCE T8 FOR USE IN INSULATED CEILINGS

4-3/4" [121mm]

23-3/4" [603mm]

ENERGY DATA MOUNTING DATA

Input Watts:

See page 2

HB Ballast & STD Lamps 228T8 (48), 328T8 (71) 232 (53), 332 (80) Luminaire Efficacy Rating LER = FP-79 Catalog Number: 2HP2-IC-232W26P

LAMP CONFIGURATIONS

See page 2

Yearly Cost of 1000 lumens, 3000 hrs at .08 KWH = $3.04

**Reference the lamp/ballast data in the Technical Section for specific lamp/ballast requirements.

CEILING COMPATIBILITY G Grid/Lay-in Standard

G Concealed T

G Slot Grid

F Aluminum Flange Trim With Supporting Swing Gates

MZ Modular Trim With Supporting Swing Gates

Ceiling Type

Trim Type

Exposed Grid Concealed T Slot Grid Flange Concealed “T” or ”Z“ Metal Pan

G G G F MZ MZ

(Verify compatibility/ consult factory.)

COOPER LIGHTING

LAMPS CONTAIN MERCURY. DISPOSE ACCORDING TO LOCAL, STATE OR FEDERAL LAWS

Safe and convenient means of disconnecting power.

ADF110356

2HP2-IC 2’x4’

PHOTOMETRICS

Coefficients of Utilization

rc rw RCR 0 1 2 3 4 5 6 7 8 9 10

2HP2-IC-232W26P Electronic Ballast F32T8/840 lamps 2850 lumens. Spacing criterion: (II) 1.2 x mounting height, (⊥) 1.4 x mounting height. Efficiency = 84.8%. Test Report:

Candela

Effective floor cavity reflectance 80% 70% 70 50 30 10 70 50 30 10 101 93 84 77 71 65 60 55 52 48 45

101 89 78 68 61 54 49 44 40 37 34

101 85 72 62 53 47 41 37 33 30 27

101 82 67 56 48 41 36 31 28 25 23

99 90 82 75 69 63 58 54 50 47 44

99 87 76 67 59 53 48 43 40 36 33

99 84 71 61 53 46 41 36 33 30 27

99 81 67 56 47 41 35 31 28 25 23

20% 50% 50 30 10

30% 50 30 10

10% 50 30 10

0% 0

94 83 73 65 57 51 46 42 38 35 33

90 80 70 62 55 50 45 41 37 34 32

87 77 68 60 54 48 43 40 36 33 31

85 72 60 51 44 38 33 29 26 23 21

94 81 69 59 51 45 40 36 32 29 27

94 78 65 55 47 40 35 31 28 25 23

90 78 67 58 50 44 39 35 32 29 26

Zonal Lumen Summary

Luminance Data

Zone 0-30 0-40 0-60 0-90 0-180

Angle In Deg 45 55 65 75 85

Lumens

%Lamp

%Fixture

1323 2200 3975 4833 4833

23.3 38.6 69.7 84.8 84.8

27.5 45.5 82.3 100.0 100.0

13642

Average 0-Deg cd/sm 2331 2123 1782 1191 945

90 76 64 54 46 40 35 31 28 25 22

87 75 65 56 49 43 38 35 31 28 26

Average 45-Deg cd/sm 2792 2747 2430 1318 1059

87 74 62 53 45 39 35 31 27 25 22

Average 90-Deg cd/sm 3312 3333 2266 1350 1172

Angle 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90

Along II

45°

Across⊥

1674 1660 1625 1571

1674 1673 1665 1646

1674 1680 1697 1694

1502 1422 1331 1231 1120 1000 870 739 604 457 316 187 112 50 0

1603 1543 1462 1374 1288 1198 1090 956 797 623 400 207 123 56 0

1667 1619 1585 1552 1501 1421 1306 1160 967 581 301 212 135 62 0

LER = FP-79 Yearly Cost of 1000 lumens, 3000 hrs at .08 KWH = $3.04

MOUNTING DATA 2 LAMP

Access Plate 7/8" [22mm]

7/8" [22mm] K.O. (2)

23-3/4" [603mm]

3 LAMP

Access Plate 7/8" [22mm] K.O.

7/8" [22mm] K.O. (4)

23-3/4" [603mm]

4-5/8" [119mm]

3" [77mm]

48" [1217mm]

3" [77mm]

7-7/8" [201mm]

4-5/8" [119mm] 48" [1217mm]

7-7/8" [201mm]

LAMP CONFIGURATIONS 3 LAMP – 18 CELL

2 LAMP – 12 CELL

4-3/4" [121mm]

4-3/4" [121mm] 2" [51mm]

10-3/16" [259mm] 23-3/4" [603mm]

2" [51mm]

7" 7" [178mm] [178mm] 23-3/4" [603mm]

Visit our web site at www.cooperlighting.com 4/13 ADF110356

Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801

2HP2-IC 2’x4’

ORDERING INFORMATION Sample Number: 2HP2GX-IC-232W26P-UNV-HB81H-U

Louver Finish I = Semi-Specular/ Haze(Low Iridescent) (Silver Only) P = Painted White (Standard)

Rating Blank =Standard ATW-SW4 =Chicago Rated Heat Removal 1 HR =Heat Removal

4

Option Aluminum Flange Trim Blank = SW (Single White) SN = Single, Natural Finish RN = In Row, Natural Finish RW= In Row, White Finish EN = End of Row, Natural Finish EW = End of Row, White Finish

Width 2 =2' Width Series HP2 = High Performance 2" Paralux Louver Trim Type G =Grid/Lay-in Standard G=Concealed T / Slot Grid

2

F =Aluminum 4 Flange Trim

Voltage 5 120V =120 Volt

MZ =Modular Trim

277V =277 Volt 347V =347 Volt

Air Supply AX =Air Supply Floating Louver

UNV =Universal Voltage 120-277

X =Blank Side/Floating Louver - Non Air Supply

6

Option GL = Single Element Fuse GM = Double Element Fuse WTR= White Reveal Flex = Flex Installed (Reference Flex ordering information) EL = Emergency 7 Installed Lamps Installed Blank = No Lamps Installed L8835 = T8 Lamp, 28W and 32W. 3500K L8841 = T8 Lamp, 28W and 32W. 4100K L88835HL = T8 Lamp, 32W 3500K, 3100k Lumens L88841HL = T8 Lamp, 32W 4100K, 3100 Lumens

AVX =Air Supply Floating Louver w/Directional Air Vane Type IC=IC Rated

Number of Lamps 2 Lamps 3 Lamps 8 Wattage 28T8=28W T8 (48") 32=32W T8 (48")

Louver Color S = Silver W = White

Number of Ballasts 1=1 Ballast 2=2 Ballast 3=3 Ballast Options RIF1 =Radio Interference Suppressor REP=Riveted End Plates Packaging U=Unit Pack PAL=Job Pack, out of carton PALC=Job Pack, in carton

AC C E S S O R I E S

Cell Configuration 26 = 2 Rows of 6, 12 Cell (2’x4’) 36 = 3 Rows of 6, 18 Cell (2’x4’) Notes: 1

Ballast Type High Performance T8 Ballasts HB8 =T8 Electronic Instant Start. Total Harmonic Distortion < 10%. Standard Ballast Factor .86 – .88 HB8 L=T8 Electronic Instant Start. Total Harmonic Distortion < 10%. Low Ballast Factor .77 – .82 HB8 N=T8 Electronic Instant Start. Total Harmonic Distortion < 10%. Normal Ballast Factor 1.0 HB8 H=T8 Electronic Instant Start. Total Harmonic Distortion < 10%. High Ballast Factor 1.15 – 1.20 HR8 T8 Electronic Program Rapid Start. Total Harmonic Distortion < 10%. Standard Ballast Factor .86 – .88 HR8 DIM=T8 Electronic Program Rapid Start. Total Harmonic Distortion < 10%. Step Dimming. Ballast Factor .88 HR8 L=T8 Electronic Program Rapid Start. Total Harmonic Distortion < 10%. Low Ballast Factor .71 – .79 HR8 H=T8 Electronic Program Rapid Start. Total Harmonic Distortion < 10%. High Ballast Factor 1.15 – 1.20 0-10V Dimming Ballasts 10 5LTV8 =T8 0-10V Program Rapid Start. Total Harmonic Distortion < 10%. Ballast Factor 0.87 13, 14 5LTVS8 =T8 0-10V Spec Grade Program Rapid Start. Total Harmonic Distortion < 10%. 11, 12 Ballast Factor 0.87 Fifth Light DALI Ballasts 9 5LT8 =T8 DALI Program Rapid Start. Total Harmonic Distortion < 10%. Ballast Factor 1.0

EQ-CLIP-U=T-BAR Safety Earthquake Clips

3

Note: An EQ Grid Clip is recommended for all 9/16” ceiling systems. Four required per fixture.

Integral End Plate Grid Lock feature not available in Heat Removal

2

Louver is recessed by 5/16" in Concealed T or Slot Grid T.

3

An EQ Grid Clip is recommended for all 9/16" ceiling systems. Four required per fixture.

4

Specify row configuration, type in catalog number when ordering complete fixtures.

5

Products also available in non-US voltage and frequencies for international markets

6

Not available when specifying emergencies, voltage must be specific

7

Fixtures equipped with "EL" option may require a 5-1/2" housing depth. If installing in field, must use low profile battery pack.

8

Standard off-center ballast on 3-lamp fixtures.

9

For a complete listing of Fifthlight Technology products and other solutions from Cooper Controls, visit www.coopercontrol.com

10

0-10V ballast do not include DALI feature. Please select DALI ballast for use with Fifth Light system.

11

Specification grade 0-10V dimming ballast are NEMA premium and CEE listed. They are compatible with low mercury and energy saving lamps.

12

Specification Grade 0-10V ballast not offered in 3 or 4-lamp versions.

13

Standard 0-10V ballast not available for 28W T8 lamps.

14

Voltage must be specified for Standard 0-10V 32W 3 and 4-lamp ballast.

SHIPPING DATA Catalog No. 2HP2-IC-228T8W26P 2HP2-IC-232W36P

Wt. 42 lbs. 42 lbs.

Visit our web site at www.cooperlighting.com 4/13 ADF110356

Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801